advertisement
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Quick reference guide
IChill 290D/291D
(Firmware rel. 1.8)
Page 1 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Index
General Advice ______________________2
General Features ____________________3
IC290D/291D Table of the
Features _____________________________4
User Interface
________________________5
Table Of The Output Status In
Alarm Condition ____________________16
Wiring Connections
_________________19
Electrical Connections ______________21
Probe and relay configuration
______22
Table Of The Parameters ____________26
Technical Data ______________________52
1. General Advice
1.1 Please Read Before Using This
Manual
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device.
Check the application limits before proceeding.
1.2 Safety Precautions
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (seeTechnical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining.
Fit the probe where it is not accessible by the end user.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful.
Full Manual
Dixell S.r.l. reserve to itself the right to modify this instruction manual without any warning.
Last available can be downloaded from he internet site.
[email protected]
Page 2 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
2. General Features
iCHILL IC290D/291D
is an electronic controller for chiller unit applications having one or two circuits:
Air/air
Air/water
Water/water
Motocondensing
Additional features :
Heat pump with gas reversibility
2.1
Main Function
Chiller management:
One circuit up to 4 compressors
Two circuits with different compressor number per circuit
Double circuit up to 6 compressors
Screw compressors
Compressor start up:
Direct
Part winding
Star - delta
Compressor Soft start:
With step valve
Automatic start-unloading (without load).
External by-pass gas valve.
Capacity step control:
Continuous control
Step control
Modulation control (screw compressors)
Thermoregulation of the compressors
Time running hours
Number of start-up per hour
Cooling liquid injection
With dedicated PTC probe
High temperature alarm of the compressor discharge side
With dedicated PTC probe
Complete management of two pump groups of the water side
2 pumps evaporator side
2 pumps condenser side
Other display readings
Safety digital inputs
Compressors running hours
Number of compressor start-up
Pump running hours
Delay counting to the next defrost
Proportional output percentage status
Compressors discharge temperature
Alarm reset with custom password
Alarm list
Compressor thermal protection alarm
Single circuit stand-by
Circuit maintenance
To work with only one circuit
Single compressor stand-by
Compressor maintenance
Compressor malfunction
Pump down management
With dedicated pressure switch
Low pressure switch
Low pressure transducer
Unloading circuit
High temperature of the evaporator inlet water
High temperature of the condenser inlet water (unit with recovery)
High condensing pressure
Low evaporating pressure
Maintenance messages
Condenser pumps
Auxiliary relays
Compressors
Evaporator pumps or pressure probes.
Weekly Energy saving
Two configurable relay outputs not depending from the control algorithm can be managed through NTC, PTC
From digital input
Weekly ON/OFF:
Three different time bands per day (only with RTC onboard)
Three different time bands per day (only with RTC onboard)
Dynamic setpoint:
Determined by analogue NTC input or 4÷20mA current input.
Change over :
Automatic chiller or heat pump functioning depending from NTC analogue input.
Remote OFF:
From configurable digital input.
Remote change over:
From configurable digital input.
Hot start :
Air / air unit
Defrost management:
Boiler:
Combined control with temperature and pressure
Forced defrost with low temperature of external air
From configurable digital input
Manual from keyboard
For electrical integration heating or anti-freeze heaters
Two proportional outputs for condensing fan speed control (inverter or phase cut) with configurable signal:
PWM
0÷10Volt
4÷20mA
Four proportional control outputs 0÷10V or ON/OFF
Complete alarm management
Supervisor / monitoring
To control the dumper in free cooling or recovery
To control an external relay
Internal Data logger up to 100 events
TTL output for XJ485 interface (Mod #Bus protocol) for
XWEB300 / XWEB3000 Dixell monitoring system for local and remote control
Page 3 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
3. IC290D/291D Table of the Features
FEATURES
OUTPUT RELAYS
10
14
DIGITAL INPUTS
18
PROBE INPUTS
10
PROPORTIONAL OUTPUTS
2 PWM outputs for condensing fan
2 0÷10V or 4÷20mA for condensing fan
4 0÷10V
OTHER OUTPUTS
TTL
Output for remote keyboard VGI890
POWER SUPPLY
12 Vac/dc (+15%;-10%)
24 Vac/dc (± 10%)
OTHERS
Internal RTC
Buzzer
configurable = configurable through parameter opt = optional
= default
IC290D
configurable configurable
configurable configurable
opt opt opt
IC291D
configurable configurable
configurable configurable
opt opt opt
Page 4 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
4. User Interface
In the main visualization it is possible to read:
status of the unit: cooling, heating, remote OFF or STD-BY
date and time, available if the Ichill is provided by internal clock
4 probes value; it is possible to manage 4 lines to visualize the probe temperature / pressure
(parameters dP06..dP09)
load / function status as showed below:
/
Compressor/s
(blinking during the start up delay)
Water pump / Supply fan
Economy function
Unloading function
Condenser fan
Electric heater
Economy or ON/OFF by timetable
Defrost
Sanitary water Alarm
Meaning of the keys:
Allows to read the value of the probes configured in the Ichill
Allows to switch on the
Ichill in heating or cooling mode (see parameter
CF78)
Allows to switch on the
Ichill in heating or cooling mode (see parameter
CF78)
Allows to read/modify the set point
Allows to read the alarms
Allows to enter the
SERVICE menù
Page 5 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Allows to put the Ichill in
STD-BY
Allows to read the main information of the circuits
(compressor status, water pump status, pressure probe value,…)
Note: in case of alarm, press any key to silence the buzzer
4.1 Keyboard configuration
Keyboard configuration
It is possible to set: o contrast and backlight (it is strongly recommended to reduce as possible the activation time of the backlight) o language selection o read information about: o Ichill firmware release (to verify the compatibility Ichill
Visograph keyboard) o Visograph keyboard firmware release o Visograph keyboard bin release
How to modify the configuration: o press o press or o press o press or to confirm to select the configuration to change to change the configuration
Page 6 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
4.2
Chiller / Heat pump selection
If the Ichill is in STD-BY press
Meaning of the simbols:
CF78 = 0:
pushing
CF78 = 1:
pushing o to switch on the machine.
key the unit starts in chiller, pushing key the unit starts in heat pump, pushing key the unit starts in heat pump key the unit starts in chiller
Page 7 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
When the Ichill is ON, press to put the machine in STD-BY.
4.3 Visualization / modification of the set point configuration
Visualization / modification of the set point
Press key to read the value of the set point (cooling set point if the Ichill is in cooling mode, heating set point if the Ichill is in heating mode, cooling and hating set point if the Ichill is in STD_BY or remote OFF, Sanitary water when enabled).
It is also possible to read the status of the Energy saving, the status of the Dynamic set point and the real value of the set point if the Energy saving or Dinamic set point are active.
To modify the set point (Cooling, Heating or Sanitary water):
press or to select the value of the set point
press
press o to modify the value
Page 8 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
press to confirm the operation
4.4 Alarm visualization and reset
Alarm visualization and reset
Press key to read the alarm status; the alarm status can be: o
Active
: the alarm is still active and it is not possible to reset it o
Reset
: the alarm is not active and it is possible to reset it
Manual reset procedure: o press o press or to select the alarm; to reset the alarm
In case of compressor overload alarm when the password is requested, follow this step: o press o press o press o to select the compressor overload alarm o press o press or to insert the password value (parameter AL46) to confirm the operation
Page 9 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
4.5 Menu SERVICE
Menu SERVICE
Pressing it is possible to read the following information:
Parameter programming
Programming clock
Energy saving and ON/OFF scheduling
Compressor maintenance
It is possible to disable the compressor for maintenance, read the working hours and number of start up (and reset them)
Water pump maintenance
It is possible to read / reset the working hours
Circuit maintenance
Visualization and reset of the alarms
Visualization and reset of the alarm log
Defrost status
Electrical heater and pump down valve status
I/O status
Screw compressor information
It is possible to read the discharge temperature, the liquid injection valve status and the minimum load valve status
Auxiliary output status
Upload and download parameter map with Hot Key
Sanitary water status, sanitary water temperature, antilegionella status, etc.
Visograph configuration
It is possible to read the Ichill firmware version (for the compatibility with the keyboard), the keyboard firmware release and keyboard bin release.
It is possible to change the language, to set the contrast and the backlight
.
Page 10 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
4.6 Parameters programming
Parameters programming
Pressing it is possible to read/modify the parameters value:
select the level 1 (default) or level 2 or level (by pressing Pr2 or Pr3 key)
press
press or to enter the password
press to confirm
the display shows “Password OK!” (otherwise repeat the procedure)
press to visualize the parameters
Page 11 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Pressing press .
or it is possible to select the group of parameters to modify, then
How to modify the value of the parameter:
press
press or to select the parameter to modify
press or to modify the value
Page 12 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
press to confirm
Press or to scroll the parameters.
4.7 Clock programming and Energy saving / ON_OFF scheduling visualization
Clock programming and Energy saving / ON_OFF scheduling visualization
It is possible to set the clock and read the Energy saving and the ON/OFF scheduler.
How to set the clock: o press date); o press o press o press or or to confirm to select the date to modify (hour, minutes, to modify the value
Page 13 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Pressing or and ON/OFF scheduling.
it is possible to read the information about the Energy saving
To modify the hour of the time band and to enable the function is necessary to enter the parameter programming (ES parameters).
4.8 Parameters programming with Hot Key 64
Parameters programming with Hot Key 64
It is possible to use the HotKey 64 for:
copy the parameter map from the HotKey 64 to the Ichill (Download)
copy the parameter map from the Ichill to HotKey 64 (Upload)
Download from HotKey 64 to Ichill:
this operation is enabled only if the Ichill is in STD-BY or remote OFF, otherwise the display shows the message “Download enabled only in stand-by”.
Download procedure:
Insert the Hot Key 64 into the 5 ways connector through the hole at the top of the Ichill (see image below)
Select “Download from HotKey to device”
Press ENTER
if the operation was successful the display shows “OK”, otherwise shows “ERR”
Upload from Ichill to Hot Key 64:
Upload procedure:
Insert the Hot Key 64 into the 5 ways connector through the hole at the top of the Ichill (see image below)
Select “Upload from device to HotKey”
Press ENTER
if the operation was successful the display shows “OK”, otherwise shows “ERR”
In case of Upload / Download failure:
Hot Key 64 not properly inserted in the 5 ways connector
Hot Key model different to Hot Key 64
Page 14 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Page 15 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
5. Table Of The Output Status In Alarm Condition
The alarm codes are made of letters and numbers to define the different typologies:.
5.1
Alarm
Code
ALARM
Alarm description
Compressor Anti freeze heaters
Boiler
Support heaters
Evapor ator
Pump /
Supply fan
Condenser fan
Cir1 / Cir2
Auxiliary relay
AP1
AP10
ALti
Probe
PB1..Pb10
alarm
Low air temperature of the evaporator inlet (air / air unit) Alarm
AEFL
Evaporator flow alarm
Yes (6)
Yes (1)
Yes
ACFL
AHFL
APFL
AtSF
AEUn
AtE1
Condenser flow alarm
Sanitary water flow switch alarm
Solar panel flow switch alarm
Supply fan overload alarm
Unloading signalling from evaporator
Evaporator 1 water pump
Yes
Yes
Yes
(6)
Yes
(6)
Yes
Yes
(4)
Yes (boiler)
Yes (boiler)
(5)
Yes
Yes evapor ator water pump
(3)
Yes conden ser water pump
(3)
Yes sanitary water pump
(3)
Yes solar panel water pump
(3)
Yes supplay fan
Yes evapor
Yes
Yes
Yes
Yes
Yes
Page 16 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1) overload alarm
AtE2
Evaporator 2 water pump overload alarm
AtC1
Condenser 1 water pump overload alarm
Yes
(4)
Yes
(4)
Yes (boiler)
(5)
AtC2
Condenser 2 water pump overload alarm
AEP1
AEP2
ACP1
ACP2
Evaporator 1 water pump maintenance
Evaporator 2 water pump maintenance support
Condenser 1 water pump maintenance
Condenser 2 water pump maintenance
ASAn
ASUn
Sanitary water pump maintenance
Solar water panel pump maintenance
ArtC
Clock alarm
Remote
Atr1
keyboard n° 1 alarm
Remote keyboard n° 2
Atr2
alarm
ArtF
Clock failure
ALOC
Generic alarm
AEE
Eeprom alarm
ACF1
ACF1
2
Configuration alarm
ArtF
Faulty clock
ArtC
Clock error
Yes
(4)
Yes
Yes
Yes ator water pump 1
Yes evapor ator water pump 2
Yes conden ser water pump 1
Yes conden ser water pump 2
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Page 17 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
(1)
(2)
(3)
(4)
(5)
(6)
AEUn
ALti
AEht
Unloading signalling from high temp of.
evaporator water
Low evaporator inlet temperature in air/air unit
High water temperature inlat evaporator
Yes
= if probe configured as anti-freeze / boiler control and Ar10 = 0
= if probe configured as auxiliary relay control
= manual alarm procedure
= compressors switched off when only 1 water pump is configured or both water pumps are in alarm
= Boiler heaters off with only 1 water pump configured or with 2 pumps but both in alarm from the corresponding digital inputs (in this case the boiler heaters are on only with thermoregulation anti-freeze setpoint as evaporator protection function)
= If the faulty probe is the regulation probe or circuit probe (condenser probe, suction probe)
5.2
ALARM: circuit alarm
Alarm
Code
Alarm description b(
n
)HP
High pressure switch of the circuit
(
n
) b(
n
)LP
Low pressure switch of the circuit
(
n
) b(
n
)AC
Anti-freeze in chiller of the circuit
(
n
) b(
n
)AH
Anti-freeze in heat pump of the circuit
(
n
) b(
n
)hP
High condensing pressure of the circuit
(
n
) b( b( b(
n
)lP b(
n n n
)hP
)LP
)PH
High condensing temperature from NTC of the circuit
(
n
)
Low condensing pressure - (evaporating with low pressure transducer) with transducer of the circuit of the
(
n
)
Low condensing temperature NTC circuit
(
n
) b(
n
)tF
Fan overload circuit
(
n
)
Pump down alarm in stop regulation of the circuit
(
n
) b(
n
)PL
Pump down in regulation start-up of the circuit
(
n
) b(
n
)dF
Bad defrost circuit
(
n
) b( b(
n n
)Cu
)Cu
Unloading from condenser high temp/press of the circuit
(
n
)
Unloading from evaporator low temp/press of the circuit
(
n
) b(
n
)rC
Recovery function disabled in circuit
(n) b(
n
)ds
Circuit
(n)
disabled from keyboard
b(
n
)Ac
Anti-freeze circuit
(n)
message in chiller
b(
n
)Ah
Anti-freeze circuit
(n)
message in heat pump
Compresso rs of the circuit
(
n
)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Compressor s of the other circuit
Fan condensing of the circuit
(
n
)
Yes after 60 seconds
Yes
Yes
Yes
Yes after 60 seconds
Yes after 60 seconds
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Fan condensing of the other circuit
Page 18 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
(
n
)
identifies the circuit 1 or 2
5.3
ALARM: compressor alarm
Alarm Code
Alarm description
C(
n
)HP
C(
n
)oP
C(
n
)tr
C(
n
)dt
C(
n
)dS
C(
n
)Mn
Compressor(
n
) high pressure switch
Compressor(
n
) oil pressure switch / Oil level switch
Compressor(
n
) overload
Compressor high discharge temperature
Compressor (n) disabled from keyboard
Compressor(
n
) maintenane
(
n
)
identifies the compressor 1, 2 , 3 , 4 , 5 , 6
Compressor
(
n
)
Yes
Yes
Yes
Yes
Yes
6. Wiring Connections
Compressors not involved
6.1
Hardware Resources: IC290D / 291D
10 relays IC290D / 14relays IC291
(MAX current on the relay contacts 5(2)A 250V; MAX current in the common line of the relays 12A
250V)
18 digital inputs (free voltage)
10 analogue inputs: configurable ( 6 NTC or PTC, 4 NTC or pressure transducer 4÷20mA or ratiometric 0÷ 5.0 Volt)
2 PWM output (to manage the condenser fan)
6 0..10V output
1 output for remote keyboard (max 2 remote panels)
1 TTL output to connect an “Hot Key 64” (parametrs programming)
1 RS 485 output
Page 19 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
6.2
Ichill 290/291D dimensions
All the measures are expressed in mm.
6.3
Keyboard VGI690 panel cut out
Page 20 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
7. Electrical Connections
The instrument is provided with:
3 removable terminal blocks MOLEX with 0.5 mm
2 wires: 16 / 8 /22 ways for digital / analogue inputs and modulating outputs.
4 removable screw terminal block STELVIO for 2.5 mm
2 wires connection: 3 / 4 / 5 / 6 ways for the relay outputs.
5 ways connector for TTL RS485 interface outputs.
3 ways connector for keyboard VGI890 to be connected with the cable
CABC3J15
.
The
LW30 KIT
is the complete kit with MOLEX + 3 mt wires already connected and the STELVIO terminals.
Check the connecitons and the line voltage before turning on the power supply.
Keep low voltage cables, such as analogue/digital inputs/outputs and probes, away from power cables and terminals.
Respect the maximum load current of each relay output, in case of power loads use filtered contactors.
Page 21 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
8. Probe and relay configuration
8.1
Analog input Pb1 - Pb2 - Pb7 -
Pb8 - Pb9 - Pb10
Parameters involved:
CF08 =
Configuration PB1
CF09 =
Configuration PB2
CF14 =
Configuration PB7
CF15 =
Configuration PB8
CF16 =
Configuration PB9
CF17 =
Configuration PB10
0.
Not enabled
1.
Temperature probe
PTC
for compressor
1 discharge
2.
Temperature probe
PTC
for compressor
2 discharge
3.
Temperature probe
PTC
for compressor
3 discharge
4.
Temperature probe
PTC
for compressor
4 discharge
5.
Temperature probe
PTC
for compressor
5 discharge
6.
Temperature probe
PTC
for compressor
6 discharge
7.
Temperature probe
NTC
for evaporator inlet
8.
Temperature probe
NTC
for evaporator
1 outlet
9.
Temperature probe
NTC
for evaporator
2 outlet
10. Temperature probe
NTC
for common evaporator outlet
11. Temperature probe
NTC
for common hot water condenser / recovery inlet
12. Temperature probe
NTC
for hot water of the condenser / recovery circuit 1 inlet
13. Temperature probe
NTC
for hot water of the condenser / recovery circuit 2 inlet
14. Temperature probe
NTC
for hot water of the condenser / recovery circuit 1 outlet
15. Temperature probe
NTC
for hot water of the condenser / recovery circuit 2 outlet
16. Temperature probe
NTC
for hot water of the condenser / recovery common outlet
17. Temperature probe
NTC
for free cooling water inlet circuit
18. Not Used
19. Temperature probe
NTC
for dynamic setpoint external air / boiler / change over
20. Temperature probe
NTC
for combined defrost circuit 1
21. Temperature probe
NTC
for combined defrost circuit 2
22. Temperature probe
NTC
for auxiliary output 1
23. Temperature probe
NTC
for auxiliary output 2
24. Temperature probe
NTC
sanitary water
1
25. Temperature probe
NTC
sanitary water
1
26. Temperature probe
NTC
solar panel
27. Temperature probe
NTC
for condensing circuit 1
28. Temperature probe
NTC
for condensing circuit 2
After the number 25 the display configuration can be selected from
o 1
to
c67
that allows to set an analogue input as digital input (see polarity of the digital input/outputs).
8.2
Analog input Configuration
Pb3 - Pb4 - Pb5 - Pb6
Parameter involved:
CF10 =
Configuration PB3
CF11 =
Configuration PB4
CF12 =
Configuration PB5
CF13 =
Configuration PB6
0
1
2
3
4
Not enabled
Temperature probe
PTC
for compressor
1 discharge
Temperature probe
PTC
for compressor
2 discharge
Temperature probe
PTC
for compressor
3 discharge
Temperature probe
PTC
for compressor
5
6
7
8
9
4 discharge
Temperature probe
PTC
for compressor
5 discharge
Temperature probe
PTC
for compressor
6 discharge
Temperature probe
NTC
for evaporator inlet
Temperature probe
NTC
for evaporator outlet 1
Temperature probe
NTC
for evaporator outlet 2
Page 22 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
10 Temperature probe
NTC
for common evaporator outlet
11 Temperature probe
NTC
for common hot water condenser / recovery inlet
12 Temperature probe
NTC
for hot water condenser / recovery inlet circuit 1
13 Temperature probe
NTC
for hot water condenser / recovery inlet circuit 2
14 Temperature probe
NTC
for hot water condenser / recovery outlet circuit 1
15 Temperature probe
NTC
for hot water condenser / recovery outlet circuit 2
16 Temperature probe
NTC
for hot water condenser / recovery common outlet circuit
17 Temperature probe
NTC
for free cooling water inlet
18 Not Used
19 Temperature probe
NTC
for external air dynamic setpoint/ boiler / change over
20 Temperature probe
NTC
for combined defrost circuit 1
21 Temperature probe
NTC
for free cooling water inlet 2
22 Temperature probe
NTC
for auxiliary output 1
23 Temperature probe
NTC
for auxiliary output 2
24 Temperature probe
NTC
sanitary water
1
25 Temperature probe
NTC
sanitary water
2
26 Temperature probe
NTC
solar panel
27 Condenser probe circuit 1 ( temperature
NTC
/ pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
28 Condenser probe circuit 2 ( temperature
NTC
/ pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
29 Evaporator pressure probe circuit 1
(pressure
4÷20 mA
/ ratio-metric
0÷
5Volt
)
30 Evaporator pressure probe circuit 1
(pressure
4÷20 mA
/ ratio-metric
0÷
5Volt
)
31 Auxiliary output 1 pressure probe control (
4÷20 mA
/ ratio-metric
0÷
5Volt)
32 Auxiliary output 2 pressure probe control (
4÷20 mA
/ ratio-metric
0÷
5Volt)
33 Dynamic setpoint pressure probe (
4÷20 mA)
After the number 30 the display read-out goes from “
o 1”
to “
c67
that allows to set an analogue input as digital input (see polarity input of digital inputs).
8.3
Digital Input Configuration Id1
– Id18
Parameters involved:
CF36 =
Configuration ID1…
CF53 =
Configuration ID18
0.
Not enabled
1.
Remote ON / OFF
2.
Remote chiller / heat pump
3.
Flow switch/ Supply fan overload
4.
Flow switch of heated side
5.
Antifreeze heater circuit 1
6.
Antifreeze heater circuit 2
7.
High pressure switch circuit 1
8.
High pressure switch circuit 2
9.
Low pressure switch circuit 1
10. Low pressure switch circuit 2
11. Compressor 1 high pressure
12. Compressor 2 high pressure
13. Compressor 3 high pressure
14. Compressor 4 high pressure
15. Compressor 5 high pressure
16. Compressor 6 high pressure
17. Compressor 1 overload
18. Compressor 2 overload
19. Compressor 3 overload
20. Compressor 4 overload
21. Compressor 5 overload
22. Compressor 6 overload
23. Condenser fan overload of circuit 1
24. Condenser fan overload of circuit 2
25. Condenser fan overload of circuit 1 and
2 (comun)
26. Water pump overload of evaporator 1
27. Water support pump overload of evaporator
28. Water pump overload of condenser 1
29. Water support pump overload of condenser
30. Not Used
31. Not Used
32. End defrost circuit 1
33. End defrost circuit 2
34. Energy Saving
35. Pressure switch / compressor 1 oil
36. Pressure switch / compressor 2 oil
37. Pressure switch / compressor 3 oil
Page 23 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
38. Pressure switch / compressor 4 oil
39. Pressure switch / compressor 5 oil
40. Pressure switch / compressor 6 oil
41. Pump down pressure switch of circuit 1
42. Pump down pressure switch of circuit 2
43. Generic alarm from digital input with stop regulation n° 1
44. Generic alarm from digital input with stop or signal regulation n° 2
45. Operation working mode: by RTC or keyboard
46. Operation mode with supplay fan only
47. Digital input of thermoregulation request
(condensing unit)
48. Digital input of cooling request
(condensing unit)
49. Digital input of heating request
(condensing unit)
50. Request step 2 (condensing unit)
51. Request step 3 (condensing unit)
52. Request step 4 (condensing unit)
53. Request step 5 (condensing unit)
54. Request step 6 (condensing unit)
55. Request step 7 (condensing unit)
56. Request step 8 (condensing unit)
57. Request step 9 (condensing unit)
58. Request step 10 (condensing unit)
59. Request step 11 (condensing unit)
60. Request step 12 (condensing unit)
61. Request step 13 (condensing unit)
62. Request step 14 (condensing unit)
63. Request step 15 (condensing unit)
64. Request step 16 (condensing unit)
65. Sanitary water flow switch
66. Solar panel flow switch
67. Only sanitary water
8.4
Digital Output
Configuration RL1- RL14
(relay)
Parameter involved:
CF54=
Configuration
Configuration RL14
RL1…
CF67=
0.
Not enabled
1.
Alarm
2.
Evaporator water pump / Supply fan
3.
Support water pump of the evaporator
4.
Anti-freeze heater / integration heating / boiler circuit 1
5.
Anti-freeze heater / integration heating / boiler circuit 2
6.
Water pump of the condenser recovery circuit
7.
Support water pump of the condenser recovery circuit
8.
4-way valve for chiller / heat pump inversion of the circuit 1
9.
4-way valve for chiller / heat pump inversion of the circuit 2
10. 1° condenser fan step ON/OFF control of the circuit 1
11. 2° condenser fan step ON/OFF control of the circuit 1
12. 3° condenser fan step ON/OFF control of the circuit 1
13. 4° condenser fan step ON/OFF control of the circuit 1
14. 1° condenser fan step ON/OFF control of the circuit 2
15. 2° condenser fan step ON/OFF control of the circuit 2
16. 3° condenser fan step ON/OFF control of the circuit 2
17. 4° condenser fan step ON/OFF control of the circuit 2
18. Solenoid valve of the pump-down circuit
1
19. Solenoid valve of the pump-down circuit
2
20. Recovery valve circuit 1
21. Recovery valve circuit 2
22. Free cooling ON/OFF valve
23. Auxiliary output circuit 1
24. Auxiliary output circuit 2
25. Solenoid valve Intermittent for screw compressor 1
26. Solenoid valve Intermittent for screw compressor 2
27. Solenoid valve of the liquid injection for compressor 1
28. Solenoid valve of the liquid injection for compressor 2
29. Sanitary valve 1
30. Sanitary valve 2
31. Sanitary heater 1
32. Sanitary heater 2
33. Sanitary heater 3
34. Solar panel water pump
35. Solar panel valve
36. Sanitary water pump
37. Hybrid exchanger 1
38. Hybrid exchanger 2
39. Direct start-up : compressor 1 relay
PW start: relay PW 1 of the compressor
1
Page 24 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Star-delta start: relay line 1 of the compressor 1
40. PW start: relay PW 2 of the compressor
1
Star-delta start: relay linea 2 compressor
1
41. Star centre of the Star-delta start of the compressor 1
42. Capacity step valve 1 compressor 1
43. Capacity step valve 2 compressor 1
44. Capacity step valve 3 compressor 1
45. By-pass gas valve compressor 1start
46. Direct start: compressor 2 start
PW start: relay 1 of the compressor 2
Star-delta start: relay line 1 of the compressor 2
47. PW start: relay PW 2 of the compressor
2
Star-delta start: relay line 2 of the compressor 2
48. Star centre of the Star-delta start of the compressor 2
49. Capacity step valve 1 compressor 2
50. Capacity step valve 2 compressor 2
51. Capacity step valve 3 compressor 2
52. By-pass gas valve compressor 2 start
53. Direct start: compressor 3 relay
PW start: relay PW 1 of the compressor
3
Star-delta start: relay line 1 of the compressor 3
54. PW start: relay PW 2 of the compressor
3
Star-delta start: relay line 1 of the compressor 3
55. Star centre of the Star-delta start of the compressor 3
56. Capacity step valve 1 compressor 3
57. Capacity step valve 2 compressor 3
58. Capacity step valve 3 compressor 3
59. By-pass gas valve compressor 3 start
60. Direct start: compressor 4 relay
PW start: PW 1 of the compressor 4
Star-delta start: relay line 1 of the compressor 4
61. PW start: relay PW 2 of the compressor
4
Star-delta start: relay line 1 of the compressor 4
62. Star centre of the Star-delta start of the compressor 4
63. Capacity step valve 1 of the compressor
4
64. Capacity step valve 2 of the compressor
4
65. Capacity step valve 3 of the compressor
4
66. By-pass gas valve compressor 4 start
67. Compressor 5 relay
68. Compressor 6 relay
8.5
Condenser control outputs) proportional configuration (2
Proportional outputs used to configure a proportional output signal to condenser fan control
Parameters involved:
CF68 =
Condenser control configuration for circuit 1
CF69 =
Condenser control configuration for circuit 2
0= 0 ÷ 10Vdc (for external mono or threephase fan control board)
1= 4÷20mA (for external mono or three-phase fan control board)
2= PWM (only for external mono-phase fan control board with cut phase control)
8.6
Proportional output configuration 0 ÷ 10 Vdc (4 outputs)
Parameters involved:
CF70 =
Proportional output 1 configuration
CF71 =
Proportional output 2 configuration
CF72 =
Proportional output 3 configuration
CF73 =
Proportional output 4 configuration
0 Not enabled
1 not used
2 not used
3 not used
4 Auxiliary output 0÷10V n° 1
5 Auxiliary output 0÷10V n° 2
6 Proportional output for modulating compressor 1
7 Proportional output for modulating compressor 2
After the read-out number 4 the display goes from the label “
o 1”
to “
c38
(see input/output polarity), that allow to configure the output as digital output to control an external relay.
Page 25 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
9. Table Of The Parameters
ST 3
ST 4
ST 5
ST 6
ST 7
ST 8
ST 9
MENU SELECTION
Label
Description
ALL
Shows all the parameters
ST
Shows only the Thermoregulation parameters
CF
Shows only the Configuration parameters
SD
Shows only the Dynamic Setpoint parameters
ES
Shows only the Energy Saving, RTC parameters
Cr
Shows only the compressor rack parameters
CO
Shows only the compressor parameters
US
Shows only the Auxiliary Output parameters
FA
Shows only the Fan Control parameters
Ar
Shows only the Antifreeze Control parameters
DF
Shows only the Defrost parameters
FS
Shows only the Sanitary Water parameters
AL
Shows only the Alarm parameters
Thermoregulation
Parameter Description
ST 1
ST 2
Chiller Setpoint
Chiller minimum Setpoint
Chiller maximum Setpoint
Heat pump setpoint
Heat pump minimum Setpoint
Heat pump maximum Setpoint
Regulation band in chiller mode
Regulation band in chiller heat pump
Thermoregulation probe selection in chiller
0= Temperature probe NTC for evaporator inlet
1= Temperature probe NTC for evaporator outlet 1
2= Temperature probe NTC for evaporator outlet 2
3= Temperature probe NTC for common evaporator outlet
4= Temperature NTC probe from remote panel 1
5= Temperature NTC probe from remote panel 2 min max u.m.
Resolution
ST02 ST03 °C/°F dec/int
-30.0
-22
ST01
-30.0
-22
ST04
0.0
0
0.0
0
ST01
70.0
158
ST04
70.0
158
25.0
45
25.0
45
°C
°F
°C
°F
ST05 ST06 °C/°F
°C
°F
°C
°F
°C
°F
°C
°F dec/int dec/int dec/int
Dec int
Dec int
Dec int
Dec int
0 5
Page 26 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
ST 10
ST 11
Pr1
Pr2
Pr3
CF 1
Thermoregulation probe selection in heat pump
0= Temperature probe NTC for evaporator inlet
1= Temperature probe NTC for evaporator outlet 1
2= Temperature probe NTC for evaporator outlet 2
3= Temperature probe NTC for common evaporator outlet
4= Temperature NTC probe from remote panel 1
5= Temperature NTC probe from remote panel 2
6= Temperature probe for water common inlet of the condenser
7= Temperature probe for water inlet of the circuit # 1 condenser
8= Temperature probe for water inlet of the circuit # 2 condenser
9= Temperature probe for water outlet of the circuit # 1 condenser
10= Temperature probe for water outlet of the circuit # 2 condenser
11= Temperature probe for water common otlet of the condenser
ATTENTION
To have the same thermoregulation for chiller and heat pump mode, set the parameters ST09 and ST10 with the same value
Type of thermoregulation
0= Proportional
1= Neutral zone
Password
Password
Password
Display read-out
Parameter Description
dP 1 dP 2 dP 3 dP4 dP5 dP6 dP7 dP8 dP9
Not used
Not used
Not used
Not used
Not used
Display read-out of the VGI890
First probe displayed on Visograph
Second probe displayed on Visograph
Third probe displayed on Visograph
Fourth probe displayed on Visograph
Configuration
Parameter Description
Unit Model
CF 2
CF 3
Type of unit
0= Air / air Chiller
1= Air / water Chiller
2= Water / water Chiller
Selection type rof unit
1= only chiller
2= only heat pump
3= chiller and heat pump
4= heat pump and free cooling
5= chiller, heat pump and free cooling
Condensing unit
0= no
1= si
Compressors
CF 4
Compressors number for circuit 1
1= 1
2= 2
3= 3
4= 4
0
0 min min
0
1
0
0
0
0
0
0
0
0
0
11
1
999
999
999 max M. u. Resolution
33
33
33
33 max M. u. Resolution
2
5
1
4
Page 27 of 52
CF 8
CF 9
CF 10
CF 11
CF 12
CF 13
CF 14
CF 15
CF 16
CF 17
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
CF 5
CF 6
CF 7
CF 18
CF 19
CF 20
Compressors number for circuit 2
0= 0
1= 1
2= 2
3= 3
Number of compressor parzialization
0= none
1= 1
2= 2
3= 3
Analog Inputs
Pressure or temperature analogue input functioning
0 = Temperature / pressure NTC – 4÷20 mA :
The condensing temperature is controlled with NTC probe while for the evaporating pressures of the circuits 1 and 2 and the pressure probe configured as auxiliary output 1 and 2 are controlled with 4÷20mA transducers.
1 = Pressure control with 4÷20 mA:
To control the evaporating and condensing pressures it is necessary a 4÷20mA transducer.
2 = Temperature / pressure NTC – 0÷5Vdc:
The condensing temperature is controlled with NTC probe while for the evaporating pressures of the circuits 1 and 2 and the pressure probe configured as auxiliary output 1 and 2 are controlled with 0÷5Vdc transducers.
3 = Pressure control with 0÷5Vdc:
To control the evaporating and condensing pressures it is necessary a ratiometric 0÷5Vdc transducer.
PB1 Configuration
If configured as digital input
PB2 Configuration
If configured as digital input
PB3 Configuration
If configured as digital input
PB4 Configuration
If configured as digital input
PB5 Configuration
If configured as digital input
PB6 Configuration
If configured as digital input
PB7 Configuration
If configured as digital input
PB8 Configuration
If configured as digital input
PB9 Configuration
If configured as digital input
PB10 Configuration
If configured as digital input
Probe Offset
PB1 Offset
PB2 Offset
PB3 Offset
0
0
0
-12.0
-21
-12.0
-21
-12.0
-21
-5.0
-72
0 o 1
0 o 1
0 o 1
0 o 1
0 o 1
0 o 1
0 o 1
0 o 1
0 o 1
0 o 1
3
3
3
33 c67
33 c67
28 c67
28 c67
28 c67
28 c67
33 c67
33 c67
28 c67
28 c67
12.0
21
12.0
21
12.0
21
5.0
72
°C
°F bar psi
°C
°F
°C
°F
Dec int
Dec int
Dec int dec int
Page 28 of 52
CF 23
CF 44
CF 45
CF 46
CF 47
CF 48
CF 49
CF 50
CF 51
CF 52
CF 53
CF 36
CF 37
CF 38
CF 39
CF 40
CF 41
CF 42
CF 43
CF 54
CF 24
CF 25
CF 26
CF 27
CF 28
CF 29
CF 30
CF 31
CF 32
CF 33
CF 34
CF 35
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
CF 21
PB4 Offset
CF 22
PB5 Offset
PB6 Offset
PB7 Offset
PB8 Offset
PB9 Offset
PB10 Offset
Pressure value at 4mA or 0.5 Vdc of the PB3 transducer
Pressure value at 20mA or 5 Vdc of the PB3 transducer
Pressure value at 4mA or 0.5 Vdc of the PB4 transducer
Pressure value at 20mA or 5 Vdc of the PB4 transducer
Pressure value at 4mA or 0.5 Vdc of the PB5 transducer
Pressure value at 20mA or 5 Vdc of the PB5 transducer
Pressure value at 4mA or 0.5 Vdc of the PB6 transducer
Pressure value at 20mA or 5 Vdc of the PB6 transducer
Digital Inputs
Configuration of ID1
Configuration of ID2
Configuration of ID3
Configuration of ID4
Configuration of ID5
Configuration of ID6
Configuration of ID7
Configuration of ID8
Configuration of ID9
Configuration of ID10
Configuration of ID11
Configuration of ID12
Configuration of ID13
Configuration of ID14
Configuration of ID15
Configuration of ID16
Configuration of ID17
Configuration of ID18
Relay Outputs
Configuration of RL1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-12.0
-21
-12.0
-21
-12.0
-21
-5.0
-72
-12.0
-21
-12.0
-21
-12.0
-21
-5.0
-72
-12.0
-21
-5.0
-72
0 -o1 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67
50.0
725
50.0
725
50.0
725
50.0
725
12.0
21
12.0
21
50.0
725
50.0
725
50.0
725
50.0
725
12.0
21
5.0
72
12.0
21
12.0
21
12.0
21
5.0
72
12.0
21
5.0
72 c68
Bar psi
Bar psi
Bar psi
Bar psi
Bar psi
Bar psi
°C
°F
°C
°F
Bar psi
Bar psi
°C
°F
°C
°F
°C
°F bar psi
°C
°F bar psi
°C
°F bar psi
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int dec int
Dec int
Dec int
Dec int dec int
Dec int dec int
Page 29 of 52
CF 55
CF 56
CF 57
CF 58
CF 59
CF 60
CF 61
CF 62
CF 63
CF 64
CF 65
CF 66
CF 67
CF 68
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
CF 69
CF 70
CF 71
CF 72
Configuration of RL2
Configuration of RL3
Configuration of RL4
Configuration of RL5
Configuration of RL6
Configuration of RL7
Configuration of RL8
Configuration of RL9
Configuration of RL10
Configuration of RL11
Configuration of RL12
Configuration of RL13
Configuration of RL14
Condensing proportional outputs
Circuit 1 output signal:
0= 0 – 10Vdc
1= 4 ÷ 20mA
2= PWM for mono phase fan control board
Circuit 2 output signal:
0= 0 – 10V
1= 4 ÷ 20Ma
2= PWM for mono phase fan control board
Proportional output
Proportional output “out 3”
0= Not enabled
1= Not used
2= Not used
3= Not used
4= Auxiliary output 0÷10V n° 1
5= Auxiliary output 0÷10V n° 2
6= Proportional output for inverter circuit 1 compressor n° 2
7= Proportional output for inverter circuit 2 compressor n° 2
Relay driver ON / OFF
Proportional output “out 4”
0= Not enabled
1= Not used
2= Not used
3= Not used
4= Auxiliary output 0÷10V n° 1
5= Auxiliary output 0÷10V n° 2
6= Proportional output for inverter circuit 1 compressor n° 2
7= Proportional output for inverter circuit 2 compressor n° 2
Relay driver ON / OFF
Proportional output “out 5”
0= Not enabled
1= Not used
2= Not used
3= Not used
4= Auxiliary output 0÷10V n° 1
5= Auxiliary output 0÷10V n° 2
6= Proportional output for inverter circuit 1 compressor n° 2
7= Proportional output for inverter circuit 2 compressor n° 2
Relay driver ON / OFF
0 -o1
0 -o1
0 -o1
0 -o1
0 -o1
0 -o1
0 -o1
0 -o1
0 -o1
0 -o1
0 -o1
0 -o1
0 -o1 c68 c68 c68 c68 c68 c68 c68 c68 c68 c68 c68 c68 c68
0 2
0 2
0 7 o 1 C38
0 7 o 1 C38
0 7 o 1 C38
Page 30 of 52
CF 84
CF 85
CF 86
CF 87
CF 88
CF 89
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
CF 73
CF 74
CF 75
CF 76
CF 77
CF 78
CF 79
CF 80
CF 81
CF 82
CF 83
Proportional output “out 6”
0= Not enabled
1= Not used
2= Not used
3= Not used
4= Auxiliary output 0÷10V n° 1
5= Auxiliary output 0÷10V n° 2
6= Proportional output for inverter circuit 1 compressor n° 2
7= Proportional output for inverter circuit 2 compressor n° 2
Relay driver ON / OFF
Remote keyboard
Remote keyboard 1 configuration
0= Not enabled
1= Enabled model with ambient temperature sensor
2= Enabled model without ambient temperature sensor
Remote Panel 2 configuration
0= Not enabled
1= Enabled model with ambient temperature sensor
2= Enabled model without ambient temperature sensor
Offset of the probe of the remote terminal 1
0 o 1
0
0
Offset of the probe of the remote terminal 2
-12.0
-21
-12.0
-21
Icon function
Icon function
0= chiller / heat pump 0
1= chiller / heat pump
Chiller / heat pump selection mode
0= Chiller / Heat pump selection by keyboard
1= Chiller / Heat pump selection by digital input
2= Chiller / Heat pump selection by analogue input
Automatic Change over
Automatic change over setpoint for chiller/ heat pump selection
(CF79 = 2)
Automatic change over differential (CF79 = 2)
0
-30.0
-22
0
0
Unit of measurement
°C or °F selection
0= °C / °BAR
1= °F / °psi
Supply voltage frequency
Power supply frequency
0= 50 Hz
1= 60 Hz
2= cc voltage
(ATTENTION
When CF83 = 2 the proportional outputs for fan control are not enabled and the frequency alarm is inhibited)
Serial Address
0
0
Serial address
Firmware Release
1
Eeprom parameter map
Regulation of unbalanced compressors (different power)
Compressor 1 capacity
Compressor 2 capacity
Compressor 3 capacity
0
0
0
7
C38
2
2
12.0
21
12.0
21
1
2
70.0
158
25.0
45
1
2
247
100%
100%
100%
°C
°F
°C
°F
°C
°F
°C
°F
Dec int
Dec int
Dec int
Dec int
Page 31 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Sd 15
Sd 16
Sd 17
Sd 18
Sd 19
Sd 20
Sd 21
Sd 10
Sd 11
Sd 12
Sd 13
Sd 14
Sd 5
Sd 6
Sd 7
Sd 8
Sd 9
CF 90
CF 91
CF 92
CF 93
CF 94
CF 95
Compressor 4 capacity
Compressor 5 capacity
Compressor 6 capacity
Maximum number of start up of the compressor in 15 minutes
0= Not enabled
Working mode of the compressor
Working mode of the compressor
0 = chiller and heat pump
1 = only chiller
2 = only heat pump
Hybrid exchangers
Enable hybrid exchangers
Dynamic Setpoint
Parameters Description
Sd 1
Maximum dynamic Offset in chiller mode
Sd 2
Sd 3
Maximum dynamic Offset in heat pump mode
External air setpoint in chiller mode
Sd 4
External air setpoint in heat pump mode
External air differential in chiller mode
External air differential in heat pump mode
Dynamic set point: summer offset analog 1
Dynamic set point: winter offset analog 1
Summer outside temperature analog 1
Winter outside temperature analog 1
Summer outside temp. differential analog 1
Winter outside temp. differential analog 1
Dynamic set point: summer offset analog 2
Dynamic set point: winter offset analog 2
Summer outside temperature analog 2
Winter outside temperature analog 2
Summer outside temp. differential analog 2
Winter outside temp. differential analog 2
Dynamic set point: summer offset relay AUX1
Dynamic set point: winter offset relay AUX1
Summer outside temperature relay AUX1
0
0
0
0
100%
100%
100%
15
0 2
0 1
54
30.0
54
30.0
54
70.0
158
70.0
54
70.0
158
70.0
158
30.0
54
30.0
158
30.0
54
30.0
54
30.0
54
30.0
max
30.0
54
30.0
54
70.0
158
70.0
158
30.0
54
30.0
54
30.0
54
30.0
54
70.0
158
-54
-30.0
-54
-30.0
-54
-30
-22
-30
-54
-30
-22
-30
-22
-30.0
-54
-30.0
-22
-30.0
-54
-30.0
-54
-30.0
-54
-30.0
min
-30.0
-54
-30.0
-54
-30.0
-22
-30
-22
-30.0
-54
-30.0
-54
-30.0
-54
-30.0
-54
-30
-22
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
M. u. Resolution
°C
°F
°C
°F
°C
Dec int
Dec int
Dec int
Dec int
Dec int
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°F
°C
°F
°C
°F
°C
°F
°C
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Page 32 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Sd 22
Winter outside temperature relay AUX1
Sd 23
Summer temperature differential relay AUX1
Sd 24
Winter temperature differential relay AUX1
Sd 25
Dynamic set point: summer offset relay AUX2
Sd 26
Dynamic set point: winter offset relay AUX2
Sd 27
Summer outside temperature relay AUX2
Sd 28
Winter outside temperature relay AUX2
Sd 29
Summer temperature differential relay AUX2
Sd 30
Winter temperature differential relay AUX2
Energy saving
Parameters Description
ES 1
ES 2
ES 3
ES 4
ES 5
ES 6
ES 7
ES 8
Start of the Time band 1 (0÷24)
End of the Time Band 1 (0÷24)
Start of the Time band 2 (0÷24)
End of the Time Band 2 (0÷24)
Start of the Time band 3 (0÷24)
End of the Time Band 3 (0÷24)
Monday: energy saving activated
Automatic unit on-off
Tuesday energy saving activated
Automatic unit on-off
ES 9
ES 10
ES 11
ES 12
ES 13
ES 14
Wednesday energy saving activated
Automatic unit on-off
Thursday energy saving activated
Automatic unit on-off
Friday energy saving activated
Automatic unit on-off
Saturday energy saving activated
Automatic unit on-off
Sunday energy saving activated
Automatic unit on-off
Energy Saving setpoint offset in chiller mode
ES 15
ES 16
ES 17
ES 18
Cr1
-30.0
-54
-30
-22
-30
-22
-30.0
-54
-30.0
-54
-30
-22
-30.0
-54
-30.0
-54
-30.0
-54 min
0
0
0
0
0
0
30.0
54
70.0
158
70.0
158
30.0
54
30.0
54
70.0
158
30.0
54
30.0
54
30.0
54 max
24.00
24.00
24.00
24.00
24.00
24.00
0 - 0 7 - 7
0 - 0
0 - 0
0 - 0
0 - 0
0 - 0
7 - 7
7 - 7
7 - 7
7 - 7
7 - 7
Energy Saving differential in chiller mode
Energy Saving setpoint offset in heat pump mode
Energy Saving differential in heat pump mode
Maximum ON time when the unit is switched on by keyboard starting from OFF state by RTC
0= Not enabled
Compressors rack
Type of functioning compressor rack
0= Not enabled
1= regulation by ST09 probe
2 = regolation by pressure probe (Evaporator pressure probe)
0
0 - 0 7 - 7
-30.0
-54
0.0
0
-30.0
-54
0.0
0
30.0
54
25.0
45
30.0
54
25.0
45
1
2
250
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F udm Risoluzione
Hr
Hr
Hr
Hr
Hr
Hr
10 Min
10 Min
10 Min
10 Min
10 Min
10 Min
°C
°F
°C
°F
°C
°F
°C
°F
Min
Dec int
Dec int
Dec int
Dec int
10 Min
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Page 33 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Cr2
Cr3
Cr4
Cr5
Set point compressor suction probe
Minimum set point compressor suction probe
Cr03
0
Cr6
Cr7
Maximum set point compressor suction probe
Regulation band suction probe
Set energy saving compressor rack
Differential energy savingcompressor rack
Cr8
Cr9
Number of compressors enabled in case of failure probe
0 ÷ 6
Number od ventilation step in case of failure probe
0 ÷ 4
Compressors
Parameters Description
CO 1
Minimum compressor ON time after the start-up.
CO 2
CO 3
Minimum compressor OFF time after the switching off.
ON delay time between two compressors or compressor and valve. During this time the led of the next resource is blinking.
Cr03
0.1
1
0.0
0
0.1
1
0
0 min
0
0
1
Cr04
4
250
250
Cr03
50
725
14.0
203
50.0
725
14.0
203
6 max
250
Bar
Psi
Bar
Psi
Bar
Psi
Bar
Psi
Bar psi
Bar
Psi
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int udm Risoluzione
10
10 sec sec
10 sec
10 sec
Sec
CO 4
CO 5
CO 6
CO 7
CO 8
CO 9
CO 10
OFF delay time between two compressors or compressor and valve. During this time the led of the next resource is blinking.
Output time delay after the main power supply start-up to the unit.
All the loads are delayed in case of frequently power failures.
Capacity Control
Functioning (see Capacity Control)
0= With on/off steps
1= Continuous with steps and direct action
2= Continuous with steps and reverse action
3= Continuous with steps and direct total action
Start-up with minimum compressor power / automatic startunloading valve
0 = Only at the compressor start-up (Minimum power automatic start-unloading valve off)
1= At the compressor start-up and during the termoregulation
(Minimum power / automatic start-unloading valve off)
2 = Only at the screw compressor start-up (Minimum power automatic start-unloading valve off)
3= At the compressor start-up and during the termoregulation
(Minimum power / Unloading valve ON with compressor off)
Relay ON time of the Solenoid valve Intermittent for screw compressor, with 0 the function is not enabled.
Relay OFF time of the Solenoid valve Intermittent for screw compressor
Compressor start-up
Kind of compressor start-up
0= Direct ( vedi avviamento compressors )
1= Part - winding
2= Star-delta
0
0
0
0
0
0
0
250
250
3
3
250
250
2
Sec
10
Sec
Sec
Sec
10 sec
Page 34 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
CO 11
CO 12
CO 13
CO 14
CO 15
CO 16
CO 17
CO 18
CO 19
CO 20
CO 21
CO 22
CO 23
CO 24
CO 25
CO 26
CO 27
CO 28
CO 29
CO 30
CO 31
If CO10= 1 part - winding start-up time. To change the time delay between the two contactors of the two compressor circuits.
Se CO10= 2 Star-delta start-up time. To change the time delay between the contactor of the line 1 and the contactor of the centre of the star. (see part – winding /start-triangle functioning)
If CO10= 2 Time of Star-delta start. Time delay to turn off the centre star contactor and to turn on the line 2 contactor (see Stardelta functioning)
By-pass gas valve start-up time / automatic start-unloading valve
(capacity step control)
0
0
0
Rotating – Balancing – Compressors Thermoregulation
Compressor rotation (See compressor rotation)
0 = Sequential
1 = Compressors rotation based on time running hours
0
2 = Compressors rotation based on number of starts-up
Circuit balancing (See Circuit balancing)
0= Circuit saturation
1= Circuit balancing
0
Evaporator water pump
Operative mode of the evaporator pump / supply fan (See
Evaporator pump function)
0= Not enabled (evaporator pump or supply fan).
1= Continuous. When the unit is running in Chiller or HP the pump or the supply fan is running.
2= With compressor. When a compressor is running also the pump or the supply fan is running.
ON compressor delay after water pump / supply fan start-up (See water pump functioning).
OFF delay evaporator water pump / supply fan after compressor switching OFF. This delay is also active when the unit is turned in stand-by (See evaporator water pump function).
Number of time running hours for pump rotation (See water pump group function)
Time to make run the pumps together before rotating from one to the other (See water pump group function)
Condenser water pump
Operative mode for condenser water pump (See condenser water pump function)
0= Not enabled.
1= Continuous. When the unit is running in Chiller or HP the is running.
2= With compressor. When a compressor is running also the pump is running.
Free
OFF delay condenser water pump after compressor switching
OFF. This delay is also active when the unit is turned in stand-by
(See evaporator water pump function).
Number of time running hours for pump rotation (See water pump group function).
Time to make run the pumps together before rotating from one to the other (See water pump group function).
Load maintenance
Compressor 1 hour counter set
Compressor 2 hour counter set
Compressor 3 hour counter set
Compressor 4 hour counter set
Compressor 5 hour counter set
Compressor 6 hour counter set
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
100
50
250
Dec.
di
Sec
Dec.
di
Sec sec
2
1
2
250
250
Min
Min
999 10Hr
250 Sec
2
250 Min
999 10Hr
250 Sec
999 10 Hr
999 10 Hr
999 10 Hr
999 10 Hr
999 10 Hr
999 10 Hr
0.1 sec
0.1 sec
10Hr
10Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
Page 35 of 52
CO 44
CO 45
CO 46
CO 47
CO 48
CO 49
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
CO 32
CO 33
CO 34
CO 35
CO 36
CO 37
CO 38
CO 39
CO 40
CO 41
CO 42
CO 43
CO 50
CO 51
CO 52
CO 53
CO 54
“Evaporator pump / Supply fan” hour counter set
2nd Evaporator pump hour counter set
Condenser pump hour counter set
2nd Condenser pump hour counter set
Pump down
Pump down operating mode (See pump down ON/OFF function)
0= Not enabled
1= Unit off with pump–down, unit on without pump–down
2= Unit off with pump–down, unit on with pump–down
3= Chiller mode off with pump–down, chiller mode on without pump–down
4= Chiller mode off with pump–down, chiller mode on with pump– down
Pump–down pressure setpoint (See pump down ON/OFF function)
Pump-down pressure differential (See pump down ON/OFF function)
Maximum pump–down time duration at start-up and stop (See pump down ON/OFF function)
Evaporator Unloading
Unloading compressor setpoint in chiller. From high temperature of the evaporator water inlet (See unloading function).
Unloading Differential. From high temperature of the evaporator water inlet (See unloading function).
Delay time to engage the Unloading function from high temperature of the evaporator water inlet (See unloading function).
Maximum unloading duration time to keep activated the
Unloading function from high temperature of the evaporator water inlet (See unloading function).
Condenser Unloading
Unloading compressor setpoint. From temperature / pressure in chiller mode (See unloading function).
Unloading Differential. From temperature / pressure in chiller mode (See unloading function).
Unloading compressor setpoint. From temperature / pressure in
HP mode (See unloading function).
Unloading Differential. From temperature / pressure in HP mode
(See unloading function).
Maximum unloading duration time from temperature/pressure control.
Number of steps for circuit with active unloading
1= 1st step
2= 2nd step
3= 3rd step
Minimum ON time of the capacity step after the unloading function start (only for capacity compressor)
Compressor liquid injection
Setpoint of the solenoid valve (on) of the liquid injection
0
0
0
1
0
1
1
Setpoint of the solenoid valve (off) of the liquid injection
Management resource in neutral zone
Maximum time of work in neutral zone without insert resource
Maximum time of work in neutral zone without rotation resource
Evaporator low water temperature Unloading
0
0
0
0
0.0
0
0
0
0
0
0
0
0
0
-30
0
0.0
0
0
0
0.0
0
0
0
0.0
0
999
999
999
999
4
50.0
725
14.0
203
250
70.0
725
25.0
45
250
250
50.0
725
14.0
203
50.0
725
14.0
203
250
3
250
150
302
25.0
45
250
999
10 Hr
10 Hr
10 Hr
10 Hr
Bar
Bar
Sec
Min
Bar psi
Bar
Psi
Bar psi
Bar
Psi
Min
°C
°F
°C
°F
10
Sec
Sec
Hr psi psi
°C
°F
°C
°F
Min
10 Hr
10 Hr
10 Hr
10 Hr
Dec int
Dec int
Dec int
Dec int
10sec
Dec int
Dec int
Dec int
Dec int
Dec / int int
Dec int
10 Min
1Hr
Page 36 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
CO 55
CO 56
CO 57
Set point unloading compressor from low evaporator water temperature
Differential unloading compressor from low evaporator water temperature
Maximum unloading duration time from low evaporator water temperature
-30.0
-22
0.1
0
0
70.0
158
25.0
45
°C
°F
°C
°F
Dec int
Dec int
250 Min
CO 58
CO 59
CO 60
CO 61
CO 62
Pump down to time maximum time pump-down in stopped
CO58 = 0 Not enabled maximum time pump-down in started
CO59 = 0 Not enabled
Compressor inverter controlled
Maximum time start up compressor inverter controlled
Minimum value proportional output from start up compressor
0
0
0
0
250
250
250
100
Sec
Sec sec
%
CO 63
CO 64
CO 65
CO 66
Minimum time capacity variation from start up compressor inverter controlled
Minimum percentage continuative of work of the compressor inverter controlled before to start counting CO64 time
Maximum time continuative of work of the compressor with percentage less of CO63
Time of forcing the compressor inverter controlled to the maximum power
Maximum time continuative of work of the compressor inverter controlled
0
0
0
0
250
100
250
250 sec
%
Min sec
10 Min
10sec
0 999 Hr 1Hr
CO 67
CO 68
CO 69
CO 70
CO 71
Minimum value of the compressor 1 inverter controlled
Maximum value of the compressor 1 inverter controlled
Minimum value of the compressor 2 inverter controlled
Maximum value of the compressor 2 inverter controlled
Minimum time capacity variation compressor inverter controlled
Tamdem function
Maximum operating time of a single compressor
CO 72
0
CO 73
CO 74
CO 75
Load maintenance
Sanitary water pump hour counter
Solar panel water pump hour counter
4 way valve
Forced time to reverse the 4 way valve when the compressor is switched off
Auxiliary relay menu function
Parameters Description
Auxiliary relay of the circuit 1
0 min
0
0
0 CO68
CO67 100
0
CO69 100
1
CO70
250
250
999
999
250 max
%
%
%
% sec
Min
10 Hr
10 Hr sec
10 Hr
10 Hr
M. U. Resolution
Page 37 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
US 1
US 2
US 3
US 4
US 5
Auxiliary relay 1 operating mode (See graph and auxiliary relay functions)
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
Analog input configuration for auxiliary relay 1 control. Allows to select which probe value Pb1..Pb10 controls the relay
Auxiliary relay 1 summer minimum set point
Auxiliary relay 1 summer maximum set point
0
1
-30.0
-22
0.0
0
US5
4
10
US5
70.0
158
50.0
725
US3 US4
Auxiliary relay 1 summer set point
US 6
US 7
Auxiliary relay 1 winter minimum set point
Auxiliary relay 1 winter maximum set point
-30.0
-22
0.0
0
US8
US8
70.0
158
50.0
725
US 8
US 9
US 10
US 11
US 12
US6 US7
Auxiliary relay 1 winter set point
Auxiliary relay 1 summer differential
Auxiliary relay 1 winter differential
Auxiliary relay circuit 2
Auxiliary relay 2 operating mode (See graph and auxiliary relay functions)
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
Analogue input configuration for auxiliary relay 2 control . Allows to select which probe value Pb1..Pb10 controls the relay
0.1
0
0.1
1
0.1
0
0.1
1
0
1
4
10
25.0
45
14.0
203
25.0
45
14.0
203
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Page 38 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
US 13
Auxiliary relay 2 summer minimum set point
US 14
Auxiliary relay 2 summer maximum set point
US 15
Auxiliary relay 2 summer set point
US 16
Auxiliary relay 2 winter minimum set point
US 17
Auxiliary relay 2 winter maximum set point
US 18
Auxiliary relay 2 winter set point
US 19
Auxiliary relay 2 summer differential
US 20
US 21
US 22
US 23
US 24
Auxiliary relay 2 winter differential
Maximum operating time of auxiliary realys
Auxiliary proportional output n° 1
Auxiliary proportional output n° 1 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
Analogue input configuration for auxiliary control 1
Allows to select which probe value Pb1..Pb10 controls output
Analog output 1 summer minimum set point
US 25
Analog output 1 summer maximum set point
-30.0
-22
0.0
0
US15
70.0
158
50.0
725
US13 US14
0.1
0
0.1
1
0
0.1
0
0.1
1
US15
-30.0
-22
0.0
0
US18
US18
70.0
158
50.0
725
US16 US17
25.0
45
14.0
203
25.0
45
14.0
203
250 min
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
0 4
1
-30.0
-22
0.0
0
10
US26
US26
70.0
158
50.0
725
°C
°F
Bar
Psi
°C
°F
Bar
Psi
Dec int
Dec int
Dec int
Dec int
Page 39 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
US 26
Analog output 1 summer set point
US 27
Analog output 1 winter minimum set point
US 28
Analog output 1 winter maximum set point
US 29
Analog output 1 winter set point
US 30
Analog output 1 summer differential
US 31
US 32
US 33
US 34
US 35
US 36
Analog output 1 winter differential
Analog output 1 minimum value
Analog output 1 maximum value
Auxiliary proportional output n° 2
Auxiliary proportional output n° 2 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
Analogue input configuration for auxiliary 2 control
Allows to select which probe value Pb1..Pb10 controls output
Analog output 2 summer minimum set point
US 37
Analog output 2 summer maximum set point
US 38
Analog output 2 summer set point
US 39
Analog output 2 winter minimum set point
US24 US25
-30.0
-22
0.0
0
US29
US29
70.0
158
50.0
725
US27 US28
0.0
0
0.0
0
0.0
0
0.0
0
25.0
45
14.0
203
25.0
45
14.0
203
0 US33 %
US32 100 %
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
0
1
-30.0
-22
0.0
0
-30.0
-22
0.0
0
4
10
US38
US38
70.0
158
50.0
725
US36 US37
US41
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
Page 40 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
US 40
US 41
US 42
US 43
Analog output 2 winter maximum set point
Analog output 2 winter set point
Analog output 2 summer differential
US 44
US 45
US 46
Analog output 2 winter differential
Analog output 2 minimum value
Analog output 2 maximum value
Operation mode under minimum value
Condenser fan
Parameters Description
FA 1
Fan configuration output
0 = Not enabled
1 = Always on
2 = ON/OFF regulation with steps
3 = ON/OFF Continuous regulation
4 = Proportional speed control
FA 2
FA 3
FA 4
Fan operating mode
0= Dependent from the compressor
1= Independent from the compressor
If the condenser fan control is the triac output, when the regulation starts the trigger output will drive the condenser fan at the maximum voltage for the time FA 3 then, then the regulation will follow the temperature/pressure of the probe.
Phase shifting of the fan motor
FA 5
FA 6
FA 7
FA 8
FA 9
Number of condensing circuits
0= one condenser circuit
1= tow condenser circuits
Pre-ventilation time before turning on the compressor in chiller mode.
To turn on the fan at the maximum speed before the compressor and reduce the successive condensing temperature/pressure increasing. (only if FA01=4)
Fan in Chiller mode
Minimum speed for condenser fan in Chiller mode.
To set the minimum fan speed percentage value (30..100%), it is related to the fan power supply.
Maximum speed for condenser fan in Chiller mode.
To set the maximim fan speed percentage value (30..100%), it is related to the fan power supply.
Proportional speed control FA01 = 4
Temperature or pressure limit to enable the minimum speed FA 7
ON/OFF regulation FA01 = 2/3
SETpoint step n° 1 min
0
0
0
0
0
0
0
0
-30.0
-22
0.0
0
US41
70.0
158
50.0
725
US39 US40
0.0
0
0.0
0
0.0
0
0.0
0
25.0
45
14.0
203
25.0
45
14.0
203
0 US45 %
US44 100 %
0 1
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi max
4
1
250
8
1
250
100
100
70.0
158
50.0
725
M. U. Resolution
Sec
Micro
Sec
Sec
%
%
°C
°F
Bar
Psi
250 s
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Page 41 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
FA 10
FA 11
FA 12
FA 13
FA 14
FA 15
FA 16
FA 17
FA 18
FA 19
FA 20
FA 21
Proportional speed control FA01 = 4
Temperature or pressure limit to enable the maximum speed FA
8
ON/OFF regulation FA01 = 2/3
SETpoint step n° 2
Proportional speed control FA01 = 4
Proportional band for condenser fan control in chiller
To set the temperature/pressure differential between the minimum and the maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 1
Proportional speed control FA01 = 4
CUT-OFF differential in chiller. To set a temperature/pressure differential to stop the fan.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 2
Over ride CUT- OFF in chiller. To set a temperature/pressure differential to keep the minimum fan speed.
-30.0
-22
0.0
0
0.0
0
0.0
0
0.0
0
0.0
0
0.0
0
0.0
0
CUT-OFF time delay. To set a time delay before activating the
CUT-OFF function after the fan start-up.
If after the compressor start-up the proportional regulator requires to turn off the fan (cut-off) and FA14 0, the fan is on at the minimum speed for the time set in this parameter. If FA14=0 the function is disabled.
Night speed in chiller. To set the maximum fan speed percentage value (30..100%), it is related to the fan power supply.
Fan in Heat pump mode
Minimum speed for condenser fan in Heat Pump mode.
To set the minimum fan speed percentage value (30..100%), it is related to the fan power supply.
Maximum speed for condenser fan in Heat Pump mode.
To set the maximum fan speed percentage value (30..100%), it is related to the fan power supply.
Proportional speed control FA01 = 4
Temperature or pressure limit to enable the minimum speed
FA16
ON/OFF regulation FA01 = 2/3
SETpoint step n° 1
Proportional speed control FA01 = 4
Temperature or pressure limit to enable the maximum speed
FA17
ON/OFF regulation FA01 = 2/3
SETpoint step n° 2
Proportional speed control FA01 = 4
Proportional band for condenser fan control in heat pump
To set the temperature/pressure differential between the minimum and the maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 1
Proportional speed control FA01 = 4
CUT-OFF differential in heat pump. To set a temperature/pressure differential to stop the fan.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 2
0
0
0
0
0.0
0
0.0
0
0.0
0
0.0
0
-30.0
-22
0.0
0
-30.0
-22
0.0
0
70.0
158
50.0
725
25.0
45
14.0
203
25.0
45
14.0
203
25.0
45
14.0
203
250
100
100
100
70.0
158
50.0
725
70.0
158
50.0
725
25.0
45
14.0
203
25.0
45
14.0
203
Sec
%
%
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
%
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Page 42 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
FA 22
FA 23
FA 24
FA 25
FA 26
FA 27
FA 28
FA 29
Over ride CUTOFF in Heat pump. To set a temperature/pressure differential to keep the minimum fan speed.
0.0
0
0.0
0
Night speed in Heat pump. To set the maximum fan speed percentage value (30..100%), it is related to the fan power supply.
Hot start
Hot start setpoint
0
Hot start differential
-30.0
-22
0.0
0
ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
3 / 4 step condenser Fan in Chiller mode
ON/OFF regulation FA01 = 2/3
SETpoint step n° 4
ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
3 / 4 step condenser Fan in heat pump
ON/OFF regulation FA01 = 2/3
SETpoint step n° 4
Antifreeze heaters – Integration heating - boiler
-30.0
-22
0.0
0
-30.0
-22
0.0
0
-30.0
-22
0.0
0
-30.0
-22
0.0
0
Parameter Description
Ar 1
Anti-freeze heaters/integration heating setpoint for air/air unit in
Chiller mode.
Ar 2
To set a temperature value, below this value the anti-freeze relay is activated.
Regulation band for antifreeze in Chiller mode.
min
-30.0
-22
0.1
0
Ar 3
Ar 4
Set Anti-freeze heaters/integration heating setpoint for air/air unit in HP mode.
To set a temperature value, below this value the anti-freeze relay is activated.
Regulation band for antifreeze in HP mode.
-30.0
-22
-30.0
-22
Ar 5
Ar 6
Antifreeze heaters / integration heating in defrost
0= ON only with thermoregulation control
1= ON with thermoregulation and during the defrosting cycle
Antifreeze probe to manage heaters / support heaters in Chiller mode.
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
0
0
70.0
158
25.0
45 max
70.0
158
25.0
45
3
70.0
158
50.0
725
70.0
158
50.0
725
70.0
158
50.0
725
70.0
158
50.0
725
25.0
45
14.0
203
100
70.0
158
70.0
158
1
°C
°F
Bar
Psi
%
°C
°F
°C
°F
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi
°C
°F
Bar
Psi m. u. Risoluzione
°C
°F
°C
°F
Dec int
Dec
Int
°C
°F
°C
°F
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Page 43 of 52
Ar 17
Ar 18
Ar 19
Ar 20
Ar 12
Ar 13
Ar 14
Ar 15
Ar 16
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Ar 7
Ar 8
Ar 9
Ar 10
Ar 11
Ar 21
Ar 22
Antifreeze probe to manage heaters / support heaters in HP mode.
0= Not enabled
1= Evaporator inlet.
2= Evaporator outlet 1 and 2.
3= Evaporator outlet 1 and 2 and common outlet.
Thermoregulation probe for anti-freeze / condenser heaters.
0= not enabled.
1= Condenser common water inlet probe.
2= Condenser common water inlet and condenser inlet 1 / 2 probe.
3= Condenser water outlet 1 / 2 probe.
4= Condenser water outlet 1 / 2 and common outlet.
Anti-freeze heaters or condenser/evaporator water pump control with unit in remote OFF or stand-by mode:
0= Control not enable
1=Controlled by anti-freeze thermoregulation.
Anti-freeze heaters control for condenser/evaporator faulty probe:
0= Anti-freeze heaters OFF
1= Anti-freeze heaters ON
Boiler function
Boiler function
0=Not enabled
1=Enabled for integration heating
2= Enabled for heating
External air temperaure setpoint for boiler heaters (on)
Temperature differential for boiler heaters (off)
Time delay before turning the boiler on
Boiler function in Chiller mode
Setpoint for boiler heaters (on) in chiller
Proportional band for boiler heaters in chiller
0
0
0
0
0
-30.0
-22
0
0
0
Boiler function in heat pump
Setpoint for boiler heaters (on) in HP
Proportional band for boiler heaters in HP
External air setpoint to stop the compressor as integration function
External air differential to stop the compressor as integration function
Anti freeze alarm
Termoregulation probe anti freeze alarm in chiller mode
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
4= External temperature
Termoregulation probe anti freeze alarm in heat pump mode
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
4= External temperature
-30.0
-22
-30.0
-22
-30.0
-22
0.1
0
-30.0
-22
0.1
0
0
0
3
4
1
1
2
70.0
158
25.0
45
250
70.0
158
70.0
158
70.0
158
25.0
45
70.0
158
25.0
45
4
4
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
Dec int
Dec int
Min
Dec int
Dec int
Dec int
Dec int
Dec int
Dec int
Page 44 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
Ar 23
Ar 24
Ar 25
Termoregulation probe anti freeze alarm water condenser
0= not enabled.
1= Condenser common water inlet probe.
2= Condenser common water inlet and condenser inlet 1 / 2 probe.
3= Condenser water outlet 1 / 2 probe.
4= Condenser water outlet 1 / 2 and common outlet.
Anti freeze alarm
Water pump / antifreeze alarm in OFF/ stand-by
0= Aways in OFF
1= ON only with thermoregulation control
Termoregulation probe water pump in antifreeze mode
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
4= External temperature
Set point starting water pump in antifreeze alarm
0
0
0
Ar 26
Ar 27
Differential starting water pump in antifreeze alarm
-30.0
-22
0.1
0
Defrost
dF 4 dF 5 dF 6 dF 7 dF 8 dF 9 dF 10
Parameter Description
dF 1 dF 2 dF 3 dF 11 dF 12 dF 13 dF 14 dF 15 dF 16
Defrost configuration:
0= Not enabled
1= Temperature / pressure
2= start depends on par. dF24 stop for time duration
3= start depends on par. dF24 stop for external contact
4= defrost with condenser fan
Temperature or pressure of the defrost start-up min
0
Temperature or pressure of the defrost stop
Minimum defrost duration.
Maximum defrost duration.
Time delay between the defrost of two circuits
OFF compressor delay before the defrost
OFF compressor delay after the defrost
Defrost interval time of the same circuit
Temperature setpoint for combined defrost of the 1st circuit after parameter DF10 counting.
Temperature setpoint for combined defrost end of the 1st circuit.
Temperature setpoint for combined defrost of the 2nd circuit after parameter DF10 counting.
-30.0
-22
-30.0
-22
Temperature setpoint for combined defrost end of the 2nd circuit.
-30.0
-22
Activation of all the steps of the 1st circuit during the defrost.
0= Not enabled
1= Enabled
Activation of all the steps of the 2nd circuit during the defrost.
0= Not enabled
1= Enabled
Time delay between two compressor ON in defrost mode
0
1
-30.0
-22
0
0
0
0
-30.0
-22
0.0
0
-30.0
-22
0.0
0
0
0
0
4
1
4
70.0
158
25.0
45 max
4
1
250
250
250
250
250
250
99
70.0
158
70.0
158
50.0
725
70.0
158
50.0
725
70.0
158
70.0
158
70.0
158
1
°C
°F
°C
°F udm Risoluzione
°C
°F bar psi
°C
°F bar psi
Sec
Min
Min
Sec
Sec
Min
°C
°F
°C
°F
°C
°F
°C
°F
Sec
Dec int
Dec int
Dec int
Dec
Int
Dec int
Dec
Int
Dec int
Dec int
Dec int
Dec int
Page 45 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
dF 17 dF 18
Fan control during defrost / dripping time
0= Not enabled
1= Only in defrost
2= For both functions defrost / dripping time
Pressure / temperature setpoint to force the ventilation ON during the defrost.
0
-30.0
-22
0.0
0
2
70.0
158
50.0
725
°C
°F bar psi
Dec int
Dec
Int
dF 19 dF 20 dF 21
Forced defrost
Minimum time delay before a forced defrost
Pressure / temperature setpoint for a forced defrost
Forced defrost differential
0
-30.0
-22
0.0
0
0.1
0
0.0
0
250
70.0
158
50.0
725
25.0
45
14.0
203 sec
°C
°F bar psi
°C
°F
Bar
Psi
Dec int
Dec int
Dec int
Dec int
dF 22 dF 23
Defrost operative mode
Defrost start-up with 2 circuits
0= Independent
1= If both have reached the necessary requirements
2= If one has reached the necessary requirements
End defrost for two circuits and common ventilation.
0= Independent
1= If both have reached the necessary end defrost requirements
2= If one has reached the necessary end defrost requirements
Start / stop defrost selection
Parameters description
dF 24
Start / stop defrost probe
0= start and stop with condenser temperatur / pressure probe
1= start with evaporator pressure probe / stop with condenser temperatur / pressure probe
2= start with condenser temperatur / pressure probe / stop with evaporator pressure probe
3= start and stop with evaporator pressure probe
Supply fan operating mode during defrost cycle
dF 25
min
0
Stop supply fan diuring defrost cycle
0= Not enabled
1= enable
Defrost only with condenser fan
0
dF 26 dF 27 dF 28 dF 29 dF 30
Set point to enable defrost with condenser fan
Hybrid exchangers summer set point
Hybrid exchangers summer differential
Hybrid exchangers winter set point
Hybrid exchangers winter differential
-30.0
-22
-30.0
-22
0.1
0
-30.0
-22
0.1
0
Sanitary water
Parameters Description
FS 1
FS 2
FS 3
Sanitary water regulation mode
Sanitary water thermoregulation priority
Sanitary water thermoregulation set point
0
0
2
2 max
3
1
70.0
158
70.0
158
25.0
45
70.0
158
25.0
45 udm
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F resolution min
0 max
2 m. u. Resolution
0 1
FS05 FS06 °C/°F dec/int
Dec int
Dec int
Dec int
Dec int
Dec int
Page 46 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
FS 4
Sanitary water thermoregulation band
FS 5
Minimum value of the sanitary water set point
FS 6
FS 7
FS 8
FS 9
FS 10
FS 11
FS 12
FS 13
FS 14
FS 15
Maximum value of the sanitary water set point
Full loads enabling to reach the sanitary water set point
Heaters enabling during the sanitary water thermoregulation
Operation working time to activate the heaters during the sanitary water thermoregulation
Time delay to activate the sanitary water valve
Reversing cycle delay during sanitary water thermoregulation
Antilegionella function operating mode
Delay time between two Antilegionella cycles
Antilegionella Set point
Minimum value of the Antilegionella set point
FS 16
FS 17
FS 18
FS 19
FS 20
Maximum value of the Antilegionella set point
Hour selection for the Antilegionella activation
Day selection for the Antilegionella activation
Minimum operating working time of the Antilegionella cycle
Temperature band for heaters deactivation during Antilegionella cycle
FS 21
Differential value to enable the freecooling function
FS 22
FS 23
FS 24
Differential value for the free cooling regulation
Set point for solar panel activation
Differential value for solar panel deactivation
FS 25
FS 28
Minimum value of the solar panel set point
FS 26
FS 27
Maximum value of the solar panel set point
Delay time to activate the sanitary water valve starting from pump activation
Delay time to deactivate the sanitary water pump starting from valve deactivation
Maximum operating working time of the Antilegionella cycle
FS 29
FS 30
Sanitary water: security set point
FS 31
FS 32
FS 33
Sanitary water: security differential
Sanitary water: minimum interruption time
Sanitary water pump operation mode
Alarms
Parameters Description
AL 1
AL 2
Low alarm
Low pressure alarm delay from analog and digital input
Low pressure alarm delay from digital input after compressor stop if the low pressure switch is used for the pump down.
AL02= 0 low pressure alarm not enable with compressor OFF
AL02≠ 0 low pressure alarm enable after AL02 time with compressor OFF min
0
0
0
0
-30.0
-22
0.1
0
0
0
0.1
0
-30.0
-22
25.0
45
FS06
FS05
0
0
0
70.0
158
1
1
250 Min
0
0
0
0.1
0
0
0
0
0 sec sec
FS15 FS16 °C/°F
-30.0
-22
FS14
250
250
1
250
FS14
Hr
°C
°F
°C
°F
Hr
0.1
FS23
70.0
158
24.00
7
250
25.0
45
25.0
45
25.0
0.1
0 45 °F
FS25 FS26 °C/°F
0.1
0
-30.0
-22
25.0
45
FS23
70.0
158 min
°C
°F
°C
°F
°C
°C
°F
°C
°F
°C
°F
0 250 sec
°C
°F
°C
°F
°C
°F
250
250
70.0
158
25.0
45
250
1 max
250
250 sec min
°C
°F
°C
°F min
Dec int
Dec int
Dec int int int
0 dec/int
Dec int
Dec int
10 min
Dec int
Dec int
Dec int dec/int
Dec int
Dec int
Dec int
Dec int
Dec int m. u. Resolution
Sec
Sec 10 Sec
Page 47 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
AL 3
AL 4
AL 5
AL 6
AL 7
AL 8
AL 9
AL 10
AL 11
AL 12
AL 13
AL 14
AL 15
AL 16
AL 17
AL 18
AL 19
AL 20
Low pressure alarm setpoint from analogue input
Low pressure alarm differential from analogue input
Maximum number of low pressure events from digital/analogue inputs:
Manual reset if AL05 = 0
Automatic reset if AL05 =16
From automatic to manual reset if AL05= 1..15
Low temperature/pressure alarm during defrost
0= Not enabled
1= Enabled
Low temperature/pressure alarm delay during defrost
Low temperature/pressure alarm with unit in OFF or stand – by:
0 = Not enabled
1= Alarm enabled
High Alarm
High temperature/pressure alarm from analogue input
High temperature/pressure alarm differential from analogue input
-30.0
-22
0.0
0
0.1
0
0.0
0
0
0
0
0
-30.0
-22
0.0
0
0.1
0
0.0
0
Oil Alarm
Low oil pressure / level delay from digital input
Minimum time for low oil pressure / level from digital input activation in normal working condition.
Maximum number of low oil pressure/level events:
Always manual reset if AL13= 0
Always automatic reset if AL13 =16
From automatic to manual reset if AL13 = 1..15
Flow alarm
Configuration
0= Not enabled
1= Only for chiller
2= Only for heat pump
3= For both chiller and heat pump
“Flow switch / supply fan overload” alarm delay after pump/fun activation.
Maximum time flow switch alarm active befor to block the water pump
Minimum “Flow switch / supply fan overload” active time duration.
Minimum “Flow switch / supply fan overload” not active time duration.
Compressor overload alarm
Compressor overload alarm delay after compressor start-up
Maximum number of compressor overload alarm events
Always manual reset if AL20 = 0
Always automatic reset if AL20 =16
From automatic to manual reset if AL20 =1..15
Pump down alarm
0
0
0
0
0
0
0
0
0
0
70.0
158
50.0
725
25.0
45
14.0
203
16
16
3
250
16
250
250
250
250
1
250
1
70.0
158
50.0
725
25.0
45
14.0
203
250
250
Sec
Sec
Sec
Sec
Sec
°C
°F bar psi
°C
°F bar psi
Sec
Sec
Sec
°C
°F bar psi
°C
°F bar psi
Dec int
Dec int
Dec int
Dec
Int
Dec int
Dec int
Dec int
Dec int
Page 48 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
AL 21
AL 22
AL 23
AL 24
AL 25
AL 26
AL 27
AL 28
AL 29
AL 30
AL 31
AL 32
AL 33
AL 34
Maximum number of pump down alarm events per hour in stop condition. After this number the alarm is logged, displayed and signalled with alarm relay + buzzer.
Manual reset if AL21 = 0
Automatic reset if AL21 =16
From automatic to manual reset if AL21 =1..15
Maximum number of pump down alarm events per hour in startup condition. After this number the alarm is logged, displayed and signalled with alarm relay + buzzer.
Always manual reset if AL22 = 0
Always automatic reset if AL22 =16
From automatic to manual reset if AL21 =1..15 and parameter
AL23 config.
Select if the pump down alarm must change from automatic to manual reset:
0= Always automatic reset
1= Manual reset after AL21 alarm events
Anti-freeze alarm in Chiller mode
Minimum antifreeze setpoint in chiller (from –30 °C to AL24)
Maximum antifreeze setpoint in chiller (from AL24 to 70 °C)
Setpoint temperature for low anti-freeze alarm, low ambient temperature (air/air), low temperature air outlet (air/air). From
AL24 to AL25.
Differential of alarm reset in Chiller mode for anti-freeze, low ambient air temperature or low outlet air temperature alarms.
Alarm delay for anti-freeze, low ambient air temperature or low outlet air temperature. The temperature must be lower than AL26 for this time duration before having the alarm event.
Maximum number of alarm events anti-freeze, low ambient air temperature or low outlet air temperature before changing from automatic to manual alarm reset:
Always manual reset if AL29 = 0
Always automatic reset if AL29 = 16
From automatic to manual if AL29 = 1. .15
Anti-freeze alarm configuration in chiller
0= to turn the compressors off when the anti-freeze control probe is lower than AL26 (after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are not activated.
1= to turn the compressors off when the anti-freeze control probe is lower than AL26 (after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are activated.
Anti-freeze alarm in Heat pump mode
Setpoint of the minimum limit in heat pump (va da – 30 °C a
AL32)
Setpoint of the maximum limit in heat pump (va da AL31 a 70 °C)
Anti-freeze alarm setpoint in heat pump
Setpoint temperature for low anti-freeze alarm, low ambient temperature (air/air), low temperature air outlet (air/air). (from
AL31 to AL32)
Alarm differential in heat pump. To reset the anti-freeze, low ambient Temperature (air/air), low temperature air outlet (air/air) alarms.
0
0
0
-30.0
-22
AL26
AL26
70.0
158
°C
°F
°C
°F
AL24 AL25 °C/°F
0
0
0
25.0
45
250
°C
°F
Sec
0
0
-30.0
-22
AL33
16
16
1
16
1
AL33
70.0
158
°C
°F
°C
°F
AL31 AL32 °C/°F
0
0
25.0
45
°C
°F
Dec int
Dec int
Dec/int
Dec int
Dec int
Dec int
Dec/int
Dec int
Page 49 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
AL 35
AL 36
AL 37
AL 38
AL 39
AL 40
AL 41
AL 42
AL 43
AL 44
AL 45
AL 46
Anti-freeze alarm delay in HP for low outlet air temperature
(air/air)
Attention
If during the Stand-by or remote off there is an anti-freeze alarm event, and the AL35 <>0, starting the heat pump mode, from keyboard or digital input. In this case the anti-freeze alarm is aborted and the compressor starts for the AL35 time to heat the air or the water.
After the AL35 time if the antifreeze probe value is still lower than
AL33 setpoint, for maximum AL36 seconds, the unit is stopped and the anti-freeze alarm is generated again.
Anti-freeze alarm delay for low air ambient temperature or low outlet air temperature in heat pump normal condition.
The detected temperature must be lower than AL33 for the time
AL36 before giving the alarm
Maximum number of anti-freeze alarm events for low air ambient temperature or low outlet air temperature in heat pump. It sets the alarm reset condition:
Always manual reset AL37 = 0
Always automatic reset AL37 = 16
From automatic to manual reset if AL37 = 1..15
Anti-freeze alarm configuration in heat pump
0= to turn the compressors off when the anti-freeze control probe is lower than AL33 (after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are not activated.
1= to turn the compressors off when the anti-freeze control probe is lower than AL33 (after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are activated.
Compressor high discharge temperature
Compressor high discharge temperature setpoint
0
0
0
0
Compressor high discharge temperature differential
Number of compressor high discharge temperature events per hour to determine the alarm reset condition:
Always manual reset if AL41 = 0
Always automatic reset if AL41 =16
From automatic to manual if AL41 = 1..15
Generic alarm 1
Maximum number of generic alarm events (each event stop the regulation) before turning the alarm from automatic to manual:
Always manual AL42 = 0
Always automatic AL42 =16
From manual to utomatic if AL42 value is between 1 and 15
Generic alarm delay time after the digital input activation
Generic alarm delay time after the digital input is not activate
0
0
0
0
Alarm relay
Enable alarm relay with unit in off or stand – by:
0= Alarm output not enabled
1= Alarm output enabled
0
Password reset: Alarm log – Compressor overload
Password value to reset the alarm log or the compressor overload alarm.
0
0
0
0
0
250 Sec
250 Sec
16
1
150
302
25.0
45
°C
°F
°C
°F
16
16
Dec / int int
Dec int
250
250
Sec
10 sec
10 sec
1
999
Page 50 of 52
AL 52
AL 53
AL 54
AL 60
AL 61
AL 62
AL 63
AL 64
AL 65
AL 66
AL 67
AL 68
AL 69
AL 70
AL 71
AL 72
AL 55
AL 56
AL 57
AL 58
AL 59
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
AL 47
AL 48
AL 49
AL 50
AL 51
Thermal alarm of the compressor
0= lock the compressor
1= lock the whole circuit
Thermal alarm when the compressor is OFF
0 = Not enabled
1= Alarm enabled
Oil alarm in OFF
Oil alarm when the compressor is OFF
0 = Not enabled
1= Alarm enabled
Generic alarm / signal 2
Functioning generic alarm n° 2
0= only signal always automatic reset
1= the alarm block the unit reset depends on the value of parameter AL51
Maximum number of generic alarm events before turning the alarm from automatic to manual:
Always manual AL51 = 0
Always automatic AL51 =16
From manual to utomatic if AL51 value is between 1 and 15
Generic alarm delay time after the digital input activation
Generic alarm delay time after the digital input is not activate
Reset High pressure / temperature alarm
Maximum number of high pressure / temperature alarm events before turning the alarm from automatic to manual:
Always manual AL54 = 0
Always automatic AL54 =16
From manual to utomatic if AL54 value is between 1 and 15
Flow alarm condenser
“Flow switch water condenser alarm delay after pump activation.
Maximum time flow switch alarm active befor to block the water pump
Minimum “Flow switch water condenser active time duration.
Minimum “Flow switch water condenser not active time duration.
High water evaporator inlet temperature
Maximum number of high water temperature alarm events
Always manual reset if AL59 = 0
Always automatic reset if AL59 =16
From automatic to manual reset if AL59 =1..15
High water temperature alarm delay time from ON compressor
Set point higt water temperature
0
0
0
Differential higt water temperature
Analogue input configuration.Allows to select which probe value
NTC/PTC (Pb1..Pb10)
Low pressure alarm delay
Sanitary water flow switch alarm delay
San. water flow switch delay to stop pump
Sanitary water flow switch activation time
San. water flow switch de-activation time
Solar panel flow switch alarm delay
Solar panel flow switch delay to stop pump
Solar panel flow switch activation time
Solar panel flow switch de-activation time
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
-30.0
-22
0.1
0
1
0
0
0
0
16
1
1
1
1
16
250
250
16
250
70.0
158
25.0
45
10
250
250
250
250
250
250
250
250
250
250
250
250
250
Sec
Sec
Sec
°C
°F
°C
°F
Sec
Sec
Sec
Sec
Sec
Sec
Sec
Sec
Sec
Sec
Sec
Sec
Sec
10 sec
Dec int
Dec int
Page 51 of 52
1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)
10. Technical Data
Ichill 290D / Ichill 291D
Housing:
self extinguishing ABS
Case:
10 DIN
Mounting:
10 DIN rail
Index of protection:
IP20 IC290D / 291D; IP40 keyboard VGI890
Keyboard frontal protection:
IP65 with gasket
Power supply:
12Vac/dc,-10%÷+15% or
24 Vac/dc±10%. 50/60 Hz
Power absorption:
10VA max
Probes:
6 temperature probes (NTC/PTC) + 4 temperature or pressure probes (NTC/PTC/4 ÷ 20ma /
0 ÷ 5Volt)
Digital inputs:
18 (free voltage)
Relay outputs:
10 (IC260D/L) or 14 (IC261D/L): SPDT 5(2) A, 250Vac.
Data storing:
on the non-volatile memory (EEPROM)
Operating temperature:
-10÷55 °C
Storage temperature:
-30÷85 °C
Relative humidity:
20 ÷ 85% (no condensing)
Measuring range:
Temperature measured by NTC probe: - 50÷110 °C (-58 ÷ 230 °F)
Temperature measured by PTC probe: -50÷150 °C (-58÷302 °F )
Pressure: 0÷ 50 bar (0÷725 psi)
Resolution:
0,1 °C or 1 °F (selectable)
Accuracy of the controller at 25°C:
±0,7 °C ±1 digit
Page 52 of 52
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement