Nano UPS Quick Guide

V.1.0

1

Package Contents

You should have received the following items inside of package:

UPS Unit

Quick Guide

-Power cable (only for the IEC-type model)

Product Introduction

2

The Nano UPS provides comprehensive protection in a small and economic package.

The UPS is more compact and offers greater comprehensive power protection against surges and spikes. This UPS will continue providing stable power to connected equipment and enable to shutdown PC safely during power failure. Its embedded microprocessor controller guarantees high reliability and it’s perfect for any home or small office application.

Product Overview

3

Front View:

1

2

3

1

2

3

Power switch

UPS status indicator

Fault/Battery status indicator

(Check the Indicator & Alarm Table for the details)

Installation & Initial Startup

4

NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged.

Placement & Storage Conditions

Install the UPS in a protected area that is free of excessive dust and has adequate air flow. Please place the UPS away from other units at least 20 cm to avoid interference. Do NOT operate the UPS where the temperature and humidity is outside the specific limits. (Please check the specs for the limitations.)

20cm 20cm

Connect to Utility and Charging

Before initial use, please p lug in the AC input cord to the wall outlet and turn on the UPS for charging. For the best results, suggest to charge the battery at least 8 hours before initial use. The UPS charges its battery while connecting to the utility with power on.

8 hours

Connect the Loads

Plug in the loads to output receptacles on the rear panel of the UPS. Simply turn on the power switch of UPS unit, then devices connected to the UPS will be protected by UPS unit.

CAUTION: NEVER connect a laser printer or scanner to the UPS unit. This may cause the damage of the unit.

Back View:

1

2

3

1

2

IEC Type NEMA Type Universal Type Schuko Type

3

1 AC input

2

3

Output receptacles

Circuit breaker

Turn On/Off the Unit

Turn on the UPS unit by pressing the power switch. Turn off the UPS unit by pressing again the power switch.

Indicators & Alarm Table for Operation

Conditions Visual Indications Alarm

AC mode

Battery mode

Low battery at battery mode

Green LED lighting

Green LED flashing every 10 seconds

Green LED flashing every second & Red LED lighting

Off

Sounding every 10 seconds

Sounding every second

Fault Red LED lighting Continuously sounding

Alarm for overtemperature protection

Red LED flashing every 0.5

seconds

Off

5

Important Safety Warning

(

SAVE THESE INSTRUCTIONS)

CAUTION!

To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive contaminants. (See the specifications for the acceptable temperature and humidity range.)

CAUTION!

To reduce the risk of overheating the UPS, do not cover the UPS' cooling vents and avoid exposing the unit to direct sunlight or installing the unit near heat emitting appliances such as space heaters or furnaces.

CAUTION! Do not attach non-computer-related items, such as medical equipment, life-support equipment, microwave ovens, or vacuum cleaners to UPS.

CAUTION!

Do not plug the UPS input into its own output.

CAUTION! Do not allow liquids or any foreign object to enter the UPS. Do not place beverages or any other liquid-containing vessels on or near the unit.

CAUTION!

In the event of an emergency, press the OFF button and disconnect the power cord from the AC power supply to properly disable the UPS.

CAUTION! Do not attach a power strip or surge suppressor to the UPS.

CAUTION! If the UPS is with metal chassis, for safety purpose, grounding is a must during UPS installation in order to reduce leakage current below 3.5mA.

Attention hazardous through electric shock. Also with disconnection of this unit from the mains, hazardous voltage still may be accessible through supply from battery. The battery supply should be therefore disconnected in the plus and minus pole at the quick connectors of the battery when maintenance or service work inside the UPS is necessary.

CAUTION!

Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.

CAUTION! When replacing the batteries, use the same number and type of batteries.

CAUTION!

Internal battery voltage is 12Vdc. Sealed, lead-acid, 6-cell battery.

CAUTION!

Do not dispose of batteries in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes.

CAUTION! Unplug the UPS prior to cleaning and do not use liquid or spray detergent.

CAUTION!

A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed before replacing batteries:

1) Remove watches, rings, or other metal objects.

2) Use tools with insulated handles.

3) Wear rubber gloves and boots.

4) Do not lay tools or metal parts on top of batteries.

5) Disconnect charging source prior to connecting or disconnecting batteries terminal.

6

Trouble Shooting

Use the table below to solve minor problems. panel.

Problem Probable Cause Solution

No LED display on the front

Alarm continuously sounds when the mains is normal.

Alarm sounds every

2 seconds when the mains is normal.

When power fails, backup time is shorten.

The mains is normal but green LED is flashing.

Low battery.

Battery fault.

The UPS is not turned on.

The UPS is overload.

UPS fault

Battery defect

Charging circuit is damaged.

The UPS is overload.

Battery voltage is too low.

Battery defect.

Power cord is loose.

Charge the UPS at least 8 hours.

Replace the battery with the same type of battery.

Press the power switch again to turn on the UPS.

Remove some loads first.

Before reconnecting equipment, please verify that the load matches the UPS capability specified in the specs.

Return the unit to service center.

Replace the battery with the same type of battery.

Return the unit to service center.

Remove some critical load.

Charge the UPS at least 8 hours.

Replace the battery with the same type of battery.

Reconnect the power cord properly.

7

Specifications

Model Nano 400 Nano 600 Nano 800

INPUT

Voltage

Voltage Range

Frequency

OUTPUT

Output Voltage (AC mode)

Output Voltage (Bat. mode)

Transfer Time

Waveform

BATTERY

Type & Num ber

Charging Time

PROTECTION

Full Protection

PHYSICAL

Dimension (DxWxH mm )

Net Weight (kgs)

ENVIRONMENT

Humidity

Temperature

110/120 VAC or 220/230/240 VAC

90~145 VAC or 180~270 VAC

50 Hz or 60 Hz sam e as input

120 VAC ± 10% / 230 VAC ± 10%

2-6 ms (Typical)

Simulated Sine Wave

12 V/4.5 AH x 1 12 V/ 7 AH x 1 12 V/9 AH x 1

8 hours recover to 90% capacity

Overcharge, discharge, short circuit, and thermal protection

228 x 82.5 x 207

2.2 2.7 3.1

0-90 %

0-40 C (non-condensing)