- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Daikin
- IM-820
- Instruction manual
Daikin IM-820 Instruction manual
Add to my manuals
24 Pages
Daikin IM-820 is a versatile air conditioner that offers both cooling and heating functions, making it suitable for year-round climate control. It features various modes, including dry mode to remove excess humidity from the air, and heat mode for efficient heating during cooler months. The unit is equipped with a wireless remote control for convenient operation, and an optional wired wall control for added flexibility. It also includes electrostatic filters for improved air quality.
advertisement
Installation and Maintenance Manual IM-820
Group: Unitary
Part Number: IM-820
Date: March 2005
Supersedes: New
MCM Ceiling/Floor Convertible Split Type Air Conditioner
Indoor Unit
Wireless Remote
Control (Standard)
Outdoor Unit
© 2005 Daikin
IM 820
Wired Wall
Control (Optional)
Page 1
Table of Contents
Model Numbers . . . . . . . . . . . . . . . . . . . . . 2
General Information . . . . . . . . . . . . . . . . . . 3
Safety Precautions .......................................3
Unit Dimensions . . . . . . . . . . . . . . . . . . . . 4
Indoor Units ..................................................4
Outdoor Units ............................................... 4
Installation Guidelines . . . . . . . . . . . . . . . 5
Installation Diagram .....................................5
Installation of Outdoor Unit ...........................5
Installation of the Indoor Unit .......................6
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Indoor Unit Clearances . . . . . . . . . . . . . . . . 6
Standard Mounting . . . . . . . . . . . . . . . . . . . 7
Semi-enclosed Mounting . . . . . . . . . . . . . . 7
Refrigerant Tubing . . . . . . . . . . . . . . . . . . 8
Tubing Length & Elevation . . . . . . . . . . . . . 8
Tubing Preparation . . . . . . . . . . . . . . . . . . . 8
Tubing Connection To Units . . . . . . . . . . . . 8
Electrical Connections . . . . . . . . . . . . . . . 9
Wiring Diagrams . . . . . . . . . . . . . . . . . . . 10
Evacuating and Charging . . . . . . . . . . . . 17
Evacuating the tubing and the indoor unit . 17
Model Numbers
Cooling Only
Indoor Unit
MCM20D
MCM25D
MCM30D
MCM40D
MCM50D
Cooling/Heat Pump
Indoor Unit
MCM20DR
MCM25DR
MCM30DR
MCM40DR
MCM50DR
Outdoor Unit
MLC20BR
MLC25BR
MLC30CR
MLC40CR
MLC50CR
Outdoor Unit
MLC20B
MLC25B
MLC30C
MLC40C
MLC50C
Additional charge . . . . . . . . . . . . . . . . . . . .17
Charge operation . . . . . . . . . . . . . . . . . . . . 17
Remote Controller Operation Guide . . . .18
Netware 2 - Wired Wall Control (Optional) 19
Special Features . . . . . . . . . . . . . . . . . . . .20
Dry mode . . . . . . . . . . . . . . . . . . . . . . . . . .20
Heat mode (heat pump only) . . . . . . . . . . .20
Overheating protection (heat pump only) . .20
Frost prevention . . . . . . . . . . . . . . . . . . . . .20
Fan speed and rated cooling capacity . . . .20
Operating Conditions ................................. 20
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Overall Checking . . . . . . . . . . . . . . . . . . . .20
Unit Indicator Lights . . . . . . . . . . . . . . . . 21
IR signal receiver . . . . . . . . . . . . . . . . . . . .21
Netware 2 - Wired Wall Control (Optional) .21
Service and Maintenance . . . . . . . . . . . . 22
Electrostatic Filters . . . . . . . . . . . . . . . . . . 22
Filter Replacement . . . . . . . . . . . . . . . . . . .22
Startup After Extended Shutdown . . . . . . .22
Troubleshooting . . . . . . . . . . . . . . . . . . . . .22
Service and Maintenance . . . . . . . . . . . . . .23
Nominal Cooling - BTUH
20,000
24,000
30,000
40,000
50,000
Nominal Cooling - BTUH
20,000
25,000
30,000
40,000
50,000
Nominal Heating - BTUH
21,000
25,000
32,000
41,000
48,000
Page 2 IM 820
General Information
This manual provides the installation procedures so your air conditioner unit operates properly and provides you the service it was designed to provide.
Special adjustment may be necessary to suit local requirements. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
Safety Precautions
Before installing the air conditioner unit, please read the following safety precautions carefully..
WARNING
• The installer must determine and follow all applicable codes and regulations. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can cause property damage, equipment damage, severe personal injury or death. This equipment must be installed by experienced, trained personnel only.
• Do not allow flammable fumes near unit or areas sharing ventilation.
• Installation and maintenance must be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance.
• All field wiring must be done in accordance with industry standards and local codes.
• Inspect the unit nameplate to be certain the voltage is the same as the voltage that will be delivered to the unit. Improper electrical wiring can cause property damage, sever personal energy or death.
• The unit must be GROUNDED.
• Make sure wiring does not touch refrigerant piping, compressor, or any moving parts of the fan motors.
• Confirm that the power supply is switched OFF before installing or servicing the unit.
WARNING
Hazardous Voltage!
Disconnect all electrical power including remote disconnects before servicing. Failure to disconnect power before servicing can cause severe personal injury or death.
CAUTION
Use copper conductors only. Unit terminals are not designed to accept other types of conductors. Failure to do so can cause damage to the equipment.
CAUTION
• Do not install in a laundry room. Humidity and laundry chemicals can corrode unit components.
• Do not install the unit where leakage of flammable gas may occur. If gas leaks and accumulates around the unit, it can cause a fire.
• Connect drainage piping properly. If drainage piping is not connected properly, water leakage can cause property damage.
• Do not overcharge the unit. This unit is factory precharged. Overcharge will cause over-current or damage to the compressor.
• Keep panel closed. Unsecured panels will cause the unit to operate noisily.
NOTICE
This product was carefully packed and thoroughly inspected before leaving the factory. Responsibility for its safe delivery was assumed by the carrier upon acceptance of the shipment. Claims for loss or damage sustained in transit must therefore be made upon the carrier, as follows:
VISIBLE LOSS OR DAMAGE
Any external evidence of loss or damage must be noted on the freight bill or carrier’s receipt, and signed by the carrier’s agent. Failure to adequately describe such external evidence of loss or damage may result in the carrie’s refusing to honor a damaged claim. The form required to file such a claim will be supplied by the carrier.
CONCEALED LOSS OR DAMAGE
Concealed loss or damage means loss or damage which does not become apparent until the product has been unpacked. The contents may be damaged in transit due to rough handling even though the carton may not show external damages. When the damage is discovered upon unpacking, make a written request for inspection by the carrier’s agent within fifteen (15) days of the delivery date. File a claim with the carrier since such damage is the carrier’s responsibility.
IM 820 Page 3
Unit Dimensions
Indoor Units
A
B
C E
Two mounting brackets shipped attached to the indoor unit. See page 7 for more detail.
F
Model MCM
A
B*
C
D
E
F
G
H
*Discharge air opening width.
Outdoor Units
20D/DR
46 1/4"
42 1/2"
47 3/4"
26 1/2"
6 1/4"
2 1/4"
20 1/2"
22"
25D/DR
46 1/4"
42 1/2"
47 3/4"
26 1/2"
6 1/4"
2 1/4"
20 1/2"
22"
D
G H
30D/DR
46 1/4"
42 1/2"
47 3/4"
26 1/2"
6 1/4"
3 3/4"
20 1/2"
22"
40D/DR
66"
62 1/4"
67 1/2"
26 1/2"
6 1/4"
3 3/4"
20 1/2"
22"
A
50D/DR
66"
62 1/4"
67 1/2"
26 1/2"
6 1/4"
3 3/4"
20 1/2"
22"
B
E
C
D
Page 4
Model MLC
A
B
C
D
E
20 & 25 B/BR
16"
33"
25 1/2"
2 1/4"
13 1/4"
30,40 & 50C/CR
19 1/4"
40 1/2"
33 1/2"
3 1/2"
15 3/4"
IM 820
Installation Guidelines
Installation Diagram
INDOOR UNIT
Air Discharge Swing Baffle
IR Receiver and
LED Indicator Lights
Air Discharge Grille
Air Intake Grille
Air Filters
Optional Wired
Wall Control
Refrigerant Tubing and Insulation
Air Intake
Wireless IR
Remote Control
Air Intake
Air Discharge Nozzle
OUTDOOR UNIT
Installation of Outdoor Unit
Install the outdoor unit in a manner to prevent mixing hot discharged air with return air flow. Also, the unit should be a suitable distance from obstructions See Figure 1 for minimum installation clearances. Double the dimensions shown if surroundings are more than 72" tall, or if there is an obstruction on top. Select the coolest possible place where intake air temperature is not greater than the outside air temperature
(maximum 113°F). See Table 1, Page 7 for weight of outdoor unit.
Figure 1. Outdoor Unit Minimum Clearances
12"
Min.
40"
Min.
Air
Intake
Air
Discharge
12"
Min.
Air
Intake
20"
Min.
Service
Access
IM 820 Page 5
Installation of the Indoor Unit
General
Electrical supply and installation must conform to local codes and regulations.
Voltage supply fluctuation must not exceed ±10% of the rated voltage. Electricity supply lines must be independent of welding transformers which can cause high supply fluctuation.
Figure 2. Indoor Unit Minimum Clearances
Locate the installation for convenient wiring and piping.
Indoor Unit Clearances
The indoor unit must be installed in a manner to prevent mixing the cool discharged air with the hot return air. Follow the installation clearances shown in Figure 2. Do not place the indoor unit in direct sunlight. The location must be suitable for piping and drainage, and be away from doors or windows.
.1/2" min.
12" min.
CEILING MOUNT
19.68"
10" max.*
*Appliances, furniture or built-in architectural features must not extend more than 10".
16" min.
40" min.
WALL/FLOOR MOUNT
Page 6 IM 820
Standard Mounting
Make sure the ceiling or wall is strong enough to support the weight of the unit (See Table 1). Remove the mounting brackets from the unit and secure to wall or ceiling as required.
The unit must be level front to back and sloped 1/8" towards condensate drain (See Figure 3).
Table 1: Unit Weight - lbs.
Model
Weight ID Unit
20
95
Weight OD Unit 125
25
99
128
30
99
209
40
154
220
50
154
231
Figure 3. Slope for condensate drainage
Semi-enclosed Mounting
In case the unit is to be half-recessed into a false ceiling, make sure the unit is well-aligned with the ceiling.
Provide the installation space as shown in Figure 4.
Figure 4. Semi-enclosed Mounting
12" min.
48" min.
1/2" min.
23"
12" min.
Top Panel of Unit
22" 1/2"
Ceiling Mount Slope
1/8"
Mounting Surface
Ceiling Board
1/2"
6.3/4"
1/2"
Wall/Floor Mount Slope
IM 820 Page 7
Refrigerant Tubing
Tubing Length & Elevation
Copper tubing to connect the indoor and outdoor units is supplied by others or it can be ordered from the factory. See
Table 2 and Figure 5 for requirements.
Table 2: Refrigeration Tubing Requirements
Model
Maximum Length, ft.
Max. elevation, ft, H
Max. number of bends
Liquid tube size - OD
Gas tube size - OD
20
49’
26’
10
1/4"
5/8"
25
49’
26’
10
3/8"
5/8"
30
115’
49’
10
3/8"
5/8"
40
115’
49’
10
3/8"
3/4"
50
115’
49’
10
3/8"
3/4"
Note: The refrigerant pre-charged in the outdoor unit is for tubing length up to 25 ft. See Table 7 for additional R-22 refrigerant required on runs longer than 25 ft.
Figure 5. Tubing length and elevations
• Remove burrs from cut ends by holding tubing downwards to prevent metal chips from entering the tubing.
• Slide the flare nuts, for both the indoor unit and outdoor unit onto the copper tubing.
• Flare the tubing as shown in Figure 6 and Table 3.
• The flare must be even and not cracked or scratched.
Figure 6. Cutting and Flaring Tube
Cutting Copper Tube
1/4 Tube
Indoor Unit
Copper Tube
Flaring Tool
See Table 3
X
Elevation
Outdoor Unit
Elevation
Outdoor Unit
Table 3: Tube Flaring Dimensions
Tube Diameter - OD
Inch Imperial
1/4
3/8
5/8
.051
.063
.087
Tubing Connection To Units
X (in.)
Rigid
.028
.039
.067
• Connect the copper tubing to both the indoor and outdoor units (See Figure 7).
• Torque each flare nut to specifications (See Table 4).
• Cover both tubes individually with 3/8" wall foam insullation.
Figure 7
Flared Tube
Indoor Unit
Tubing Preparation
• Do not use contaminated or damaged copper tubing. Do not remove plastic, rubber plugs or brass nuts from the valves, fittings, tubings and coils until you are ready to connect suction or liquid line into valves or fittings.
• If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the brazing work is done. This will eliminate soot formation on the inside wall of the copper tubing.
• Cut the copper tubing with a tube cutter (See Figure 6).
Page 8
Unit Fitting
Table 4:
Tube Size (in.)
1/4
3/8
5/8
Flare Nut
Torque (ft./lb.)
13.3
31.0
48.0
IM 820
Electrical Connections
WARNING
Improper installation can cause severe personal injury or death. Wiring must be done by a qualified technician in compliance with local codes.
• Wiring must be in accordance with all applicable electrical codes.
• Wires must not touch the refrigerant piping, compressor or any moving part.
• All electrical field wiring must be clamped at both the indoor unit and the outdoor unit.
Note: Field install 10A fuse in outdoor unit as shown in wire diagrams for unit sizes 30, 40, and 50.
• See Table 5, and 6 for the number of wires, wire gage and fuse/circuit breaker size required.
• NEC requires an approved electrical disconnect within sight of the unit so that anyone working on the unit can turn off the power and see that its not accidently turned back on. This will require two disconnects, one by the outdoor unit and one by the indoor unit.
Table 5: Wire, Fuse/Breaker Requirements - Cooling
Only
20 25 40 50 Unit Size
Voltage - 60Hz. 1 Ph.
Power supply wire size
No. of 12 ga. wires between units
Fuse/Breaker size
12 ga.
10 ga.
30
208/230
8 ga.
8 ga.
6 ga.
2 + gnd.
2 + gnd 3 + gnd 3 + gnd 3 + gnd
20 amp.
25 amp.
35 amp.
40 amp.
55 amp.
Table 6: Wire, Fuse/Breaker Requirements - Heat
Pump Only
Unit Size 20 25 30 40 50
Voltage - 60Hz. 1 Ph.
Power supply wire size 12 ga.
10 ga.
208/230
8 ga.
8 ga.
6 ga.
No. of 12 ga. wires between units*
Fuse/Breaker size
4 + gnd.
4 + gnd 6 + gnd 6 + gnd 6 + gnd
20 amp.
25 amp.
35 amp.
40 amp.
55 amp.
* Not including the low voltage OD coil sensor cable.
IM 820 Page 9
Wiring Diagrams
MODEL MCM20D/25D INDOOR UNIT- COOLING ONLY
RETURN AIR SENSOR
ROOM
JH
INDOOR COIL SENSOR
ID
OD
CN4
CN6
L
TRANSFORMER
WIRED
WALL
CONTROL
(OPTIONAL)
WIRELESS
REMOTE
CONTROLLER
AS
LOW MED
COMP.
LIVE
N2
N1
NOTE: DISCONNECT CN6
IF CN4 IS USED
KEY:
---- - FIELD SUPPLY WIRING
AS - AIR SWING MOTOR
BLACK
RED
AS
WHITE
BLUE
YELLOW
BLACK
G/Y
BLACK
BLACK
GREEN/YELLOW
COMP.
L N N
FL
FM
FH
AC IC
MC
FAN MOTOR
GREEN/YELLOW
L2
L1
} 208/230V
1 PHASE
60Hz
12 GA. WIRE
COMP N
Page 10
BROWN
FAN
MOTOR
C
COMPRESSOR
S
R
RED
CAPACITOR
BLUE
GREEN/YELLOW
BLUE
BLUE BLUE
CAPACITOR
RED
WHITE
MODEL MLC20B/25B OUTDOOR UNIT
IM 820
IM 820
MODEL MCM 030D INDOOR UNIT- COOLING ONLY
RETURN AIR SENSOR
ROOM
INDOOR COIL SENSOR
ID
OD
CN4 CN6
L
WIRED
WALL
CONTROL
(OPTIONAL)
WIRELESS
REMOTE
CONTROLLER
NOTE: DISCONNECT CN6
IF CN4 IS USED
TRANSFORMER
AS
LOW MED
COMP.
LIVE
N2
N1
RED BLUE
WHITE
BLUE
YELLOW
AS
BLACK
BLACK
GREEN/YELLOW
KEY:
---- - FIELD SUPPLIED WIRING
AS - AIR SWING MOTOR
COMP. L N
FL
FM
FH
A.C.
I.C.
MC
FAN MOTOR
GREEN/YELLOW
12 GA. WIRE
208-230V
1 PH
60HZ
{
L2
L1
*NOTE: FIELD INSTALL 10A FUSE
IN BLUE AND RED WIRE AS SHOWN
RED
L N
BLUE
S
CAP.
R COMP.
L
BLUE
*10A
N
G/Y
RED
*10A
RED
1
2
RED REDRED
R/L1S/L2 T/L3 A1
HIGH / LOW
RED
PRESSURE SWITCH
A C
MAGNETIC
RED
BLUE
U/T1V/T2 W/T3 A2
CONTACTOR
BLUE BLUE
REDRED
BLACK
RED
WHITE
RED
BLACK
BLUE
WHITE
C
S
R
RED
RED
BROWN
COMPRESSOR CRANKCASE
HEATER
BROWN
FAN
MOTOR
G/Y
MODEL MLC30C OUTDOOR UNIT
Page 11
MODEL MCM40D/50D INDOOR UNIT- COOLING ONLY
RETURN AIR SENSOR
ROOM
INDOOR COIL SENSOR
ID
WIRED
WALL
CONTROL
(OPTIONAL)
WIRELESS
REMOTE
CONTROLLER
NOTE: DISCONNECT CN6
IF CN4 IS USED
CN4
CN6
TRANSFORMER
L
AS
LOW MED
COMP.
LIVE
N2
N1
KEY:
---- - FIELD SUPPLIED WIRING
AS - AIR SWING MOTOR
RED
BLACK
AS
BLUE
WHITE
BLUE
YELLOW
BLACK
GREEN/YELLOW
COMP. L/L1 N/L2
FM
FH
FL
A.C.
I.C.
MC
FAN MOTOR
GREEN/YELLOW
208-230V
1 PH
{
60Hz
L2
L1
12 GA. WIRE
*NOTE: FIELD INSTALL 10A FUSE
IN BLUE AND RED WIRE AS SHOWN
L/L1 N/L2
REDRED RED
1L1 3L2 5L3
1
2T1 4T2 6T3
REDRED
2
COMP. L/L1 N/L2
RED
*10A FUSE
BLUE
GREEN/YELLOW
BLUE
*10A FUSE
RED
RED
8
A1
A2
7
BLUE BLUE
RED 2
6
LOCK OUT
RELAY
HIGH
PRESSURE
SWITCH
BLUE
PURPLE
BLACK
LOW
PRESSURE
SWITCH
BLACK
RED
WHITE
WHITE
RED
RED
C
BROWN
COMPRESSOR
R
S
CRANKCASE
HEATER
BROWN
FAN
MOTOR
G/Y
BLUE
MODEL MLC40C/50C OUTDOOR UNIT
Page 12 IM 820
IM 820
MODEL MCM20DR/25DR INDOOR UNIT - HEAT PUMP
RETURN AIR SENSOR
ROOM
JH
INDOOR COIL SENSOR
ID
OD
CN4 CN6
WIRED
WALL
CONTROL
(OPTIONAL)
WIRELESS
REMOTE
CONTROLLER
NOTE: DISCONNECT CN6
IF CN4 IS USED
4WV
RMODE
AS
LOW MED
TRANSFORMER
L
COMP.
LIVE
N2
N1
4WV OF COMP.
L
BLACK
BLACK
BLACK
RED
AS
BLUE
WHITE
BLUE
YELLOW
G/Y
GREEN/YELLOW
N N
KEY:
---- - FIELD SUPPLIED WIRING
AS - AIR SWING MOTOR
4WV - 4 WAY VALVE
FL
FM
FH
A.C.
I.C.
MC
FAN MOTOR
GREEN/YELLOW
L2
L1
208-230V
1 PH
60Hz
LOW VOLTAGE CABLE TO
OUTDOOR COIL SENSOR
12 GA. WIRE
TH2
BLACK
BLACK
BLACK
BROWN
BROWN
4WV OF COMP.
N
FAN
MOTOR
RED
BLUE
WHITE
MOTOR
C
CONPRESSOR
S
RED
R
BLUE
BLACK
4V
KEY:
---- - FIELD SUPPLIED WIRING
4V - 4 WAY VALVE
TH2 - OUTDOOR THERMISTOR
AS - AIR SWING MOTOR
MOEL MLC20BR/25BR OUTDOOR UNIT
BLACK
Page 13
208-230V
1 PH
{
60Hz
L2
L1
MODEL MCM 30DR INDOOR UNIT - HEAT PUMP
RETURN AIR SENSOR
ROOM
JH
INDOOR COIL SENSOR
TO OUTDOOR
DEFROST SENSOR
ID
OD
CN4 CN6
WIRED
WALL
CONTROL
(OPTIONAL)
WIRELESS
REMOTE
CONTROLLER 4WV
RMODE
TRANSFORMER
AS
LOW MED
L
COMP.
LIVE
N2
N1
NOTE:
DISCONNECT CN6
IF CN4 IS USED:
RED
AS
BLUE
YELLOW
WHITE
BLUE
FL
FM
FH
BLACK
GREEN/YELLOW KEY:
---- - FIELD SUPPLIED WIRING
AS - AIR SWING MOTOR
4WV - 4 WAY VALVE
A 4WV OF COMP.
L N
A.C.
I.C.
MC
FAN MOTOR
GREEN/YELLOW
LOW VOLTAGE CABLE TO
OUTDOOR COIL SENSOR
12 GA. WIRE
Page 14
RED
21
22
REDRED
L1
T1
L
L2
T2
REDRED
N
RED
L3
T3
13
14
C
COMPRESSOR
R
S
CRANKCASE
HEATER
BLUE
*10A FUSE
GREEN/YELLOW
*10A FUSE
A 4WV OF COMP.
L
BLUE
RED
4WV
WHITE
A1
A2
BLACK
BLUE
HIGH
PRESSURE
SWITCH
BLACK
FAN
MOTOR
N
G/Y
*NOTE: FIELD INSTALL 10A FUSE
IN BLUE AND RED WIRE AS SHOWN
MODEL MLC30CR - OUTDOOR UNIT
IM 820
208-230V
1 PH
{
60Hz
L2
L1
MODEL MCM 40DR/50DR INDOOR UNIT
RETURN AIR SENSOR
ROOM
INDOOR COIL SENSOR
TO OUTDOOR
DEFROST SENSOR
ID
OD
CN4
CN6
WIRED
WALL
CONTROL
(OPTIONAL)
WIRELESS
REMOTE
CONTROLLER
4WV
JH
RMODE
TRANSFORMER
L
AS
LOW MED
COMP.
LIVE
N2
N1
KEY:
---- - FIELD SUPPLIED WIRING
AS - AIR SWING MOTOR
A 4WV OF COMP.
L
L1
N
L2
RED
AS
BLUE
WHITE
YELLOW
BLACK
BLACK
GREEN/YELLOW
FL
FM
FH
A.C.
MC
I.C.
FAN MOTOR
GREEN/YELLOW
LOW VOLTAGE CABLE TO
OUTDOOR COIL SENSOR
12 GA. WIRE
IM 820
RED
1L1
2T1
RED
L
3L2
4T2
L1
N
REDRED
6T3 2
REDRED
L2
RED
5L3 1
CRANKCASE
HEATER
C
COMPRESSOR
R
S
BLUE
*10A FUSE
GREEN/YELLOW
*10A FUSE
A 4WV OF COMP. L
L1
N
L2
BLUE
RED
4WV
PURPLE
A1
A2
BLACK
BLUE
HIGH
PRESSURE
SWITCH
BLUE
FAN
MOTOR
G/Y
*NOTE: FIELD INSTALL 10A FUSE
IN BLUE AND RED WIRE AS SHOWN
MODEL MLC40CR/50CR
Page 15
Page 16
MODEL : MLC 20B - 25B OUTDOOR UNIT - COOLING ONLY
- OPTIONAL LOW AMBIENT KIT (208/230V - 1 PHASE - 60HZ)
CM
C
S
R
WHITE
OL
RED
CAPACITOR
BLUE
GREEN/YELLOW
BLUE BLUE
CAPACITOR
FM
YELLOW
ORANGE
OUTDOOR COIL SENSOR
KEY
CM - COMPRESSOR MOTOR
FM - OUTDOOR FAN MOTOR
FSCM - FAN SPEED CONTROL MODULE
12 GA. FIELD SUPPLIED WIRING
1 2 3 4 5
FSCM
COMP N
(TO INDOOR UNIT)
MODEL : MLC 20BR - 25BR OUTDOOR UNIT - HEAT PUMP
- OPTIONAL LOW AMBIENT KIT (208/230V - 1 PHASE - 60HZ)
KEY
FM - FAN MOTOR
CM - COMPRESSOR MOTOR
4V - 4 WAY VALVE
TH2 - OUTDOOR THERMISTOR
FSCM - FAN SPEED CONTROL MODULE
12 GA. FIELD SUPPLIED WIRING TH2
BLACK
BLACK
(TO INDOOR UNIT)
4V OF COMP.
BLACK
N E
BROWN BLUE
E
4 3 2 1
FSCM
E
FM
RED
BLACK
4V
C
R CM
S
RED
BLUE
BLUE
BLACK
IM 820
Evacuating and Charging
Evacuating the tubing and the indoor unit
The outdoor unit is pre-charged with refrigerant R-22. The indoor unit and the refrigerant connection tubing must be evacuated as follows:
1.
Remove the 3 caps from the valves on the outdoor unit.
2. Connect the center of the charging gauge to the vacuum pump.
3. Connect the charging gauge to the service port of the
3-way valve (See Figure 9).
4. Start the pump and evacuate to -760 mm Hg (-29.9" Hg).
5. Close the valve of the changing gauge and stop the vacuum pump.
6. On the outdoor unit, open both valves using a 4 mm
Allen wrench (See Figure 8).
Figure 8. 3-way Suction Valve on Outdoor Unit
Hex Socket for 4 mm
Allen wrench
Flare Nut
Refrigerant
Tubing
Service
Port
Outdoor Unit
3-way Valve
Table 7: Additional R-22 ounces per foot of tubing
(when tubing length is more than 25 ft.) and maximum tubing length.
Model
20D
25D
30D
40D
50D
20DR
25DR
30DR
Oz. Per ft.
.16
.40
.53
.55
.55
.16
.50
.53
Max. Length
49’
49’
115’
115’
115’
49’
49’
115’
40DR
50DR
.55
.55
115’
115’
Charge operation
This operation must be done by weighing the R-22 being added thru the service port on the 3-way suction valve.
See Table 7 and Figure 10.
1.
Remove the service port cap.
2. Connect the low pressure side of the charging gauge to the suction service port center of the cylinder tank and close the high pressure side of the gauge. Purge the air from the service hose (See Figure 10).
3. Start the air conditioner unit.
4. Open the gas cylinder and low pressure charging valve.
5. When the required refrigerant quantity is pumped into the unit, close the low pressure side and the gas cylinder valve.
6. Disconnect the service hose from service port. Put back the service port cap.
Figure 9 Evacuation Schematic
Indoor Unit
Liquid side
Outdoor Unit
Discharge Valve
Close
Gas side
Vacuum
Pump
Close
Suction Valve
Low
Press.
High
Press.
Figure 10. Charging Schematic
Indoor Unit
Liquid side
Gas side
Outdoor Unit
Discharge Valve
Suction Valve
Low
Press.
High
Press.
Additional charge
The refrigerant is pre-charged in the outdoor unit. If the tubing length between the indoor and outdoor unit is no more than 25 ft.
, then an additional charge after evacuation is not necessary. If the tubing length is more than 25 ft., use additional R-22 as indicated in Table 7.
IM 820 Page 17
Remote Controller Operation Guide
Transmission source
• The source where the signal is transmitted.
Signal Transmission Indication
• Blinks to confirm the last setting was sent to the unit.
Temperature Setting
• Set the desired room temperature by pressing the buttons to increase or decrease the set temperature.
• The temperature setting range is from 60°F to 86°F.
• Press both buttons simultaneously to toggle the temperature setting between °C and °F.
Fan Speed Selection
• Press the button until the desired fan option displays (auto, low, med. or high). "Auto" automatically selects high fan until room temperature is within 2 o
F of setting, then switches to low fan. Fan runs continuouse in COOL and cycles in
HEAT.
ON Timer Setting
• Press the SET button will activate the on timer function.
• Set the desired on time by pressing the SET button continuously. If the timer is set to 7.30am, the air conditioner will turn on at 7.30 sharp.
• Press the CLR button to cancel the on timer setting.
Automatic Air Swing
• Press the SWING button to activate the automatic air swing function.
• To distribute the air to a specific direction, press the SWING button and wait until the air conditioner baffle swings to the desired direction. Press the button again to hold it.
Clock Time Setting
• Press button + or - to increase or decrease the clock time.
On/Off Button
• Press once to start the air conditioner.
• Press again to stop the air conditioner.
Operation mode
• Press the MODE button to select the type of operating mode.
• For cooling only unit, the available modes are : COOL, DRY & FAN.
• For heat pump unit, the available modes are: AUTO, COOL, DRY,
FAN & HEAT.
OFF Timer Setting
• Press the SET button will activate the off timer function.
• Set the desired off time by pressing the SET button continuously.
• Press the CLR button to cancel the off timer setting.
Sleep mode setting
• Press the button to activate sleep mode. This function is available under COOL, HEAT & AUTO mode.
• In COOL mode, the set temperature will increase 1.0°F after 30 minutes,
2°F after 1 hour and a total of 4°F after 2 hours.
• In HEAT mode, the set temperature will decrease 2°F after 30 minutes,
4°F after 1 hour and a total of 5°F after 2 hours.
Symbol Identification
Auto low med high
Cool Dry Fan Heat Sleep Power Timer Auto Fan Speed
Page 18 IM 820
Netware 2 - Wired Wall Control (Optional)
SET CLOCK
SLEEP
AUTO
FAN
DRY AUTO COOL HEAT FAN
SLEEP
SWING
MON TUE WED THU FRI SAT SUN
AM
PM
TIME ACTIVATE SET TIMER
ON
OFF
SET CLOCK
COOL
TEMP.
HEAT
TEMP.
ROOM
TEMP.
MODE
˚F
˚C
ON/OFF
SET TEMP
Features:
1.
Modes - Cool, Heat, Auto, Dry, Fan and Off.
2. Temperature Range - 60° F to 86° F. (Press both arrows simultaneously to convert from °C to °F.)
3. Timer - Seven day clock capable of a different On/Off time for each day of the week. Note: Hold button is used to temporarily override timer.
4. Shows time of day.
5. Electronic lockout to prevent tampering.
6. Fan Speeds - Low, medium, high and auto.
7. Sleep - Sets temperature back for sleeping.
8. Swing - Swings or positions air baffle for better air distribution.
9. Display normally shows room temperature. (Momentarily shows set point when a change is made.)
SWING
HOLD
CLOCK
ON TIMER
DAY
OFF TIMER
HOUR MINUTE
(heat pump only).
11. Error codes blink on display:
E1 - Room sensor loose or defective.
E2 - Indoor coil sensor loose or defective.
E3 - Outdoor coil sensor loose or defective.
E4 - Compressor cycling on overload.
E5 - Low refrigerant charge.
For more detail, see manual that ships with the Wall Control.
IM 820 Page 19
Special Features
Dry mode
• Select this mode when the standard Cool mode does not provide sufficient dehumidification. The compressor and indoor low fan will cycle together and will operate for longer periods of time to provide the increased rate of dehumidification. As a result, the room temperature differential may increase slightly.
Heat mode (heat pump only)
• When the unit is switched on from cold start or defrosting cycle, the indoor fan will start to operate only after the coil warms up.
• When the set temperature is achieved, the indoor fan will operate until the coil cools down.
Overheating protection (heat pump only)
• In case the coil overheats (145°F), the compressor will cut out.
Frost prevention
• If the indoor coil starts to frost, an LED light will blink to indicate that the unit is in defrost.
Fan speed and rated cooling capacity
• The rated cooling capacity is provided at high indoor fan speed.
• The cooling capacity is slightly lower when the unit is operating at MEDIUM and LOW fan speed.
Operating Conditions
Cooling
Temperature
Minimum Indoor
Maximum Indoor
Minimum Outdoor
Maximum Outdoor
Ts (dry bulb) °F
61
90
66*
114
Th (wet bulb) °F
52
73
24
75
* 32
Kit.
° F on size 20 and 25, 23 ° F on size 30, 40 and 50 with optional Low Ambient
Heating (heat pump only)
Temperature
Minimum Indoor
Maximum Indoor
Minimum Outdoor
Maximum Outdoor
Ts °F
61
86
16
75
Ts = Dry Bulb Temperature, Th = Wet Bulb Temperature
Th °F
—
—
21
64
Overall Checking
Ensure that:
1. The unit has been mounted properly.
2. Refrigerant tubing connections have been checked for leaks
3. Proper wiring and circuit breakers have been installed.
Drainage check:
Check condensate drain for leaks and proper flow.
Test run:
Check the following items:
• Are all electrical plugs firmly inserted into there receptcales?
• Is there any abnormal sound from the unit?
• Is there any abnormal vibration on the unit itself or piping?
Confirm that:
1. Condenser fan is running, with warm/cold air blowing off the outdoor unit. (Cooling only/Heat Pump)
2. Evaporator blower is running and discharge cool/warm air.
(Cooling only/Heat Pump) delay in the circuit. Thus, it requires about 3 minutes before the outdoor unit will start.
Page 20 IM 820
Unit Indicator Lights
IR signal receiver
When an infrared remote control operating signal is transmitted, the indoor unit beeps and indicator lights confirm acceptance of the signal transmission.
Figure 11. IR Receiver & LED Indicator Lights Location
INDOOR UNIT
Air Discharge
Swing Baffle
Wireless Remote Control
Figure 12. LED Indicator Lights Display
Cooling Unit
Cool Dry Fan
IR Receiver and LED
Indicator Lights
Air Discharge
Grille
Air Filters
Air Intake Grille
Optional Wired
Wall Control
Wireless Remote
Control
Figure 13: Mode and Diagnostic Chart
Cool Dry Fan Heat
Cool Dry Fan Heat
Mode or Fault
Cooling mode
Dry mode
Fan mode
Heat mode
Auto mode in heating operation.
Auto mode in cooling operation.
Defrost operation
Compressor overload protection
Outdoor coil sensor contact loose/short
Room air sensor contact loose/short
ON Blinking
Netware 2 - Wired Wall Control (Optional)
Error codes blink on wall control display as follows:
E1 - Room sensor loose or defective.
E2 - Indoor coil sensor loose or defective.
E3 - Outdoor coil sensor loose or defective.
E4 - Compressor cycling on overload.
E5 - Low refrigerant charge.
IM 820 Page 21
Service and Maintenance
WARNING
Disconnect the electrical power supply before performing any service, maintenance or troubleshooting.
Electrostatic Filters
Pre-charged electrostatic polypropylene filter removes microscopic dust, smoke and small invisible particles to keep the room air clean.
Filter Replacement
WARNING
Disconnect the main power supply before opening the return air grille.
DO NOT restore power until the grille is closed.
See Figure 14.
Replace the electrostatic air purifying filters every 6 months or sooner if they turn brown.
Replacement filters can be purchased from your sales representative or distributor.
Use the new filter immediately once it has been removed from the package.
1.
Open the return air grilles and remove the filters.
2. Use a vacuum cleaner or wash with water with a neutral cleaning agent.
3. Rise and dry before installing the filter.
Note: Never use chemicals such as gasoline or paint thinner to clean the filters. Filters will be damaged.
Figure 14. Changing the Filters
Startup After Extended Shutdown
• Inspect thoroughly and clean indoor and outdoor units.
• Clean or replace air filter.
• Clean condensate drain line.
• Clean clogged indoor and outdoor coils.
• Check fan imbalanced before operation.
• Tighten all wire connections.
• Check for refrigerant leakage.
Note: The crankcase heater should be energized for at least
6 hours before starting the unit.
Troubleshooting
If any malfunction of the unit is noted, immediately switch off the power supply.
Check the following chart for possible causes/treatments.
If the trouble persists, please call your local dealer/serviceman.
Trouble
The compressor does not operate.
Possible cause/treatment
Protection against frequent starting. Wait for 3 to 4 minutes for the compressor to start operating.
Power failure.
Fans and compressor do not operate.
Air flow too low or insufficient cooling/heating capacity.
Discharge air flow has bad odor.
Condensation on the return air grille of the indoor unit.
Condensate leaking into room.
Hissing sound from the unit during operation.
Check fuse or circuit breaker.
Power supply disconnect off.
Delay timer may be set incorrectly.
Dirty air filters.
Doors or windows open.
Adjust thermostat setting.
Smoke, perfume, etc. may have collected on the indoor coil.
Clean coil.
Use dry mode. High humidity in conditioned space.
Set temperature too low.
Increase temperature setting and operate unit at high fan speed.
Condensate drain plugged.
Refrigerant fluid flowing into the evaporator coil. Operate for a while to see if sound goes away.
Page 22 IM 820
Service and Maintenance
WARNING
Disconnect the main power supply before performing any service, maintenance or troubleshooting.
The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention. .
Item
Indoor Unit
Air Filters
Indoor Unit
Maintenance Procedures
Clean the grille and panel by wiping it using soft cloth soaked in lukewarm water (below 40°C/104°F) with neutral detergent solution.
Note. Do not use gasoline, volatile substances or chemicals to clean the unit.
Frequency
1. Remove the filter before cleaning it.
2. Remove the dust adhering on the filter by using a vacuum cleaner or wash with lukewarm water (below 40°C/104°F) with neutral detergent solution.
3. Rinse well and dry the filter before placing it back onto the unit.
Note. Do not use gasoline, volatile substances or chemicals to clean the filter.
At least once a month.
Every year.
Condense Drain Pan and
Pipe
Indoor Fan
Indoor/Outdoor Coil
Power Supply
Compressor
Compressor Oil
Fan Motor Oil
Check and clean if necessary.
Every year.
Check for abnormal noise.
Clean the louvers and coil. Be careful not to bend or flatten the aluminium fins.
DO NOT use cleaning fluids that might corrode the coil.
1. Check the running current and voltage for indoor and outdoor units.
2. Check the electrical wiring and tighten the terminals.
No maintenance needed if refrigerant circuit remains sealed. However, check for refrigerant leaks at joints and fittings.
Oil is factory charged. Not necessary to add oil if circuit remains sealed.
All motors are pre-lubricated and sealed at factory.
Every year.
Every year.
Every year.
Every year.
No maintenance required.
No maintenance required.
IM 820 Page 23
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www. DaikinApplied.com.
Daikin Applied
800.432.1342
www.DaikinApplied.com
© 2004 Daikin
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Model Numbers
- 3 General Information
- 3 Safety Precautions
- 4 Unit Dimensions
- 4 Indoor Units
- 4 Outdoor Units
- 5 Installation Guidelines
- 5 Installation Diagram
- 5 Installation of Outdoor Unit
- 6 Installation of the Indoor Unit
- 6 General
- 6 Indoor Unit Clearances
- 7 Standard Mounting
- 7 Semi-enclosed Mounting
- 8 Refrigerant Tubing
- 8 Tubing Length & Elevation
- 8 Tubing Preparation
- 8 Tubing Connection To Units
- 9 Electrical Connections
- 10 Wiring Diagrams
- 17 Evacuating and Charging
- 17 Additional charge
- 17 Charge operation
- 18 Remote Controller Operation Guide
- 20 Special Features
- 20 Dry mode
- 20 Heat mode (heat pump only)
- 20 Overheating protection (heat pump only)
- 20 Frost prevention
- 20 Fan speed and rated cooling capacity
- 20 Operating Conditions
- 20 Cooling
- 20 Overall Checking
- 21 Unit Indicator Lights
- 21 IR signal receiver
- 22 Service and Maintenance
- 22 Electrostatic Filters
- 22 Filter Replacement
- 22 Startup After Extended Shutdown
- 22 Troubleshooting
- 23 Service and Maintenance