Quick reference guide IChill 290D/291D (Firmware rel. 1.8)


Add to my manuals
52 Pages

advertisement

Quick reference guide IChill 290D/291D (Firmware rel. 1.8) | Manualzz

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Quick reference guide

IChill 290D/291D

(Firmware rel. 1.8)

Page 1 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

Index

General Advice ______________________2

General Features ____________________3

IC290D/291D Table of the

Features _____________________________4

User Interface

________________________5

Table Of The Output Status In

Alarm Condition ____________________16

Wiring Connections

_________________19

Electrical Connections ______________21

Probe and relay configuration

______22

Table Of The Parameters ____________26

Technical Data ______________________52

1. General Advice

1.1 Please Read Before Using This

Manual

This manual is part of the product and should be kept near the instrument for easy and quick reference.

The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device.

Check the application limits before proceeding.

1.2 Safety Precautions

Check the supply voltage is correct before connecting the instrument.

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation

Warning: disconnect all electrical connections before any kind of maintenance.

The instrument must not be opened.

 In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” with a detailed description of the fault.

Consider the maximum current which can be applied to each relay (seeTechnical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining.

Fit the probe where it is not accessible by the end user.

 In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful.

Full Manual

Dixell S.r.l. reserve to itself the right to modify this instruction manual without any warning.

Last available can be downloaded from he internet site.

[email protected]

Page 2 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

2. General Features

iCHILL IC290D/291D

is an electronic controller for chiller unit applications having one or two circuits:

Air/air

Air/water

Water/water

Motocondensing

Additional features :

 Heat pump with gas reversibility

2.1

Main Function

Chiller management:

One circuit up to 4 compressors

Two circuits with different compressor number per circuit

Double circuit up to 6 compressors 

 Screw compressors

Compressor start up:

Direct

Part winding

 Star - delta

Compressor Soft start:

With step valve

Automatic start-unloading (without load).

 External by-pass gas valve.

Capacity step control:

Continuous control

Step control

 Modulation control (screw compressors)

Thermoregulation of the compressors

Time running hours

Number of start-up per hour

Cooling liquid injection

 With dedicated PTC probe

High temperature alarm of the compressor discharge side

 With dedicated PTC probe

Complete management of two pump groups of the water side

2 pumps evaporator side

2 pumps condenser side

Other display readings

Safety digital inputs

Compressors running hours

Number of compressor start-up

Pump running hours

Delay counting to the next defrost

Proportional output percentage status

 Compressors discharge temperature

Alarm reset with custom password

Alarm list

Compressor thermal protection alarm

Single circuit stand-by

Circuit maintenance

To work with only one circuit

Single compressor stand-by

Compressor maintenance

Compressor malfunction

Pump down management

With dedicated pressure switch

Low pressure switch

 Low pressure transducer

Unloading circuit

High temperature of the evaporator inlet water

High temperature of the condenser inlet water (unit with recovery)

High condensing pressure

Low evaporating pressure

Maintenance messages

 Condenser pumps

Auxiliary relays

Compressors

Evaporator pumps or pressure probes.

Weekly Energy saving

Two configurable relay outputs not depending from the control algorithm can be managed through NTC, PTC

 From digital input

Weekly ON/OFF:

Three different time bands per day (only with RTC onboard)

Three different time bands per day (only with RTC onboard)

Dynamic setpoint:

 Determined by analogue NTC input or 4÷20mA current input.

Change over :

 Automatic chiller or heat pump functioning depending from NTC analogue input.

Remote OFF:

 From configurable digital input.

Remote change over:

 From configurable digital input.

Hot start :

 Air / air unit

Defrost management:

Boiler:

Combined control with temperature and pressure

Forced defrost with low temperature of external air

From configurable digital input

Manual from keyboard

For electrical integration heating or anti-freeze heaters

Two proportional outputs for condensing fan speed control (inverter or phase cut) with configurable signal:

PWM

0÷10Volt

4÷20mA

Four proportional control outputs 0÷10V or ON/OFF

Complete alarm management

Supervisor / monitoring

To control the dumper in free cooling or recovery

To control an external relay

Internal Data logger up to 100 events

TTL output for XJ485 interface (Mod #Bus protocol) for

XWEB300 / XWEB3000 Dixell monitoring system for local and remote control

Page 3 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

3. IC290D/291D Table of the Features

FEATURES

OUTPUT RELAYS

10

14

DIGITAL INPUTS

18

PROBE INPUTS

10

PROPORTIONAL OUTPUTS

2 PWM outputs for condensing fan

2 0÷10V or 4÷20mA for condensing fan

4 0÷10V

OTHER OUTPUTS

TTL

Output for remote keyboard VGI890

POWER SUPPLY

12 Vac/dc (+15%;-10%)

24 Vac/dc (± 10%)

OTHERS

Internal RTC

Buzzer

 configurable = configurable through parameter opt = optional

= default

IC290D

configurable configurable

configurable configurable

opt opt opt

IC291D

configurable configurable

configurable configurable

opt opt opt

Page 4 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

4. User Interface

In the main visualization it is possible to read:

 status of the unit: cooling, heating, remote OFF or STD-BY

 date and time, available if the Ichill is provided by internal clock

 4 probes value; it is possible to manage 4 lines to visualize the probe temperature / pressure

(parameters dP06..dP09)

 load / function status as showed below:

/

Compressor/s

(blinking during the start up delay)

Water pump / Supply fan

Economy function

Unloading function

Condenser fan

Electric heater

Economy or ON/OFF by timetable

Defrost

Sanitary water Alarm

Meaning of the keys:

Allows to read the value of the probes configured in the Ichill

Allows to switch on the

Ichill in heating or cooling mode (see parameter

CF78)

Allows to switch on the

Ichill in heating or cooling mode (see parameter

CF78)

Allows to read/modify the set point

Allows to read the alarms

Allows to enter the

SERVICE menù

Page 5 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Allows to put the Ichill in

STD-BY

Allows to read the main information of the circuits

(compressor status, water pump status, pressure probe value,…)

Note: in case of alarm, press any key to silence the buzzer

4.1 Keyboard configuration

Keyboard configuration

It is possible to set: o contrast and backlight (it is strongly recommended to reduce as possible the activation time of the backlight) o language selection o read information about: o Ichill firmware release (to verify the compatibility Ichill



Visograph keyboard) o Visograph keyboard firmware release o Visograph keyboard bin release

How to modify the configuration: o press o press or o press o press or to confirm to select the configuration to change to change the configuration

Page 6 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

4.2

Chiller / Heat pump selection

If the Ichill is in STD-BY press

Meaning of the simbols:

CF78 = 0:

pushing

CF78 = 1:

pushing o to switch on the machine.

key the unit starts in chiller, pushing key the unit starts in heat pump, pushing key the unit starts in heat pump key the unit starts in chiller

Page 7 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

When the Ichill is ON, press to put the machine in STD-BY.

4.3 Visualization / modification of the set point configuration

Visualization / modification of the set point

Press key to read the value of the set point (cooling set point if the Ichill is in cooling mode, heating set point if the Ichill is in heating mode, cooling and hating set point if the Ichill is in STD_BY or remote OFF, Sanitary water when enabled).

It is also possible to read the status of the Energy saving, the status of the Dynamic set point and the real value of the set point if the Energy saving or Dinamic set point are active.

To modify the set point (Cooling, Heating or Sanitary water):

 press or to select the value of the set point

 press

 press o to modify the value

Page 8 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

 press to confirm the operation

4.4 Alarm visualization and reset

Alarm visualization and reset

Press key to read the alarm status; the alarm status can be: o

Active

: the alarm is still active and it is not possible to reset it o

Reset

: the alarm is not active and it is possible to reset it

Manual reset procedure: o press o press or to select the alarm; to reset the alarm

In case of compressor overload alarm when the password is requested, follow this step: o press o press o press o to select the compressor overload alarm o press o press or to insert the password value (parameter AL46) to confirm the operation

Page 9 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

4.5 Menu SERVICE

Menu SERVICE

Pressing it is possible to read the following information:

Parameter programming

Programming clock

Energy saving and ON/OFF scheduling

Compressor maintenance

It is possible to disable the compressor for maintenance, read the working hours and number of start up (and reset them)

Water pump maintenance

It is possible to read / reset the working hours

Circuit maintenance

Visualization and reset of the alarms

Visualization and reset of the alarm log

Defrost status

Electrical heater and pump down valve status

I/O status

Screw compressor information

It is possible to read the discharge temperature, the liquid injection valve status and the minimum load valve status

Auxiliary output status

Upload and download parameter map with Hot Key

Sanitary water status, sanitary water temperature, antilegionella status, etc.

Visograph configuration

It is possible to read the Ichill firmware version (for the compatibility with the keyboard), the keyboard firmware release and keyboard bin release.

It is possible to change the language, to set the contrast and the backlight

.

Page 10 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

4.6 Parameters programming

Parameters programming

Pressing it is possible to read/modify the parameters value:

 select the level 1 (default) or level 2 or level (by pressing Pr2 or Pr3 key)

 press

 press or to enter the password

 press to confirm

 the display shows “Password OK!” (otherwise repeat the procedure)

 press to visualize the parameters

Page 11 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Pressing press .

or it is possible to select the group of parameters to modify, then

How to modify the value of the parameter:

 press

 press or to select the parameter to modify

 press or to modify the value

Page 12 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

 press to confirm

Press or to scroll the parameters.

4.7 Clock programming and Energy saving / ON_OFF scheduling visualization

Clock programming and Energy saving / ON_OFF scheduling visualization

It is possible to set the clock and read the Energy saving and the ON/OFF scheduler.

How to set the clock: o press date); o press o press o press or or to confirm to select the date to modify (hour, minutes, to modify the value

Page 13 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Pressing or and ON/OFF scheduling.

it is possible to read the information about the Energy saving

To modify the hour of the time band and to enable the function is necessary to enter the parameter programming (ES parameters).

4.8 Parameters programming with Hot Key 64

Parameters programming with Hot Key 64

It is possible to use the HotKey 64 for:

 copy the parameter map from the HotKey 64 to the Ichill (Download)

 copy the parameter map from the Ichill to HotKey 64 (Upload)

Download from HotKey 64 to Ichill:

this operation is enabled only if the Ichill is in STD-BY or remote OFF, otherwise the display shows the message “Download enabled only in stand-by”.

Download procedure:

 Insert the Hot Key 64 into the 5 ways connector through the hole at the top of the Ichill (see image below)

 Select “Download from HotKey to device”

 Press ENTER

 if the operation was successful the display shows “OK”, otherwise shows “ERR”

Upload from Ichill to Hot Key 64:

Upload procedure:

 Insert the Hot Key 64 into the 5 ways connector through the hole at the top of the Ichill (see image below)

 Select “Upload from device to HotKey”

 Press ENTER

 if the operation was successful the display shows “OK”, otherwise shows “ERR”

In case of Upload / Download failure:

 Hot Key 64 not properly inserted in the 5 ways connector

 Hot Key model different to Hot Key 64

Page 14 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Page 15 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

5. Table Of The Output Status In Alarm Condition

The alarm codes are made of letters and numbers to define the different typologies:.

5.1

Alarm

Code

ALARM

Alarm description

Compressor Anti freeze heaters

Boiler

Support heaters

Evapor ator

Pump /

Supply fan

Condenser fan

Cir1 / Cir2

Auxiliary relay

AP1

AP10

ALti

Probe

PB1..Pb10

alarm

Low air temperature of the evaporator inlet (air / air unit) Alarm

AEFL

Evaporator flow alarm

Yes (6)

Yes (1)

Yes

ACFL

AHFL

APFL

AtSF

AEUn

AtE1

Condenser flow alarm

Sanitary water flow switch alarm

Solar panel flow switch alarm

Supply fan overload alarm

Unloading signalling from evaporator

Evaporator 1 water pump

Yes

Yes

Yes

(6)

Yes

(6)

Yes

Yes

(4)

Yes (boiler)

Yes (boiler)

(5)

Yes

Yes evapor ator water pump

(3)

Yes conden ser water pump

(3)

Yes sanitary water pump

(3)

Yes solar panel water pump

(3)

Yes supplay fan

Yes evapor

Yes

Yes

Yes

Yes

Yes

Page 16 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1) overload alarm

AtE2

Evaporator 2 water pump overload alarm

AtC1

Condenser 1 water pump overload alarm

Yes

(4)

Yes

(4)

Yes (boiler)

(5)

AtC2

Condenser 2 water pump overload alarm

AEP1

AEP2

ACP1

ACP2

Evaporator 1 water pump maintenance

Evaporator 2 water pump maintenance support

Condenser 1 water pump maintenance

Condenser 2 water pump maintenance

ASAn

ASUn

Sanitary water pump maintenance

Solar water panel pump maintenance

ArtC

Clock alarm

Remote

Atr1

keyboard n° 1 alarm

Remote keyboard n° 2

Atr2

alarm

ArtF

Clock failure

ALOC

Generic alarm

AEE

Eeprom alarm

ACF1

ACF1

2

Configuration alarm

ArtF

Faulty clock

ArtC

Clock error

Yes

(4)

Yes

Yes

Yes ator water pump 1

Yes evapor ator water pump 2

Yes conden ser water pump 1

Yes conden ser water pump 2

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Page 17 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

(1)

(2)

(3)

(4)

(5)

(6)

AEUn

ALti

AEht

Unloading signalling from high temp of.

evaporator water

Low evaporator inlet temperature in air/air unit

High water temperature inlat evaporator

Yes

= if probe configured as anti-freeze / boiler control and Ar10 = 0

= if probe configured as auxiliary relay control

= manual alarm procedure

= compressors switched off when only 1 water pump is configured or both water pumps are in alarm

= Boiler heaters off with only 1 water pump configured or with 2 pumps but both in alarm from the corresponding digital inputs (in this case the boiler heaters are on only with thermoregulation anti-freeze setpoint as evaporator protection function)

= If the faulty probe is the regulation probe or circuit probe (condenser probe, suction probe)

5.2

ALARM: circuit alarm

Alarm

Code

Alarm description b(

n

)HP

High pressure switch of the circuit

(

n

) b(

n

)LP

Low pressure switch of the circuit

(

n

) b(

n

)AC

Anti-freeze in chiller of the circuit

(

n

) b(

n

)AH

Anti-freeze in heat pump of the circuit

(

n

) b(

n

)hP

High condensing pressure of the circuit

(

n

) b( b( b(

n

)lP b(

n n n

)hP

)LP

)PH

High condensing temperature from NTC of the circuit

(

n

)

Low condensing pressure - (evaporating with low pressure transducer) with transducer of the circuit of the

(

n

)

Low condensing temperature NTC circuit

(

n

) b(

n

)tF

Fan overload circuit

(

n

)

Pump down alarm in stop regulation of the circuit

(

n

) b(

n

)PL

Pump down in regulation start-up of the circuit

(

n

) b(

n

)dF

Bad defrost circuit

(

n

) b( b(

n n

)Cu

)Cu

Unloading from condenser high temp/press of the circuit

(

n

)

Unloading from evaporator low temp/press of the circuit

(

n

) b(

n

)rC

Recovery function disabled in circuit

(n) b(

n

)ds

Circuit

(n)

disabled from keyboard

b(

n

)Ac

Anti-freeze circuit

(n)

message in chiller

b(

n

)Ah

Anti-freeze circuit

(n)

message in heat pump

Compresso rs of the circuit

(

n

)

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Compressor s of the other circuit

Fan condensing of the circuit

(

n

)

Yes after 60 seconds

Yes

Yes

Yes

Yes after 60 seconds

Yes after 60 seconds

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Fan condensing of the other circuit

Page 18 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

(

n

)

identifies the circuit 1 or 2

5.3

ALARM: compressor alarm

Alarm Code

Alarm description

C(

n

)HP

C(

n

)oP

C(

n

)tr

C(

n

)dt

C(

n

)dS

C(

n

)Mn

Compressor(

n

) high pressure switch

Compressor(

n

) oil pressure switch / Oil level switch

Compressor(

n

) overload

Compressor high discharge temperature

Compressor (n) disabled from keyboard

Compressor(

n

) maintenane

(

n

)

identifies the compressor 1, 2 , 3 , 4 , 5 , 6

Compressor

(

n

)

Yes

Yes

Yes

Yes

Yes

6. Wiring Connections

Compressors not involved

6.1

Hardware Resources: IC290D / 291D

10 relays IC290D / 14relays IC291

(MAX current on the relay contacts 5(2)A 250V; MAX current in the common line of the relays 12A

250V)

18 digital inputs (free voltage)

10 analogue inputs: configurable ( 6 NTC or PTC, 4 NTC or pressure transducer 4÷20mA or ratiometric 0÷ 5.0 Volt)

2 PWM output (to manage the condenser fan)

6 0..10V output

1 output for remote keyboard (max 2 remote panels)

1 TTL output to connect an “Hot Key 64” (parametrs programming)

1 RS 485 output

Page 19 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

6.2

Ichill 290/291D dimensions

All the measures are expressed in mm.

6.3

Keyboard VGI690 panel cut out

Page 20 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

7. Electrical Connections

The instrument is provided with:

 3 removable terminal blocks MOLEX with 0.5 mm

2 wires: 16 / 8 /22 ways for digital / analogue inputs and modulating outputs.

 4 removable screw terminal block STELVIO for 2.5 mm

2 wires connection: 3 / 4 / 5 / 6 ways for the relay outputs.

 5 ways connector for TTL RS485 interface outputs.

 3 ways connector for keyboard VGI890 to be connected with the cable

CABC3J15

.

 The

LW30 KIT

is the complete kit with MOLEX + 3 mt wires already connected and the STELVIO terminals.

 Check the connecitons and the line voltage before turning on the power supply.

 Keep low voltage cables, such as analogue/digital inputs/outputs and probes, away from power cables and terminals.

Respect the maximum load current of each relay output, in case of power loads use filtered contactors.

Page 21 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

8. Probe and relay configuration

8.1

Analog input Pb1 - Pb2 - Pb7 -

Pb8 - Pb9 - Pb10

Parameters involved:

CF08 =

Configuration PB1

CF09 =

Configuration PB2

CF14 =

Configuration PB7

CF15 =

Configuration PB8

CF16 =

Configuration PB9

CF17 =

Configuration PB10

0.

Not enabled

1.

Temperature probe

PTC

for compressor

1 discharge

2.

Temperature probe

PTC

for compressor

2 discharge

3.

Temperature probe

PTC

for compressor

3 discharge

4.

Temperature probe

PTC

for compressor

4 discharge

5.

Temperature probe

PTC

for compressor

5 discharge

6.

Temperature probe

PTC

for compressor

6 discharge

7.

Temperature probe

NTC

for evaporator inlet

8.

Temperature probe

NTC

for evaporator

1 outlet

9.

Temperature probe

NTC

for evaporator

2 outlet

10. Temperature probe

NTC

for common evaporator outlet

11. Temperature probe

NTC

for common hot water condenser / recovery inlet

12. Temperature probe

NTC

for hot water of the condenser / recovery circuit 1 inlet

13. Temperature probe

NTC

for hot water of the condenser / recovery circuit 2 inlet

14. Temperature probe

NTC

for hot water of the condenser / recovery circuit 1 outlet

15. Temperature probe

NTC

for hot water of the condenser / recovery circuit 2 outlet

16. Temperature probe

NTC

for hot water of the condenser / recovery common outlet

17. Temperature probe

NTC

for free cooling water inlet circuit

18. Not Used

19. Temperature probe

NTC

for dynamic setpoint external air / boiler / change over

20. Temperature probe

NTC

for combined defrost circuit 1

21. Temperature probe

NTC

for combined defrost circuit 2

22. Temperature probe

NTC

for auxiliary output 1

23. Temperature probe

NTC

for auxiliary output 2

24. Temperature probe

NTC

sanitary water

1

25. Temperature probe

NTC

sanitary water

1

26. Temperature probe

NTC

solar panel

27. Temperature probe

NTC

for condensing circuit 1

28. Temperature probe

NTC

for condensing circuit 2

After the number 25 the display configuration can be selected from

o 1

to

c67

that allows to set an analogue input as digital input (see polarity of the digital input/outputs).

8.2

Analog input Configuration

Pb3 - Pb4 - Pb5 - Pb6

Parameter involved:

CF10 =

Configuration PB3

CF11 =

Configuration PB4

CF12 =

Configuration PB5

CF13 =

Configuration PB6

0

1

2

3

4

Not enabled

Temperature probe

PTC

for compressor

1 discharge

Temperature probe

PTC

for compressor

2 discharge

Temperature probe

PTC

for compressor

3 discharge

Temperature probe

PTC

for compressor

5

6

7

8

9

4 discharge

Temperature probe

PTC

for compressor

5 discharge

Temperature probe

PTC

for compressor

6 discharge

Temperature probe

NTC

for evaporator inlet

Temperature probe

NTC

for evaporator outlet 1

Temperature probe

NTC

for evaporator outlet 2

Page 22 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

10 Temperature probe

NTC

for common evaporator outlet

11 Temperature probe

NTC

for common hot water condenser / recovery inlet

12 Temperature probe

NTC

for hot water condenser / recovery inlet circuit 1

13 Temperature probe

NTC

for hot water condenser / recovery inlet circuit 2

14 Temperature probe

NTC

for hot water condenser / recovery outlet circuit 1

15 Temperature probe

NTC

for hot water condenser / recovery outlet circuit 2

16 Temperature probe

NTC

for hot water condenser / recovery common outlet circuit

17 Temperature probe

NTC

for free cooling water inlet

18 Not Used

19 Temperature probe

NTC

for external air dynamic setpoint/ boiler / change over

20 Temperature probe

NTC

for combined defrost circuit 1

21 Temperature probe

NTC

for free cooling water inlet 2

22 Temperature probe

NTC

for auxiliary output 1

23 Temperature probe

NTC

for auxiliary output 2

24 Temperature probe

NTC

sanitary water

1

25 Temperature probe

NTC

sanitary water

2

26 Temperature probe

NTC

solar panel

27 Condenser probe circuit 1 ( temperature

NTC

/ pressure

4÷20 mA

/ ratio-metric

0÷ 5Volt

)

28 Condenser probe circuit 2 ( temperature

NTC

/ pressure

4÷20 mA

/ ratio-metric

0÷ 5Volt

)

29 Evaporator pressure probe circuit 1

(pressure

4÷20 mA

/ ratio-metric

5Volt

)

30 Evaporator pressure probe circuit 1

(pressure

4÷20 mA

/ ratio-metric

5Volt

)

31 Auxiliary output 1 pressure probe control (

4÷20 mA

/ ratio-metric

5Volt)

32 Auxiliary output 2 pressure probe control (

4÷20 mA

/ ratio-metric

5Volt)

33 Dynamic setpoint pressure probe (

4÷20 mA)

After the number 30 the display read-out goes from “

o 1”

to “

c67

that allows to set an analogue input as digital input (see polarity input of digital inputs).

8.3

Digital Input Configuration Id1

– Id18

Parameters involved:

CF36 =

Configuration ID1…

CF53 =

Configuration ID18

0.

Not enabled

1.

Remote ON / OFF

2.

Remote chiller / heat pump

3.

Flow switch/ Supply fan overload

4.

Flow switch of heated side

5.

Antifreeze heater circuit 1

6.

Antifreeze heater circuit 2

7.

High pressure switch circuit 1

8.

High pressure switch circuit 2

9.

Low pressure switch circuit 1

10. Low pressure switch circuit 2

11. Compressor 1 high pressure

12. Compressor 2 high pressure

13. Compressor 3 high pressure

14. Compressor 4 high pressure

15. Compressor 5 high pressure

16. Compressor 6 high pressure

17. Compressor 1 overload

18. Compressor 2 overload

19. Compressor 3 overload

20. Compressor 4 overload

21. Compressor 5 overload

22. Compressor 6 overload

23. Condenser fan overload of circuit 1

24. Condenser fan overload of circuit 2

25. Condenser fan overload of circuit 1 and

2 (comun)

26. Water pump overload of evaporator 1

27. Water support pump overload of evaporator

28. Water pump overload of condenser 1

29. Water support pump overload of condenser

30. Not Used

31. Not Used

32. End defrost circuit 1

33. End defrost circuit 2

34. Energy Saving

35. Pressure switch / compressor 1 oil

36. Pressure switch / compressor 2 oil

37. Pressure switch / compressor 3 oil

Page 23 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

38. Pressure switch / compressor 4 oil

39. Pressure switch / compressor 5 oil

40. Pressure switch / compressor 6 oil

41. Pump down pressure switch of circuit 1

42. Pump down pressure switch of circuit 2

43. Generic alarm from digital input with stop regulation n° 1

44. Generic alarm from digital input with stop or signal regulation n° 2

45. Operation working mode: by RTC or keyboard

46. Operation mode with supplay fan only

47. Digital input of thermoregulation request

(condensing unit)

48. Digital input of cooling request

(condensing unit)

49. Digital input of heating request

(condensing unit)

50. Request step 2 (condensing unit)

51. Request step 3 (condensing unit)

52. Request step 4 (condensing unit)

53. Request step 5 (condensing unit)

54. Request step 6 (condensing unit)

55. Request step 7 (condensing unit)

56. Request step 8 (condensing unit)

57. Request step 9 (condensing unit)

58. Request step 10 (condensing unit)

59. Request step 11 (condensing unit)

60. Request step 12 (condensing unit)

61. Request step 13 (condensing unit)

62. Request step 14 (condensing unit)

63. Request step 15 (condensing unit)

64. Request step 16 (condensing unit)

65. Sanitary water flow switch

66. Solar panel flow switch

67. Only sanitary water

8.4

Digital Output

Configuration RL1- RL14

(relay)

Parameter involved:

CF54=

Configuration

Configuration RL14

RL1…

CF67=

0.

Not enabled

1.

Alarm

2.

Evaporator water pump / Supply fan

3.

Support water pump of the evaporator

4.

Anti-freeze heater / integration heating / boiler circuit 1

5.

Anti-freeze heater / integration heating / boiler circuit 2

6.

Water pump of the condenser recovery circuit

7.

Support water pump of the condenser recovery circuit

8.

4-way valve for chiller / heat pump inversion of the circuit 1

9.

4-way valve for chiller / heat pump inversion of the circuit 2

10. 1° condenser fan step ON/OFF control of the circuit 1

11. 2° condenser fan step ON/OFF control of the circuit 1

12. 3° condenser fan step ON/OFF control of the circuit 1

13. 4° condenser fan step ON/OFF control of the circuit 1

14. 1° condenser fan step ON/OFF control of the circuit 2

15. 2° condenser fan step ON/OFF control of the circuit 2

16. 3° condenser fan step ON/OFF control of the circuit 2

17. 4° condenser fan step ON/OFF control of the circuit 2

18. Solenoid valve of the pump-down circuit

1

19. Solenoid valve of the pump-down circuit

2

20. Recovery valve circuit 1

21. Recovery valve circuit 2

22. Free cooling ON/OFF valve

23. Auxiliary output circuit 1

24. Auxiliary output circuit 2

25. Solenoid valve Intermittent for screw compressor 1

26. Solenoid valve Intermittent for screw compressor 2

27. Solenoid valve of the liquid injection for compressor 1

28. Solenoid valve of the liquid injection for compressor 2

29. Sanitary valve 1

30. Sanitary valve 2

31. Sanitary heater 1

32. Sanitary heater 2

33. Sanitary heater 3

34. Solar panel water pump

35. Solar panel valve

36. Sanitary water pump

37. Hybrid exchanger 1

38. Hybrid exchanger 2

39. Direct start-up : compressor 1 relay

PW start: relay PW 1 of the compressor

1

Page 24 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Star-delta start: relay line 1 of the compressor 1

40. PW start: relay PW 2 of the compressor

1

Star-delta start: relay linea 2 compressor

1

41. Star centre of the Star-delta start of the compressor 1

42. Capacity step valve 1 compressor 1

43. Capacity step valve 2 compressor 1

44. Capacity step valve 3 compressor 1

45. By-pass gas valve compressor 1start

46. Direct start: compressor 2 start

PW start: relay 1 of the compressor 2

Star-delta start: relay line 1 of the compressor 2

47. PW start: relay PW 2 of the compressor

2

Star-delta start: relay line 2 of the compressor 2

48. Star centre of the Star-delta start of the compressor 2

49. Capacity step valve 1 compressor 2

50. Capacity step valve 2 compressor 2

51. Capacity step valve 3 compressor 2

52. By-pass gas valve compressor 2 start

53. Direct start: compressor 3 relay

PW start: relay PW 1 of the compressor

3

Star-delta start: relay line 1 of the compressor 3

54. PW start: relay PW 2 of the compressor

3

Star-delta start: relay line 1 of the compressor 3

55. Star centre of the Star-delta start of the compressor 3

56. Capacity step valve 1 compressor 3

57. Capacity step valve 2 compressor 3

58. Capacity step valve 3 compressor 3

59. By-pass gas valve compressor 3 start

60. Direct start: compressor 4 relay

PW start: PW 1 of the compressor 4

Star-delta start: relay line 1 of the compressor 4

61. PW start: relay PW 2 of the compressor

4

Star-delta start: relay line 1 of the compressor 4

62. Star centre of the Star-delta start of the compressor 4

63. Capacity step valve 1 of the compressor

4

64. Capacity step valve 2 of the compressor

4

65. Capacity step valve 3 of the compressor

4

66. By-pass gas valve compressor 4 start

67. Compressor 5 relay

68. Compressor 6 relay

8.5

Condenser control outputs) proportional configuration (2

Proportional outputs used to configure a proportional output signal to condenser fan control

Parameters involved:

CF68 =

Condenser control configuration for circuit 1

CF69 =

Condenser control configuration for circuit 2

0= 0 ÷ 10Vdc (for external mono or threephase fan control board)

1= 4÷20mA (for external mono or three-phase fan control board)

2= PWM (only for external mono-phase fan control board with cut phase control)

8.6

Proportional output configuration 0 ÷ 10 Vdc (4 outputs)

Parameters involved:

CF70 =

Proportional output 1 configuration

CF71 =

Proportional output 2 configuration

CF72 =

Proportional output 3 configuration

CF73 =

Proportional output 4 configuration

0 Not enabled

1 not used

2 not used

3 not used

4 Auxiliary output 0÷10V n° 1

5 Auxiliary output 0÷10V n° 2

6 Proportional output for modulating compressor 1

7 Proportional output for modulating compressor 2

After the read-out number 4 the display goes from the label “

o 1”

to “

c38

(see input/output polarity), that allow to configure the output as digital output to control an external relay.

Page 25 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

9. Table Of The Parameters

ST 3

ST 4

ST 5

ST 6

ST 7

ST 8

ST 9

MENU SELECTION

Label

Description

ALL

Shows all the parameters

ST

Shows only the Thermoregulation parameters

CF

Shows only the Configuration parameters

SD

Shows only the Dynamic Setpoint parameters

ES

Shows only the Energy Saving, RTC parameters

Cr

Shows only the compressor rack parameters

CO

Shows only the compressor parameters

US

Shows only the Auxiliary Output parameters

FA

Shows only the Fan Control parameters

Ar

Shows only the Antifreeze Control parameters

DF

Shows only the Defrost parameters

FS

Shows only the Sanitary Water parameters

AL

Shows only the Alarm parameters

Thermoregulation

Parameter Description

ST 1

ST 2

Chiller Setpoint

Chiller minimum Setpoint

Chiller maximum Setpoint

Heat pump setpoint

Heat pump minimum Setpoint

Heat pump maximum Setpoint

Regulation band in chiller mode

Regulation band in chiller heat pump

Thermoregulation probe selection in chiller

0= Temperature probe NTC for evaporator inlet

1= Temperature probe NTC for evaporator outlet 1

2= Temperature probe NTC for evaporator outlet 2

3= Temperature probe NTC for common evaporator outlet

4= Temperature NTC probe from remote panel 1

5= Temperature NTC probe from remote panel 2 min max u.m.

Resolution

ST02 ST03 °C/°F dec/int

-30.0

-22

ST01

-30.0

-22

ST04

0.0

0

0.0

0

ST01

70.0

158

ST04

70.0

158

25.0

45

25.0

45

°C

°F

°C

°F

ST05 ST06 °C/°F

°C

°F

°C

°F

°C

°F

°C

°F dec/int dec/int dec/int

Dec int

Dec int

Dec int

Dec int

0 5

Page 26 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

ST 10

ST 11

Pr1

Pr2

Pr3

CF 1

Thermoregulation probe selection in heat pump

0= Temperature probe NTC for evaporator inlet

1= Temperature probe NTC for evaporator outlet 1

2= Temperature probe NTC for evaporator outlet 2

3= Temperature probe NTC for common evaporator outlet

4= Temperature NTC probe from remote panel 1

5= Temperature NTC probe from remote panel 2

6= Temperature probe for water common inlet of the condenser

7= Temperature probe for water inlet of the circuit # 1 condenser

8= Temperature probe for water inlet of the circuit # 2 condenser

9= Temperature probe for water outlet of the circuit # 1 condenser

10= Temperature probe for water outlet of the circuit # 2 condenser

11= Temperature probe for water common otlet of the condenser

ATTENTION

To have the same thermoregulation for chiller and heat pump mode, set the parameters ST09 and ST10 with the same value

Type of thermoregulation

0= Proportional

1= Neutral zone

Password

Password

Password

Display read-out

Parameter Description

dP 1 dP 2 dP 3 dP4 dP5 dP6 dP7 dP8 dP9

Not used

Not used

Not used

Not used

Not used

Display read-out of the VGI890

First probe displayed on Visograph

Second probe displayed on Visograph

Third probe displayed on Visograph

Fourth probe displayed on Visograph

Configuration

Parameter Description

Unit Model

CF 2

CF 3

Type of unit

0= Air / air Chiller

1= Air / water Chiller

2= Water / water Chiller

Selection type rof unit

1= only chiller

2= only heat pump

3= chiller and heat pump

4= heat pump and free cooling

5= chiller, heat pump and free cooling

Condensing unit

0= no

1= si

Compressors

CF 4

Compressors number for circuit 1

1= 1

2= 2

3= 3

4= 4

0

0 min min

0

1

0

0

0

0

0

0

0

0

0

11

1

999

999

999 max M. u. Resolution

33

33

33

33 max M. u. Resolution

2

5

1

4

Page 27 of 52

CF 8

CF 9

CF 10

CF 11

CF 12

CF 13

CF 14

CF 15

CF 16

CF 17

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

CF 5

CF 6

CF 7

CF 18

CF 19

CF 20

Compressors number for circuit 2

0= 0

1= 1

2= 2

3= 3

Number of compressor parzialization

0= none

1= 1

2= 2

3= 3

Analog Inputs

Pressure or temperature analogue input functioning

0 = Temperature / pressure NTC – 4÷20 mA :

The condensing temperature is controlled with NTC probe while for the evaporating pressures of the circuits 1 and 2 and the pressure probe configured as auxiliary output 1 and 2 are controlled with 4÷20mA transducers.

1 = Pressure control with 4÷20 mA:

To control the evaporating and condensing pressures it is necessary a 4÷20mA transducer.

2 = Temperature / pressure NTC – 0÷5Vdc:

The condensing temperature is controlled with NTC probe while for the evaporating pressures of the circuits 1 and 2 and the pressure probe configured as auxiliary output 1 and 2 are controlled with 0÷5Vdc transducers.

3 = Pressure control with 0÷5Vdc:

To control the evaporating and condensing pressures it is necessary a ratiometric 0÷5Vdc transducer.

PB1 Configuration

If configured as digital input

PB2 Configuration

If configured as digital input

PB3 Configuration

If configured as digital input

PB4 Configuration

If configured as digital input

PB5 Configuration

If configured as digital input

PB6 Configuration

If configured as digital input

PB7 Configuration

If configured as digital input

PB8 Configuration

If configured as digital input

PB9 Configuration

If configured as digital input

PB10 Configuration

If configured as digital input

Probe Offset

PB1 Offset

PB2 Offset

PB3 Offset

0

0

0

-12.0

-21

-12.0

-21

-12.0

-21

-5.0

-72

0 o 1

0 o 1

0 o 1

0 o 1

0 o 1

0 o 1

0 o 1

0 o 1

0 o 1

0 o 1

3

3

3

33 c67

33 c67

28 c67

28 c67

28 c67

28 c67

33 c67

33 c67

28 c67

28 c67

12.0

21

12.0

21

12.0

21

5.0

72

°C

°F bar psi

°C

°F

°C

°F

Dec int

Dec int

Dec int dec int

Page 28 of 52

CF 23

CF 44

CF 45

CF 46

CF 47

CF 48

CF 49

CF 50

CF 51

CF 52

CF 53

CF 36

CF 37

CF 38

CF 39

CF 40

CF 41

CF 42

CF 43

CF 54

CF 24

CF 25

CF 26

CF 27

CF 28

CF 29

CF 30

CF 31

CF 32

CF 33

CF 34

CF 35

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

CF 21

PB4 Offset

CF 22

PB5 Offset

PB6 Offset

PB7 Offset

PB8 Offset

PB9 Offset

PB10 Offset

Pressure value at 4mA or 0.5 Vdc of the PB3 transducer

Pressure value at 20mA or 5 Vdc of the PB3 transducer

Pressure value at 4mA or 0.5 Vdc of the PB4 transducer

Pressure value at 20mA or 5 Vdc of the PB4 transducer

Pressure value at 4mA or 0.5 Vdc of the PB5 transducer

Pressure value at 20mA or 5 Vdc of the PB5 transducer

Pressure value at 4mA or 0.5 Vdc of the PB6 transducer

Pressure value at 20mA or 5 Vdc of the PB6 transducer

Digital Inputs

Configuration of ID1

Configuration of ID2

Configuration of ID3

Configuration of ID4

Configuration of ID5

Configuration of ID6

Configuration of ID7

Configuration of ID8

Configuration of ID9

Configuration of ID10

Configuration of ID11

Configuration of ID12

Configuration of ID13

Configuration of ID14

Configuration of ID15

Configuration of ID16

Configuration of ID17

Configuration of ID18

Relay Outputs

Configuration of RL1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

-12.0

-21

-12.0

-21

-12.0

-21

-5.0

-72

-12.0

-21

-12.0

-21

-12.0

-21

-5.0

-72

-12.0

-21

-5.0

-72

0 -o1 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67 c67

50.0

725

50.0

725

50.0

725

50.0

725

12.0

21

12.0

21

50.0

725

50.0

725

50.0

725

50.0

725

12.0

21

5.0

72

12.0

21

12.0

21

12.0

21

5.0

72

12.0

21

5.0

72 c68

Bar psi

Bar psi

Bar psi

Bar psi

Bar psi

Bar psi

°C

°F

°C

°F

Bar psi

Bar psi

°C

°F

°C

°F

°C

°F bar psi

°C

°F bar psi

°C

°F bar psi

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int dec int

Dec int

Dec int

Dec int dec int

Dec int dec int

Page 29 of 52

CF 55

CF 56

CF 57

CF 58

CF 59

CF 60

CF 61

CF 62

CF 63

CF 64

CF 65

CF 66

CF 67

CF 68

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

CF 69

CF 70

CF 71

CF 72

Configuration of RL2

Configuration of RL3

Configuration of RL4

Configuration of RL5

Configuration of RL6

Configuration of RL7

Configuration of RL8

Configuration of RL9

Configuration of RL10

Configuration of RL11

Configuration of RL12

Configuration of RL13

Configuration of RL14

Condensing proportional outputs

Circuit 1 output signal:

0= 0 – 10Vdc

1= 4 ÷ 20mA

2= PWM for mono phase fan control board

Circuit 2 output signal:

0= 0 – 10V

1= 4 ÷ 20Ma

2= PWM for mono phase fan control board

Proportional output

Proportional output “out 3”

0= Not enabled

1= Not used

2= Not used

3= Not used

4= Auxiliary output 0÷10V n° 1

5= Auxiliary output 0÷10V n° 2

6= Proportional output for inverter circuit 1 compressor n° 2

7= Proportional output for inverter circuit 2 compressor n° 2

Relay driver ON / OFF

Proportional output “out 4”

0= Not enabled

1= Not used

2= Not used

3= Not used

4= Auxiliary output 0÷10V n° 1

5= Auxiliary output 0÷10V n° 2

6= Proportional output for inverter circuit 1 compressor n° 2

7= Proportional output for inverter circuit 2 compressor n° 2

Relay driver ON / OFF

Proportional output “out 5”

0= Not enabled

1= Not used

2= Not used

3= Not used

4= Auxiliary output 0÷10V n° 1

5= Auxiliary output 0÷10V n° 2

6= Proportional output for inverter circuit 1 compressor n° 2

7= Proportional output for inverter circuit 2 compressor n° 2

Relay driver ON / OFF

0 -o1

0 -o1

0 -o1

0 -o1

0 -o1

0 -o1

0 -o1

0 -o1

0 -o1

0 -o1

0 -o1

0 -o1

0 -o1 c68 c68 c68 c68 c68 c68 c68 c68 c68 c68 c68 c68 c68

0 2

0 2

0 7 o 1 C38

0 7 o 1 C38

0 7 o 1 C38

Page 30 of 52

CF 84

CF 85

CF 86

CF 87

CF 88

CF 89

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

CF 73

CF 74

CF 75

CF 76

CF 77

CF 78

CF 79

CF 80

CF 81

CF 82

CF 83

Proportional output “out 6”

0= Not enabled

1= Not used

2= Not used

3= Not used

4= Auxiliary output 0÷10V n° 1

5= Auxiliary output 0÷10V n° 2

6= Proportional output for inverter circuit 1 compressor n° 2

7= Proportional output for inverter circuit 2 compressor n° 2

Relay driver ON / OFF

Remote keyboard

Remote keyboard 1 configuration

0= Not enabled

1= Enabled model with ambient temperature sensor

2= Enabled model without ambient temperature sensor

Remote Panel 2 configuration

0= Not enabled

1= Enabled model with ambient temperature sensor

2= Enabled model without ambient temperature sensor

Offset of the probe of the remote terminal 1

0 o 1

0

0

Offset of the probe of the remote terminal 2

-12.0

-21

-12.0

-21

Icon function

Icon function

0= chiller / heat pump 0

1= chiller / heat pump

Chiller / heat pump selection mode

0= Chiller / Heat pump selection by keyboard

1= Chiller / Heat pump selection by digital input

2= Chiller / Heat pump selection by analogue input

Automatic Change over

Automatic change over setpoint for chiller/ heat pump selection

(CF79 = 2)

Automatic change over differential (CF79 = 2)

0

-30.0

-22

0

0

Unit of measurement

°C or °F selection

0= °C / °BAR

1= °F / °psi

Supply voltage frequency

Power supply frequency

0= 50 Hz

1= 60 Hz

2= cc voltage

(ATTENTION

When CF83 = 2 the proportional outputs for fan control are not enabled and the frequency alarm is inhibited)

Serial Address

0

0

Serial address

Firmware Release

1

Eeprom parameter map

Regulation of unbalanced compressors (different power)

Compressor 1 capacity

Compressor 2 capacity

Compressor 3 capacity

0

0

0

7

C38

2

2

12.0

21

12.0

21

1

2

70.0

158

25.0

45

1

2

247

100%

100%

100%

°C

°F

°C

°F

°C

°F

°C

°F

Dec int

Dec int

Dec int

Dec int

Page 31 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Sd 15

Sd 16

Sd 17

Sd 18

Sd 19

Sd 20

Sd 21

Sd 10

Sd 11

Sd 12

Sd 13

Sd 14

Sd 5

Sd 6

Sd 7

Sd 8

Sd 9

CF 90

CF 91

CF 92

CF 93

CF 94

CF 95

Compressor 4 capacity

Compressor 5 capacity

Compressor 6 capacity

Maximum number of start up of the compressor in 15 minutes

0= Not enabled

Working mode of the compressor

Working mode of the compressor

0 = chiller and heat pump

1 = only chiller

2 = only heat pump

Hybrid exchangers

Enable hybrid exchangers

Dynamic Setpoint

Parameters Description

Sd 1

Maximum dynamic Offset in chiller mode

Sd 2

Sd 3

Maximum dynamic Offset in heat pump mode

External air setpoint in chiller mode

Sd 4

External air setpoint in heat pump mode

External air differential in chiller mode

External air differential in heat pump mode

Dynamic set point: summer offset analog 1

Dynamic set point: winter offset analog 1

Summer outside temperature analog 1

Winter outside temperature analog 1

Summer outside temp. differential analog 1

Winter outside temp. differential analog 1

Dynamic set point: summer offset analog 2

Dynamic set point: winter offset analog 2

Summer outside temperature analog 2

Winter outside temperature analog 2

Summer outside temp. differential analog 2

Winter outside temp. differential analog 2

Dynamic set point: summer offset relay AUX1

Dynamic set point: winter offset relay AUX1

Summer outside temperature relay AUX1

0

0

0

0

100%

100%

100%

15

0 2

0 1

54

30.0

54

30.0

54

70.0

158

70.0

54

70.0

158

70.0

158

30.0

54

30.0

158

30.0

54

30.0

54

30.0

54

30.0

max

30.0

54

30.0

54

70.0

158

70.0

158

30.0

54

30.0

54

30.0

54

30.0

54

70.0

158

-54

-30.0

-54

-30.0

-54

-30

-22

-30

-54

-30

-22

-30

-22

-30.0

-54

-30.0

-22

-30.0

-54

-30.0

-54

-30.0

-54

-30.0

min

-30.0

-54

-30.0

-54

-30.0

-22

-30

-22

-30.0

-54

-30.0

-54

-30.0

-54

-30.0

-54

-30

-22

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

M. u. Resolution

°C

°F

°C

°F

°C

Dec int

Dec int

Dec int

Dec int

Dec int

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°F

°C

°F

°C

°F

°C

°F

°C

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Page 32 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Sd 22

Winter outside temperature relay AUX1

Sd 23

Summer temperature differential relay AUX1

Sd 24

Winter temperature differential relay AUX1

Sd 25

Dynamic set point: summer offset relay AUX2

Sd 26

Dynamic set point: winter offset relay AUX2

Sd 27

Summer outside temperature relay AUX2

Sd 28

Winter outside temperature relay AUX2

Sd 29

Summer temperature differential relay AUX2

Sd 30

Winter temperature differential relay AUX2

Energy saving

Parameters Description

ES 1

ES 2

ES 3

ES 4

ES 5

ES 6

ES 7

ES 8

Start of the Time band 1 (0÷24)

End of the Time Band 1 (0÷24)

Start of the Time band 2 (0÷24)

End of the Time Band 2 (0÷24)

Start of the Time band 3 (0÷24)

End of the Time Band 3 (0÷24)

Monday: energy saving activated

Automatic unit on-off

Tuesday energy saving activated

Automatic unit on-off

ES 9

ES 10

ES 11

ES 12

ES 13

ES 14

Wednesday energy saving activated

Automatic unit on-off

Thursday energy saving activated

Automatic unit on-off

Friday energy saving activated

Automatic unit on-off

Saturday energy saving activated

Automatic unit on-off

Sunday energy saving activated

Automatic unit on-off

Energy Saving setpoint offset in chiller mode

ES 15

ES 16

ES 17

ES 18

Cr1

-30.0

-54

-30

-22

-30

-22

-30.0

-54

-30.0

-54

-30

-22

-30.0

-54

-30.0

-54

-30.0

-54 min

0

0

0

0

0

0

30.0

54

70.0

158

70.0

158

30.0

54

30.0

54

70.0

158

30.0

54

30.0

54

30.0

54 max

24.00

24.00

24.00

24.00

24.00

24.00

0 - 0 7 - 7

0 - 0

0 - 0

0 - 0

0 - 0

0 - 0

7 - 7

7 - 7

7 - 7

7 - 7

7 - 7

Energy Saving differential in chiller mode

Energy Saving setpoint offset in heat pump mode

Energy Saving differential in heat pump mode

Maximum ON time when the unit is switched on by keyboard starting from OFF state by RTC

0= Not enabled

Compressors rack

Type of functioning compressor rack

0= Not enabled

1= regulation by ST09 probe

2 = regolation by pressure probe (Evaporator pressure probe)

0

0 - 0 7 - 7

-30.0

-54

0.0

0

-30.0

-54

0.0

0

30.0

54

25.0

45

30.0

54

25.0

45

1

2

250

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F udm Risoluzione

Hr

Hr

Hr

Hr

Hr

Hr

10 Min

10 Min

10 Min

10 Min

10 Min

10 Min

°C

°F

°C

°F

°C

°F

°C

°F

Min

Dec int

Dec int

Dec int

Dec int

10 Min

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Page 33 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Cr2

Cr3

Cr4

Cr5

Set point compressor suction probe

Minimum set point compressor suction probe

Cr03

0

Cr6

Cr7

Maximum set point compressor suction probe

Regulation band suction probe

Set energy saving compressor rack

Differential energy savingcompressor rack

Cr8

Cr9

Number of compressors enabled in case of failure probe

0 ÷ 6

Number od ventilation step in case of failure probe

0 ÷ 4

Compressors

Parameters Description

CO 1

Minimum compressor ON time after the start-up.

CO 2

CO 3

Minimum compressor OFF time after the switching off.

ON delay time between two compressors or compressor and valve. During this time the led of the next resource is blinking.

Cr03

0.1

1

0.0

0

0.1

1

0

0 min

0

0

1

Cr04

4

250

250

Cr03

50

725

14.0

203

50.0

725

14.0

203

6 max

250

Bar

Psi

Bar

Psi

Bar

Psi

Bar

Psi

Bar psi

Bar

Psi

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int udm Risoluzione

10

10 sec sec

10 sec

10 sec

Sec

CO 4

CO 5

CO 6

CO 7

CO 8

CO 9

CO 10

OFF delay time between two compressors or compressor and valve. During this time the led of the next resource is blinking.

Output time delay after the main power supply start-up to the unit.

All the loads are delayed in case of frequently power failures.

Capacity Control

Functioning (see Capacity Control)

0= With on/off steps

1= Continuous with steps and direct action

2= Continuous with steps and reverse action

3= Continuous with steps and direct total action

Start-up with minimum compressor power / automatic startunloading valve

0 = Only at the compressor start-up (Minimum power automatic start-unloading valve off)

1= At the compressor start-up and during the termoregulation

(Minimum power / automatic start-unloading valve off)

2 = Only at the screw compressor start-up (Minimum power automatic start-unloading valve off)

3= At the compressor start-up and during the termoregulation

(Minimum power / Unloading valve ON with compressor off)

Relay ON time of the Solenoid valve Intermittent for screw compressor, with 0 the function is not enabled.

Relay OFF time of the Solenoid valve Intermittent for screw compressor

Compressor start-up

Kind of compressor start-up

0= Direct ( vedi avviamento compressors )

1= Part - winding

2= Star-delta

0

0

0

0

0

0

0

250

250

3

3

250

250

2

Sec

10

Sec

Sec

Sec

10 sec

Page 34 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

CO 11

CO 12

CO 13

CO 14

CO 15

CO 16

CO 17

CO 18

CO 19

CO 20

CO 21

CO 22

CO 23

CO 24

CO 25

CO 26

CO 27

CO 28

CO 29

CO 30

CO 31

If CO10= 1 part - winding start-up time. To change the time delay between the two contactors of the two compressor circuits.

Se CO10= 2 Star-delta start-up time. To change the time delay between the contactor of the line 1 and the contactor of the centre of the star. (see part – winding /start-triangle functioning)

If CO10= 2 Time of Star-delta start. Time delay to turn off the centre star contactor and to turn on the line 2 contactor (see Stardelta functioning)

By-pass gas valve start-up time / automatic start-unloading valve

(capacity step control)

0

0

0

Rotating – Balancing – Compressors Thermoregulation

Compressor rotation (See compressor rotation)

0 = Sequential

1 = Compressors rotation based on time running hours

0

2 = Compressors rotation based on number of starts-up

Circuit balancing (See Circuit balancing)

0= Circuit saturation

1= Circuit balancing

0

Evaporator water pump

Operative mode of the evaporator pump / supply fan (See

Evaporator pump function)

0= Not enabled (evaporator pump or supply fan).

1= Continuous. When the unit is running in Chiller or HP the pump or the supply fan is running.

2= With compressor. When a compressor is running also the pump or the supply fan is running.

ON compressor delay after water pump / supply fan start-up (See water pump functioning).

OFF delay evaporator water pump / supply fan after compressor switching OFF. This delay is also active when the unit is turned in stand-by (See evaporator water pump function).

Number of time running hours for pump rotation (See water pump group function)

Time to make run the pumps together before rotating from one to the other (See water pump group function)

Condenser water pump

Operative mode for condenser water pump (See condenser water pump function)

0= Not enabled.

1= Continuous. When the unit is running in Chiller or HP the is running.

2= With compressor. When a compressor is running also the pump is running.

Free

OFF delay condenser water pump after compressor switching

OFF. This delay is also active when the unit is turned in stand-by

(See evaporator water pump function).

Number of time running hours for pump rotation (See water pump group function).

Time to make run the pumps together before rotating from one to the other (See water pump group function).

Load maintenance

Compressor 1 hour counter set

Compressor 2 hour counter set

Compressor 3 hour counter set

Compressor 4 hour counter set

Compressor 5 hour counter set

Compressor 6 hour counter set

0

1

0

0

0

0

0

0

0

0

0

0

0

0

0

100

50

250

Dec.

di

Sec

Dec.

di

Sec sec

2

1

2

250

250

Min

Min

999 10Hr

250 Sec

2

250 Min

999 10Hr

250 Sec

999 10 Hr

999 10 Hr

999 10 Hr

999 10 Hr

999 10 Hr

999 10 Hr

0.1 sec

0.1 sec

10Hr

10Hr

10 Hr

10 Hr

10 Hr

10 Hr

10 Hr

10 Hr

Page 35 of 52

CO 44

CO 45

CO 46

CO 47

CO 48

CO 49

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

CO 32

CO 33

CO 34

CO 35

CO 36

CO 37

CO 38

CO 39

CO 40

CO 41

CO 42

CO 43

CO 50

CO 51

CO 52

CO 53

CO 54

“Evaporator pump / Supply fan” hour counter set

2nd Evaporator pump hour counter set

Condenser pump hour counter set

2nd Condenser pump hour counter set

Pump down

Pump down operating mode (See pump down ON/OFF function)

0= Not enabled

1= Unit off with pump–down, unit on without pump–down

2= Unit off with pump–down, unit on with pump–down

3= Chiller mode off with pump–down, chiller mode on without pump–down

4= Chiller mode off with pump–down, chiller mode on with pump– down

Pump–down pressure setpoint (See pump down ON/OFF function)

Pump-down pressure differential (See pump down ON/OFF function)

Maximum pump–down time duration at start-up and stop (See pump down ON/OFF function)

Evaporator Unloading

Unloading compressor setpoint in chiller. From high temperature of the evaporator water inlet (See unloading function).

Unloading Differential. From high temperature of the evaporator water inlet (See unloading function).

Delay time to engage the Unloading function from high temperature of the evaporator water inlet (See unloading function).

Maximum unloading duration time to keep activated the

Unloading function from high temperature of the evaporator water inlet (See unloading function).

Condenser Unloading

Unloading compressor setpoint. From temperature / pressure in chiller mode (See unloading function).

Unloading Differential. From temperature / pressure in chiller mode (See unloading function).

Unloading compressor setpoint. From temperature / pressure in

HP mode (See unloading function).

Unloading Differential. From temperature / pressure in HP mode

(See unloading function).

Maximum unloading duration time from temperature/pressure control.

Number of steps for circuit with active unloading

1= 1st step

2= 2nd step

3= 3rd step

Minimum ON time of the capacity step after the unloading function start (only for capacity compressor)

Compressor liquid injection

Setpoint of the solenoid valve (on) of the liquid injection

0

0

0

1

0

1

1

Setpoint of the solenoid valve (off) of the liquid injection

Management resource in neutral zone

Maximum time of work in neutral zone without insert resource

Maximum time of work in neutral zone without rotation resource

Evaporator low water temperature Unloading

0

0

0

0

0.0

0

0

0

0

0

0

0

0

0

-30

0

0.0

0

0

0

0.0

0

0

0

0.0

0

999

999

999

999

4

50.0

725

14.0

203

250

70.0

725

25.0

45

250

250

50.0

725

14.0

203

50.0

725

14.0

203

250

3

250

150

302

25.0

45

250

999

10 Hr

10 Hr

10 Hr

10 Hr

Bar

Bar

Sec

Min

Bar psi

Bar

Psi

Bar psi

Bar

Psi

Min

°C

°F

°C

°F

10

Sec

Sec

Hr psi psi

°C

°F

°C

°F

Min

10 Hr

10 Hr

10 Hr

10 Hr

Dec int

Dec int

Dec int

Dec int

10sec

Dec int

Dec int

Dec int

Dec int

Dec / int int

Dec int

10 Min

1Hr

Page 36 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

CO 55

CO 56

CO 57

Set point unloading compressor from low evaporator water temperature

Differential unloading compressor from low evaporator water temperature

Maximum unloading duration time from low evaporator water temperature

-30.0

-22

0.1

0

0

70.0

158

25.0

45

°C

°F

°C

°F

Dec int

Dec int

250 Min

CO 58

CO 59

CO 60

CO 61

CO 62

Pump down to time maximum time pump-down in stopped

CO58 = 0 Not enabled maximum time pump-down in started

CO59 = 0 Not enabled

Compressor inverter controlled

Maximum time start up compressor inverter controlled

Minimum value proportional output from start up compressor

0

0

0

0

250

250

250

100

Sec

Sec sec

%

CO 63

CO 64

CO 65

CO 66

Minimum time capacity variation from start up compressor inverter controlled

Minimum percentage continuative of work of the compressor inverter controlled before to start counting CO64 time

Maximum time continuative of work of the compressor with percentage less of CO63

Time of forcing the compressor inverter controlled to the maximum power

Maximum time continuative of work of the compressor inverter controlled

0

0

0

0

250

100

250

250 sec

%

Min sec

10 Min

10sec

0 999 Hr 1Hr

CO 67

CO 68

CO 69

CO 70

CO 71

Minimum value of the compressor 1 inverter controlled

Maximum value of the compressor 1 inverter controlled

Minimum value of the compressor 2 inverter controlled

Maximum value of the compressor 2 inverter controlled

Minimum time capacity variation compressor inverter controlled

Tamdem function

Maximum operating time of a single compressor

CO 72

0

CO 73

CO 74

CO 75

Load maintenance

Sanitary water pump hour counter

Solar panel water pump hour counter

4 way valve

Forced time to reverse the 4 way valve when the compressor is switched off

Auxiliary relay menu function

Parameters Description

Auxiliary relay of the circuit 1

0 min

0

0

0 CO68

CO67 100

0

CO69 100

1

CO70

250

250

999

999

250 max

%

%

%

% sec

Min

10 Hr

10 Hr sec

10 Hr

10 Hr

M. U. Resolution

Page 37 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

US 1

US 2

US 3

US 4

US 5

Auxiliary relay 1 operating mode (See graph and auxiliary relay functions)

0= Not enabled

1= Always available with direct action

2= Available only when the unit is on with direct action

3= Always available with reverse action

4= Available only when the unit is on with reverse action

Analog input configuration for auxiliary relay 1 control. Allows to select which probe value Pb1..Pb10 controls the relay

Auxiliary relay 1 summer minimum set point

Auxiliary relay 1 summer maximum set point

0

1

-30.0

-22

0.0

0

US5

4

10

US5

70.0

158

50.0

725

US3 US4

Auxiliary relay 1 summer set point

US 6

US 7

Auxiliary relay 1 winter minimum set point

Auxiliary relay 1 winter maximum set point

-30.0

-22

0.0

0

US8

US8

70.0

158

50.0

725

US 8

US 9

US 10

US 11

US 12

US6 US7

Auxiliary relay 1 winter set point

Auxiliary relay 1 summer differential

Auxiliary relay 1 winter differential

Auxiliary relay circuit 2

Auxiliary relay 2 operating mode (See graph and auxiliary relay functions)

0= Not enabled

1= Always available with direct action

2= Available only when the unit is on with direct action

3= Always available with reverse action

4= Available only when the unit is on with reverse action

Analogue input configuration for auxiliary relay 2 control . Allows to select which probe value Pb1..Pb10 controls the relay

0.1

0

0.1

1

0.1

0

0.1

1

0

1

4

10

25.0

45

14.0

203

25.0

45

14.0

203

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Page 38 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

US 13

Auxiliary relay 2 summer minimum set point

US 14

Auxiliary relay 2 summer maximum set point

US 15

Auxiliary relay 2 summer set point

US 16

Auxiliary relay 2 winter minimum set point

US 17

Auxiliary relay 2 winter maximum set point

US 18

Auxiliary relay 2 winter set point

US 19

Auxiliary relay 2 summer differential

US 20

US 21

US 22

US 23

US 24

Auxiliary relay 2 winter differential

Maximum operating time of auxiliary realys

Auxiliary proportional output n° 1

Auxiliary proportional output n° 1 operating mode

0= Not enabled

1= Always available with direct action

2= Available only when the unit is on with direct action

3= Always available with reverse action

4= Available only when the unit is on with reverse action

Analogue input configuration for auxiliary control 1

Allows to select which probe value Pb1..Pb10 controls output

Analog output 1 summer minimum set point

US 25

Analog output 1 summer maximum set point

-30.0

-22

0.0

0

US15

70.0

158

50.0

725

US13 US14

0.1

0

0.1

1

0

0.1

0

0.1

1

US15

-30.0

-22

0.0

0

US18

US18

70.0

158

50.0

725

US16 US17

25.0

45

14.0

203

25.0

45

14.0

203

250 min

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

0 4

1

-30.0

-22

0.0

0

10

US26

US26

70.0

158

50.0

725

°C

°F

Bar

Psi

°C

°F

Bar

Psi

Dec int

Dec int

Dec int

Dec int

Page 39 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

US 26

Analog output 1 summer set point

US 27

Analog output 1 winter minimum set point

US 28

Analog output 1 winter maximum set point

US 29

Analog output 1 winter set point

US 30

Analog output 1 summer differential

US 31

US 32

US 33

US 34

US 35

US 36

Analog output 1 winter differential

Analog output 1 minimum value

Analog output 1 maximum value

Auxiliary proportional output n° 2

Auxiliary proportional output n° 2 operating mode

0= Not enabled

1= Always available with direct action

2= Available only when the unit is on with direct action

3= Always available with reverse action

4= Available only when the unit is on with reverse action

Analogue input configuration for auxiliary 2 control

Allows to select which probe value Pb1..Pb10 controls output

Analog output 2 summer minimum set point

US 37

Analog output 2 summer maximum set point

US 38

Analog output 2 summer set point

US 39

Analog output 2 winter minimum set point

US24 US25

-30.0

-22

0.0

0

US29

US29

70.0

158

50.0

725

US27 US28

0.0

0

0.0

0

0.0

0

0.0

0

25.0

45

14.0

203

25.0

45

14.0

203

0 US33 %

US32 100 %

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

0

1

-30.0

-22

0.0

0

-30.0

-22

0.0

0

4

10

US38

US38

70.0

158

50.0

725

US36 US37

US41

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

Page 40 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

US 40

US 41

US 42

US 43

Analog output 2 winter maximum set point

Analog output 2 winter set point

Analog output 2 summer differential

US 44

US 45

US 46

Analog output 2 winter differential

Analog output 2 minimum value

Analog output 2 maximum value

Operation mode under minimum value

Condenser fan

Parameters Description

FA 1

Fan configuration output

0 = Not enabled

1 = Always on

2 = ON/OFF regulation with steps

3 = ON/OFF Continuous regulation

4 = Proportional speed control

FA 2

FA 3

FA 4

Fan operating mode

0= Dependent from the compressor

1= Independent from the compressor

If the condenser fan control is the triac output, when the regulation starts the trigger output will drive the condenser fan at the maximum voltage for the time FA 3 then, then the regulation will follow the temperature/pressure of the probe.

Phase shifting of the fan motor

FA 5

FA 6

FA 7

FA 8

FA 9

Number of condensing circuits

0= one condenser circuit

1= tow condenser circuits

Pre-ventilation time before turning on the compressor in chiller mode.

To turn on the fan at the maximum speed before the compressor and reduce the successive condensing temperature/pressure increasing. (only if FA01=4)

Fan in Chiller mode

Minimum speed for condenser fan in Chiller mode.

To set the minimum fan speed percentage value (30..100%), it is related to the fan power supply.

Maximum speed for condenser fan in Chiller mode.

To set the maximim fan speed percentage value (30..100%), it is related to the fan power supply.

Proportional speed control FA01 = 4

Temperature or pressure limit to enable the minimum speed FA 7

ON/OFF regulation FA01 = 2/3

SETpoint step n° 1 min

0

0

0

0

0

0

0

0

-30.0

-22

0.0

0

US41

70.0

158

50.0

725

US39 US40

0.0

0

0.0

0

0.0

0

0.0

0

25.0

45

14.0

203

25.0

45

14.0

203

0 US45 %

US44 100 %

0 1

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi max

4

1

250

8

1

250

100

100

70.0

158

50.0

725

M. U. Resolution

Sec

Micro

Sec

Sec

%

%

°C

°F

Bar

Psi

250  s

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Page 41 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

FA 10

FA 11

FA 12

FA 13

FA 14

FA 15

FA 16

FA 17

FA 18

FA 19

FA 20

FA 21

Proportional speed control FA01 = 4

Temperature or pressure limit to enable the maximum speed FA

8

ON/OFF regulation FA01 = 2/3

SETpoint step n° 2

Proportional speed control FA01 = 4

Proportional band for condenser fan control in chiller

To set the temperature/pressure differential between the minimum and the maximum of the fan speed regulation.

ON/OFF regulation FA01 = 2/3

Differential step circuit n° 1

Proportional speed control FA01 = 4

CUT-OFF differential in chiller. To set a temperature/pressure differential to stop the fan.

ON/OFF regulation FA01 = 2/3

Differential step circuit n° 2

Over ride CUT- OFF in chiller. To set a temperature/pressure differential to keep the minimum fan speed.

-30.0

-22

0.0

0

0.0

0

0.0

0

0.0

0

0.0

0

0.0

0

0.0

0

CUT-OFF time delay. To set a time delay before activating the

CUT-OFF function after the fan start-up.

If after the compressor start-up the proportional regulator requires to turn off the fan (cut-off) and FA14  0, the fan is on at the minimum speed for the time set in this parameter. If FA14=0 the function is disabled.

Night speed in chiller. To set the maximum fan speed percentage value (30..100%), it is related to the fan power supply.

Fan in Heat pump mode

Minimum speed for condenser fan in Heat Pump mode.

To set the minimum fan speed percentage value (30..100%), it is related to the fan power supply.

Maximum speed for condenser fan in Heat Pump mode.

To set the maximum fan speed percentage value (30..100%), it is related to the fan power supply.

Proportional speed control FA01 = 4

Temperature or pressure limit to enable the minimum speed

FA16

ON/OFF regulation FA01 = 2/3

SETpoint step n° 1

Proportional speed control FA01 = 4

Temperature or pressure limit to enable the maximum speed

FA17

ON/OFF regulation FA01 = 2/3

SETpoint step n° 2

Proportional speed control FA01 = 4

Proportional band for condenser fan control in heat pump

To set the temperature/pressure differential between the minimum and the maximum of the fan speed regulation.

ON/OFF regulation FA01 = 2/3

Differential step circuit n° 1

Proportional speed control FA01 = 4

CUT-OFF differential in heat pump. To set a temperature/pressure differential to stop the fan.

ON/OFF regulation FA01 = 2/3

Differential step circuit n° 2

0

0

0

0

0.0

0

0.0

0

0.0

0

0.0

0

-30.0

-22

0.0

0

-30.0

-22

0.0

0

70.0

158

50.0

725

25.0

45

14.0

203

25.0

45

14.0

203

25.0

45

14.0

203

250

100

100

100

70.0

158

50.0

725

70.0

158

50.0

725

25.0

45

14.0

203

25.0

45

14.0

203

Sec

%

%

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

%

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Page 42 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

FA 22

FA 23

FA 24

FA 25

FA 26

FA 27

FA 28

FA 29

Over ride CUTOFF in Heat pump. To set a temperature/pressure differential to keep the minimum fan speed.

0.0

0

0.0

0

Night speed in Heat pump. To set the maximum fan speed percentage value (30..100%), it is related to the fan power supply.

Hot start

Hot start setpoint

0

Hot start differential

-30.0

-22

0.0

0

ON/OFF regulation FA01 = 2/3

SETpoint step n° 3

3 / 4 step condenser Fan in Chiller mode

ON/OFF regulation FA01 = 2/3

SETpoint step n° 4

ON/OFF regulation FA01 = 2/3

SETpoint step n° 3

3 / 4 step condenser Fan in heat pump

ON/OFF regulation FA01 = 2/3

SETpoint step n° 4

Antifreeze heaters – Integration heating - boiler

-30.0

-22

0.0

0

-30.0

-22

0.0

0

-30.0

-22

0.0

0

-30.0

-22

0.0

0

Parameter Description

Ar 1

Anti-freeze heaters/integration heating setpoint for air/air unit in

Chiller mode.

Ar 2

To set a temperature value, below this value the anti-freeze relay is activated.

Regulation band for antifreeze in Chiller mode.

min

-30.0

-22

0.1

0

Ar 3

Ar 4

Set Anti-freeze heaters/integration heating setpoint for air/air unit in HP mode.

To set a temperature value, below this value the anti-freeze relay is activated.

Regulation band for antifreeze in HP mode.

-30.0

-22

-30.0

-22

Ar 5

Ar 6

Antifreeze heaters / integration heating in defrost

0= ON only with thermoregulation control

1= ON with thermoregulation and during the defrosting cycle

Antifreeze probe to manage heaters / support heaters in Chiller mode.

0= Not enabled

1= Evaporator inlet

2= Evaporator outlet 1 and 2

3= Evaporator outlet 1 and 2 and common outlet

0

0

70.0

158

25.0

45 max

70.0

158

25.0

45

3

70.0

158

50.0

725

70.0

158

50.0

725

70.0

158

50.0

725

70.0

158

50.0

725

25.0

45

14.0

203

100

70.0

158

70.0

158

1

°C

°F

Bar

Psi

%

°C

°F

°C

°F

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi

°C

°F

Bar

Psi m. u. Risoluzione

°C

°F

°C

°F

Dec int

Dec

Int

°C

°F

°C

°F

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Page 43 of 52

Ar 17

Ar 18

Ar 19

Ar 20

Ar 12

Ar 13

Ar 14

Ar 15

Ar 16

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Ar 7

Ar 8

Ar 9

Ar 10

Ar 11

Ar 21

Ar 22

Antifreeze probe to manage heaters / support heaters in HP mode.

0= Not enabled

1= Evaporator inlet.

2= Evaporator outlet 1 and 2.

3= Evaporator outlet 1 and 2 and common outlet.

Thermoregulation probe for anti-freeze / condenser heaters.

0= not enabled.

1= Condenser common water inlet probe.

2= Condenser common water inlet and condenser inlet 1 / 2 probe.

3= Condenser water outlet 1 / 2 probe.

4= Condenser water outlet 1 / 2 and common outlet.

Anti-freeze heaters or condenser/evaporator water pump control with unit in remote OFF or stand-by mode:

0= Control not enable

1=Controlled by anti-freeze thermoregulation.

Anti-freeze heaters control for condenser/evaporator faulty probe:

0= Anti-freeze heaters OFF

1= Anti-freeze heaters ON

Boiler function

Boiler function

0=Not enabled

1=Enabled for integration heating

2= Enabled for heating

External air temperaure setpoint for boiler heaters (on)

Temperature differential for boiler heaters (off)

Time delay before turning the boiler on

Boiler function in Chiller mode

Setpoint for boiler heaters (on) in chiller

Proportional band for boiler heaters in chiller

0

0

0

0

0

-30.0

-22

0

0

0

Boiler function in heat pump

Setpoint for boiler heaters (on) in HP

Proportional band for boiler heaters in HP

External air setpoint to stop the compressor as integration function

External air differential to stop the compressor as integration function

Anti freeze alarm

Termoregulation probe anti freeze alarm in chiller mode

0= Not enabled

1= Evaporator inlet

2= Evaporator outlet 1 and 2

3= Evaporator outlet 1 and 2 and common outlet

4= External temperature

Termoregulation probe anti freeze alarm in heat pump mode

0= Not enabled

1= Evaporator inlet

2= Evaporator outlet 1 and 2

3= Evaporator outlet 1 and 2 and common outlet

4= External temperature

-30.0

-22

-30.0

-22

-30.0

-22

0.1

0

-30.0

-22

0.1

0

0

0

3

4

1

1

2

70.0

158

25.0

45

250

70.0

158

70.0

158

70.0

158

25.0

45

70.0

158

25.0

45

4

4

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F

Dec int

Dec int

Min

Dec int

Dec int

Dec int

Dec int

Dec int

Dec int

Page 44 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

Ar 23

Ar 24

Ar 25

Termoregulation probe anti freeze alarm water condenser

0= not enabled.

1= Condenser common water inlet probe.

2= Condenser common water inlet and condenser inlet 1 / 2 probe.

3= Condenser water outlet 1 / 2 probe.

4= Condenser water outlet 1 / 2 and common outlet.

Anti freeze alarm

Water pump / antifreeze alarm in OFF/ stand-by

0= Aways in OFF

1= ON only with thermoregulation control

Termoregulation probe water pump in antifreeze mode

0= Not enabled

1= Evaporator inlet

2= Evaporator outlet 1 and 2

3= Evaporator outlet 1 and 2 and common outlet

4= External temperature

Set point starting water pump in antifreeze alarm

0

0

0

Ar 26

Ar 27

Differential starting water pump in antifreeze alarm

-30.0

-22

0.1

0

Defrost

dF 4 dF 5 dF 6 dF 7 dF 8 dF 9 dF 10

Parameter Description

dF 1 dF 2 dF 3 dF 11 dF 12 dF 13 dF 14 dF 15 dF 16

Defrost configuration:

0= Not enabled

1= Temperature / pressure

2= start depends on par. dF24 stop for time duration

3= start depends on par. dF24 stop for external contact

4= defrost with condenser fan

Temperature or pressure of the defrost start-up min

0

Temperature or pressure of the defrost stop

Minimum defrost duration.

Maximum defrost duration.

Time delay between the defrost of two circuits

OFF compressor delay before the defrost

OFF compressor delay after the defrost

Defrost interval time of the same circuit

Temperature setpoint for combined defrost of the 1st circuit after parameter DF10 counting.

Temperature setpoint for combined defrost end of the 1st circuit.

Temperature setpoint for combined defrost of the 2nd circuit after parameter DF10 counting.

-30.0

-22

-30.0

-22

Temperature setpoint for combined defrost end of the 2nd circuit.

-30.0

-22

Activation of all the steps of the 1st circuit during the defrost.

0= Not enabled

1= Enabled

Activation of all the steps of the 2nd circuit during the defrost.

0= Not enabled

1= Enabled

Time delay between two compressor ON in defrost mode

0

1

-30.0

-22

0

0

0

0

-30.0

-22

0.0

0

-30.0

-22

0.0

0

0

0

0

4

1

4

70.0

158

25.0

45 max

4

1

250

250

250

250

250

250

99

70.0

158

70.0

158

50.0

725

70.0

158

50.0

725

70.0

158

70.0

158

70.0

158

1

°C

°F

°C

°F udm Risoluzione

°C

°F bar psi

°C

°F bar psi

Sec

Min

Min

Sec

Sec

Min

°C

°F

°C

°F

°C

°F

°C

°F

Sec

Dec int

Dec int

Dec int

Dec

Int

Dec int

Dec

Int

Dec int

Dec int

Dec int

Dec int

Page 45 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

dF 17 dF 18

Fan control during defrost / dripping time

0= Not enabled

1= Only in defrost

2= For both functions defrost / dripping time

Pressure / temperature setpoint to force the ventilation ON during the defrost.

0

-30.0

-22

0.0

0

2

70.0

158

50.0

725

°C

°F bar psi

Dec int

Dec

Int

dF 19 dF 20 dF 21

Forced defrost

Minimum time delay before a forced defrost

Pressure / temperature setpoint for a forced defrost

Forced defrost differential

0

-30.0

-22

0.0

0

0.1

0

0.0

0

250

70.0

158

50.0

725

25.0

45

14.0

203 sec

°C

°F bar psi

°C

°F

Bar

Psi

Dec int

Dec int

Dec int

Dec int

dF 22 dF 23

Defrost operative mode

Defrost start-up with 2 circuits

0= Independent

1= If both have reached the necessary requirements

2= If one has reached the necessary requirements

End defrost for two circuits and common ventilation.

0= Independent

1= If both have reached the necessary end defrost requirements

2= If one has reached the necessary end defrost requirements

Start / stop defrost selection

Parameters description

dF 24

Start / stop defrost probe

0= start and stop with condenser temperatur / pressure probe

1= start with evaporator pressure probe / stop with condenser temperatur / pressure probe

2= start with condenser temperatur / pressure probe / stop with evaporator pressure probe

3= start and stop with evaporator pressure probe

Supply fan operating mode during defrost cycle

dF 25

min

0

Stop supply fan diuring defrost cycle

0= Not enabled

1= enable

Defrost only with condenser fan

0

dF 26 dF 27 dF 28 dF 29 dF 30

Set point to enable defrost with condenser fan

Hybrid exchangers summer set point

Hybrid exchangers summer differential

Hybrid exchangers winter set point

Hybrid exchangers winter differential

-30.0

-22

-30.0

-22

0.1

0

-30.0

-22

0.1

0

Sanitary water

Parameters Description

FS 1

FS 2

FS 3

Sanitary water regulation mode

Sanitary water thermoregulation priority

Sanitary water thermoregulation set point

0

0

2

2 max

3

1

70.0

158

70.0

158

25.0

45

70.0

158

25.0

45 udm

°C

°F

°C

°F

°C

°F

°C

°F

°C

°F resolution min

0 max

2 m. u. Resolution

0 1

FS05 FS06 °C/°F dec/int

Dec int

Dec int

Dec int

Dec int

Dec int

Page 46 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

FS 4

Sanitary water thermoregulation band

FS 5

Minimum value of the sanitary water set point

FS 6

FS 7

FS 8

FS 9

FS 10

FS 11

FS 12

FS 13

FS 14

FS 15

Maximum value of the sanitary water set point

Full loads enabling to reach the sanitary water set point

Heaters enabling during the sanitary water thermoregulation

Operation working time to activate the heaters during the sanitary water thermoregulation

Time delay to activate the sanitary water valve

Reversing cycle delay during sanitary water thermoregulation

Antilegionella function operating mode

Delay time between two Antilegionella cycles

Antilegionella Set point

Minimum value of the Antilegionella set point

FS 16

FS 17

FS 18

FS 19

FS 20

Maximum value of the Antilegionella set point

Hour selection for the Antilegionella activation

Day selection for the Antilegionella activation

Minimum operating working time of the Antilegionella cycle

Temperature band for heaters deactivation during Antilegionella cycle

FS 21

Differential value to enable the freecooling function

FS 22

FS 23

FS 24

Differential value for the free cooling regulation

Set point for solar panel activation

Differential value for solar panel deactivation

FS 25

FS 28

Minimum value of the solar panel set point

FS 26

FS 27

Maximum value of the solar panel set point

Delay time to activate the sanitary water valve starting from pump activation

Delay time to deactivate the sanitary water pump starting from valve deactivation

Maximum operating working time of the Antilegionella cycle

FS 29

FS 30

Sanitary water: security set point

FS 31

FS 32

FS 33

Sanitary water: security differential

Sanitary water: minimum interruption time

Sanitary water pump operation mode

Alarms

Parameters Description

AL 1

AL 2

Low alarm

Low pressure alarm delay from analog and digital input

Low pressure alarm delay from digital input after compressor stop if the low pressure switch is used for the pump down.

AL02= 0 low pressure alarm not enable with compressor OFF

AL02≠ 0 low pressure alarm enable after AL02 time with compressor OFF min

0

0

0

0

-30.0

-22

0.1

0

0

0

0.1

0

-30.0

-22

25.0

45

FS06

FS05

0

0

0

70.0

158

1

1

250 Min

0

0

0

0.1

0

0

0

0

0 sec sec

FS15 FS16 °C/°F

-30.0

-22

FS14

250

250

1

250

FS14

Hr

°C

°F

°C

°F

Hr

0.1

FS23

70.0

158

24.00

7

250

25.0

45

25.0

45

25.0

0.1

0 45 °F

FS25 FS26 °C/°F

0.1

0

-30.0

-22

25.0

45

FS23

70.0

158 min

°C

°F

°C

°F

°C

°C

°F

°C

°F

°C

°F

0 250 sec

°C

°F

°C

°F

°C

°F

250

250

70.0

158

25.0

45

250

1 max

250

250 sec min

°C

°F

°C

°F min

Dec int

Dec int

Dec int int int

0 dec/int

Dec int

Dec int

10 min

Dec int

Dec int

Dec int dec/int

Dec int

Dec int

Dec int

Dec int

Dec int m. u. Resolution

Sec

Sec 10 Sec

Page 47 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

AL 3

AL 4

AL 5

AL 6

AL 7

AL 8

AL 9

AL 10

AL 11

AL 12

AL 13

AL 14

AL 15

AL 16

AL 17

AL 18

AL 19

AL 20

Low pressure alarm setpoint from analogue input

Low pressure alarm differential from analogue input

Maximum number of low pressure events from digital/analogue inputs:

Manual reset if AL05 = 0

Automatic reset if AL05 =16

From automatic to manual reset if AL05= 1..15

Low temperature/pressure alarm during defrost

0= Not enabled

1= Enabled

Low temperature/pressure alarm delay during defrost

Low temperature/pressure alarm with unit in OFF or stand – by:

0 = Not enabled

1= Alarm enabled

High Alarm

High temperature/pressure alarm from analogue input

High temperature/pressure alarm differential from analogue input

-30.0

-22

0.0

0

0.1

0

0.0

0

0

0

0

0

-30.0

-22

0.0

0

0.1

0

0.0

0

Oil Alarm

Low oil pressure / level delay from digital input

Minimum time for low oil pressure / level from digital input activation in normal working condition.

Maximum number of low oil pressure/level events:

Always manual reset if AL13= 0

Always automatic reset if AL13 =16

From automatic to manual reset if AL13 = 1..15

Flow alarm

Configuration

0= Not enabled

1= Only for chiller

2= Only for heat pump

3= For both chiller and heat pump

“Flow switch / supply fan overload” alarm delay after pump/fun activation.

Maximum time flow switch alarm active befor to block the water pump

Minimum “Flow switch / supply fan overload” active time duration.

Minimum “Flow switch / supply fan overload” not active time duration.

Compressor overload alarm

Compressor overload alarm delay after compressor start-up

Maximum number of compressor overload alarm events

Always manual reset if AL20 = 0

Always automatic reset if AL20 =16

From automatic to manual reset if AL20 =1..15

Pump down alarm

0

0

0

0

0

0

0

0

0

0

70.0

158

50.0

725

25.0

45

14.0

203

16

16

3

250

16

250

250

250

250

1

250

1

70.0

158

50.0

725

25.0

45

14.0

203

250

250

Sec

Sec

Sec

Sec

Sec

°C

°F bar psi

°C

°F bar psi

Sec

Sec

Sec

°C

°F bar psi

°C

°F bar psi

Dec int

Dec int

Dec int

Dec

Int

Dec int

Dec int

Dec int

Dec int

Page 48 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

AL 21

AL 22

AL 23

AL 24

AL 25

AL 26

AL 27

AL 28

AL 29

AL 30

AL 31

AL 32

AL 33

AL 34

Maximum number of pump down alarm events per hour in stop condition. After this number the alarm is logged, displayed and signalled with alarm relay + buzzer.

Manual reset if AL21 = 0

Automatic reset if AL21 =16

From automatic to manual reset if AL21 =1..15

Maximum number of pump down alarm events per hour in startup condition. After this number the alarm is logged, displayed and signalled with alarm relay + buzzer.

Always manual reset if AL22 = 0

Always automatic reset if AL22 =16

From automatic to manual reset if AL21 =1..15 and parameter

AL23 config.

Select if the pump down alarm must change from automatic to manual reset:

0= Always automatic reset

1= Manual reset after AL21 alarm events

Anti-freeze alarm in Chiller mode

Minimum antifreeze setpoint in chiller (from –30 °C to AL24)

Maximum antifreeze setpoint in chiller (from AL24 to 70 °C)

Setpoint temperature for low anti-freeze alarm, low ambient temperature (air/air), low temperature air outlet (air/air). From

AL24 to AL25.

Differential of alarm reset in Chiller mode for anti-freeze, low ambient air temperature or low outlet air temperature alarms.

Alarm delay for anti-freeze, low ambient air temperature or low outlet air temperature. The temperature must be lower than AL26 for this time duration before having the alarm event.

Maximum number of alarm events anti-freeze, low ambient air temperature or low outlet air temperature before changing from automatic to manual alarm reset:

Always manual reset if AL29 = 0

Always automatic reset if AL29 = 16

From automatic to manual if AL29 = 1. .15

Anti-freeze alarm configuration in chiller

0= to turn the compressors off when the anti-freeze control probe is lower than AL26 (after the time delay), the display shows the alarm label.

Buzzer and Alarm relay are not activated.

1= to turn the compressors off when the anti-freeze control probe is lower than AL26 (after the time delay), the display shows the alarm label.

Buzzer and Alarm relay are activated.

Anti-freeze alarm in Heat pump mode

Setpoint of the minimum limit in heat pump (va da – 30 °C a

AL32)

Setpoint of the maximum limit in heat pump (va da AL31 a 70 °C)

Anti-freeze alarm setpoint in heat pump

Setpoint temperature for low anti-freeze alarm, low ambient temperature (air/air), low temperature air outlet (air/air). (from

AL31 to AL32)

Alarm differential in heat pump. To reset the anti-freeze, low ambient Temperature (air/air), low temperature air outlet (air/air) alarms.

0

0

0

-30.0

-22

AL26

AL26

70.0

158

°C

°F

°C

°F

AL24 AL25 °C/°F

0

0

0

25.0

45

250

°C

°F

Sec

0

0

-30.0

-22

AL33

16

16

1

16

1

AL33

70.0

158

°C

°F

°C

°F

AL31 AL32 °C/°F

0

0

25.0

45

°C

°F

Dec int

Dec int

Dec/int

Dec int

Dec int

Dec int

Dec/int

Dec int

Page 49 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

AL 35

AL 36

AL 37

AL 38

AL 39

AL 40

AL 41

AL 42

AL 43

AL 44

AL 45

AL 46

Anti-freeze alarm delay in HP for low outlet air temperature

(air/air)

Attention

If during the Stand-by or remote off there is an anti-freeze alarm event, and the AL35 <>0, starting the heat pump mode, from keyboard or digital input. In this case the anti-freeze alarm is aborted and the compressor starts for the AL35 time to heat the air or the water.

After the AL35 time if the antifreeze probe value is still lower than

AL33 setpoint, for maximum AL36 seconds, the unit is stopped and the anti-freeze alarm is generated again.

Anti-freeze alarm delay for low air ambient temperature or low outlet air temperature in heat pump normal condition.

The detected temperature must be lower than AL33 for the time

AL36 before giving the alarm

Maximum number of anti-freeze alarm events for low air ambient temperature or low outlet air temperature in heat pump. It sets the alarm reset condition:

Always manual reset AL37 = 0

Always automatic reset AL37 = 16

From automatic to manual reset if AL37 = 1..15

Anti-freeze alarm configuration in heat pump

0= to turn the compressors off when the anti-freeze control probe is lower than AL33 (after the time delay), the display shows the alarm label.

Buzzer and Alarm relay are not activated.

1= to turn the compressors off when the anti-freeze control probe is lower than AL33 (after the time delay), the display shows the alarm label.

Buzzer and Alarm relay are activated.

Compressor high discharge temperature

Compressor high discharge temperature setpoint

0

0

0

0

Compressor high discharge temperature differential

Number of compressor high discharge temperature events per hour to determine the alarm reset condition:

Always manual reset if AL41 = 0

Always automatic reset if AL41 =16

From automatic to manual if AL41 = 1..15

Generic alarm 1

Maximum number of generic alarm events (each event stop the regulation) before turning the alarm from automatic to manual:

Always manual AL42 = 0

Always automatic AL42 =16

From manual to utomatic if AL42 value is between 1 and 15

Generic alarm delay time after the digital input activation

Generic alarm delay time after the digital input is not activate

0

0

0

0

Alarm relay

Enable alarm relay with unit in off or stand – by:

0= Alarm output not enabled

1= Alarm output enabled

0

Password reset: Alarm log – Compressor overload

Password value to reset the alarm log or the compressor overload alarm.

0

0

0

0

0

250 Sec

250 Sec

16

1

150

302

25.0

45

°C

°F

°C

°F

16

16

Dec / int int

Dec int

250

250

Sec

10 sec

10 sec

1

999

Page 50 of 52

AL 52

AL 53

AL 54

AL 60

AL 61

AL 62

AL 63

AL 64

AL 65

AL 66

AL 67

AL 68

AL 69

AL 70

AL 71

AL 72

AL 55

AL 56

AL 57

AL 58

AL 59

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

AL 47

AL 48

AL 49

AL 50

AL 51

Thermal alarm of the compressor

0= lock the compressor

1= lock the whole circuit

Thermal alarm when the compressor is OFF

0 = Not enabled

1= Alarm enabled

Oil alarm in OFF

Oil alarm when the compressor is OFF

0 = Not enabled

1= Alarm enabled

Generic alarm / signal 2

Functioning generic alarm n° 2

0= only signal always automatic reset

1= the alarm block the unit reset depends on the value of parameter AL51

Maximum number of generic alarm events before turning the alarm from automatic to manual:

Always manual AL51 = 0

Always automatic AL51 =16

From manual to utomatic if AL51 value is between 1 and 15

Generic alarm delay time after the digital input activation

Generic alarm delay time after the digital input is not activate

Reset High pressure / temperature alarm

Maximum number of high pressure / temperature alarm events before turning the alarm from automatic to manual:

Always manual AL54 = 0

Always automatic AL54 =16

From manual to utomatic if AL54 value is between 1 and 15

Flow alarm condenser

“Flow switch water condenser alarm delay after pump activation.

Maximum time flow switch alarm active befor to block the water pump

Minimum “Flow switch water condenser active time duration.

Minimum “Flow switch water condenser not active time duration.

High water evaporator inlet temperature

Maximum number of high water temperature alarm events

Always manual reset if AL59 = 0

Always automatic reset if AL59 =16

From automatic to manual reset if AL59 =1..15

High water temperature alarm delay time from ON compressor

Set point higt water temperature

0

0

0

Differential higt water temperature

Analogue input configuration.Allows to select which probe value

NTC/PTC (Pb1..Pb10)

Low pressure alarm delay

Sanitary water flow switch alarm delay

San. water flow switch delay to stop pump

Sanitary water flow switch activation time

San. water flow switch de-activation time

Solar panel flow switch alarm delay

Solar panel flow switch delay to stop pump

Solar panel flow switch activation time

Solar panel flow switch de-activation time

0

0

0

0

0

1

0

0

0

0

0

0

0

0

0

0

-30.0

-22

0.1

0

1

0

0

0

0

16

1

1

1

1

16

250

250

16

250

70.0

158

25.0

45

10

250

250

250

250

250

250

250

250

250

250

250

250

250

Sec

Sec

Sec

°C

°F

°C

°F

Sec

Sec

Sec

Sec

Sec

Sec

Sec

Sec

Sec

Sec

Sec

Sec

Sec

10 sec

Dec int

Dec int

Page 51 of 52

1592015850 Quick reference guide IC290D/291D FW 1.8 (rel 1.1)

10. Technical Data

Ichill 290D / Ichill 291D

Housing:

self extinguishing ABS

Case:

10 DIN

Mounting:

10 DIN rail

Index of protection:

IP20 IC290D / 291D; IP40 keyboard VGI890

Keyboard frontal protection:

IP65 with gasket

Power supply:

12Vac/dc,-10%÷+15% or

24 Vac/dc±10%. 50/60 Hz

Power absorption:

10VA max

Probes:

6 temperature probes (NTC/PTC) + 4 temperature or pressure probes (NTC/PTC/4 ÷ 20ma /

0 ÷ 5Volt)

Digital inputs:

18 (free voltage)

Relay outputs:

10 (IC260D/L) or 14 (IC261D/L): SPDT 5(2) A, 250Vac.

Data storing:

on the non-volatile memory (EEPROM)

Operating temperature:

-10÷55 °C

Storage temperature:

-30÷85 °C

Relative humidity:

20 ÷ 85% (no condensing)

Measuring range:

Temperature measured by NTC probe: - 50÷110 °C (-58 ÷ 230 °F)

Temperature measured by PTC probe: -50÷150 °C (-58÷302 °F )

Pressure: 0÷ 50 bar (0÷725 psi)

Resolution:

0,1 °C or 1 °F (selectable)

Accuracy of the controller at 25°C:

±0,7 °C ±1 digit

Page 52 of 52

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement