Murphy MC-900 MATIC MC-900, MC-900-2 Generator Engine Control System MANUAL GENERATOR ENGINE CONTROL SYSTEM DESIGN, INSTALLATION AND OPERATING MANUAL

Below you will find brief information for MC-900 MC-900, MC-900 MC-900-2, MC-900 MC-900-12, MC-900 MC-900-24, MC-900-2 MC-900-2-12, MC-900-2 MC-900-2-24. This manual details installation, operation, maintenance, and troubleshooting for Murphy's MC-900 series manual generator engine control systems. It covers both four-cycle and two-cycle engine models, outlining features like overcrank protection, shutdown time delays, and multiple shutdown circuits.

PDF
Document
Murphy MC-900 Series Manual Generator Control System Operating Manual | Manualzz

Advertisement

Advertisement

/

Advertisement

Key features

  • Manual Start

  • Automatic Shutdown

  • Shutdown Time Delay Bypass

  • Overcrank Protection

  • Overspeed Protection

  • Oil Pressure Monitoring

  • Water Temperature Monitoring

  • Spare Shutdown Circuits

  • Remote Indication of Shutdowns

  • Status Signal Output

Frequently asked questions

You can test the overspeed switch setting by starting the engine, adjusting the governor to normal RPM, and depressing and holding the Overspeed Test pushbutton. Slowly turn the Overspeed Set adjustment counterclockwise until the “Overspeed” and “Overspeed Relay” lights come on and the engine shuts down. Release the pushbutton and restart the engine. Increase the governor speed setting slowly until the engine shuts down again on overspeed. This should occur about 10% above governor speed.

The shutdown circuits are used to automatically shut down the engine in the event of a fault, such as overcrank, overspeed, low oil pressure, high water temperature, or other user-defined conditions.

To reset the shutdown circuits, turn the Mode Selector switch OFF.

The input switches should be dry contact type with a maximum current of 2 ma, 8 VDC or less. The frequency signal for the speed sensing circuit requires a minimum input of 2 volts RMS from a magnetic pickup. The output for remote indication of shutdowns is rated at 1 amp, 30 VDC maximum. The output for an auxiliary starter contactor is also rated 1 amp, 30 VDC maximum.