Protec 6100 User Manual
Protec 6100 is a digital addressable fire alarm control panel that provides reliable and comprehensive fire protection for various premises. It offers advanced features such as multifunction zone status indications, multifunction display, and user-friendly controls, making it an ideal choice for diverse applications. Protec 6100 ensures the safety of occupants and property by promptly detecting and alerting in case of a fire, enabling timely evacuation and emergency response.
PDF
Document
Advertisement
Advertisement

Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND
+44 (0) 1282 717171 www.protec.co.uk [email protected]
6100 SINGLE LOOP DIGITAL
ADDRESSABLE FIRE ALARM
CONTROL PANEL
USER MANUAL
+44 (0) 1282 717171 www.protec.co.uk [email protected]
6100 SINGLE LOOP DIGITAL
ADDRESSABLE FIRE ALARM
CONTROL PANEL
USER MANUAL

N93-571-87 Issue 5 NH Page 2 of 34 © Protec Fire Detection plc 2019
Document Revision Details
Issue Modification Detail Author Date
0 Document Creation NH 15/11/2011
1 Section 14.0 amended, miscellaneous text tidied NH 17/01/2012
2 Refer to ECN3414 NH 10/10/2013
3 Addition of WEEE data in section 1.0 NH 22/06/2014
4 Refer to ECN3729 NH 14/07/2015
5 Update to BS5839 references
Refer to ECN4363 NH 16/05/2019
Document Revision Details
Issue Modification Detail Author Date
0 Document Creation NH 15/11/2011
1 Section 14.0 amended, miscellaneous text tidied NH 17/01/2012
2 Refer to ECN3414 NH 10/10/2013
3 Addition of WEEE data in section 1.0 NH 22/06/2014
4 Refer to ECN3729 NH 14/07/2015
5 Update to BS5839 references
Refer to ECN4363 NH 16/05/2019

N93-571-87 Issue 5 NH Page 3 of 34 © Protec Fire Detection plc 2019
Table of Contents
1.0 INTRODUCTION .................................................................................................................................... 5
2.0 USER RESPONSIBILITIES ................................................................................................................... 6
2.1 Requirements of the Premises Management Named Person ......................................................... 6
3.0 ROUTINE TESTING OF THE SYSTEM ................................................................................................. 7
3.1 Daily Inspection ............................................................................................................................... 7
3.2 Weekly Test ..................................................................................................................................... 7
3.3 Monthly Test .................................................................................................................................... 7
3.4 Periodic Inspection .......................................................................................................................... 7
3.5 Annual Test ..................................................................................................................................... 8
3.6 5 Yearly Test ................................................................................................................................... 8
4.0 6100 ACCESS LEVELS......................................................................................................................... 9
4.1 Access Level 1 ( General User ) ..................................................................................................... 9
4.2 Access Level 2 ( Authorised / Trained User ) .................................................................................. 9
5.0 6100 INDICATIONS AND CONTROLS ............................................................................................... 10
5.1 Multifunction Display ..................................................................................................................... 10
5.2 General Indications ....................................................................................................................... 10
5.3 Multifunction Zone Status Indications ( Row 2, first 16 zones only ) ............................................. 10
5.4 Code Entry and Menu Navigation Keys ........................................................................................ 10
5.5 Sound Alarms, Silence Alarms, Reset Panel and Mute Buzzer keys............................................ 10
6.0 6100 FIRE INDICATIONS .................................................................................................................... 11
6.1 General Fire Indicator Illuminated ................................................................................................. 11
6.2 Multifunction Zone Indicator Flashing Red .................................................................................... 11
7.0 6100 FAULT INDICATIONS ................................................................................................................ 11
7.1 Zone Faults ................................................................................................................................... 11
7.2 System Faults ................................................................................................................................ 11
7.3 Alarm Fault .................................................................................................................................... 11
7.4 Supply Fault .................................................................................................................................. 12
7.5 Aux. Supply Fault .......................................................................................................................... 12
7.6 Repeat Panel Fault ........................................................................................................................ 12
7.7 Fire link Fault ................................................................................................................................. 12
8.0 6100 DISABLEMENT INDICATIONS .................................................................................................. 12
8.1 Zone Disablement ......................................................................................................................... 12
8.2 Alarm Disablement ........................................................................................................................ 12
8.3 Fire Link Disablement .................................................................................................................... 12
9.0 MISCELLANEOUS INDICATIONS ...................................................................................................... 12
9.1 Power on Indication ....................................................................................................................... 12
9.2 Pre Alarm ...................................................................................................................................... 12
9.3 Outputs Delayed ............................................................................................................................ 12
10.0 SYSTEM DELAYS ............................................................................................................................... 13
11.0 COINCIDENCE OPERATION .............................................................................................................. 13
12.0 6100 RESPONSE TO AN ALARM ...................................................................................................... 14
12.1 Automatic Detection ................................................................................................................... 14
12.2 Manual Detection ....................................................................................................................... 14
12.3 Coincidence Activation .............................................................................................................. 14
12.4 Silencing the Alarms .................................................................................................................. 14
Table of Contents
1.0 INTRODUCTION .................................................................................................................................... 5
2.0 USER RESPONSIBILITIES ................................................................................................................... 6
2.1 Requirements of the Premises Management Named Person ......................................................... 6
3.0 ROUTINE TESTING OF THE SYSTEM ................................................................................................. 7
3.1 Daily Inspection ............................................................................................................................... 7
3.2 Weekly Test ..................................................................................................................................... 7
3.3 Monthly Test .................................................................................................................................... 7
3.4 Periodic Inspection .......................................................................................................................... 7
3.5 Annual Test ..................................................................................................................................... 8
3.6 5 Yearly Test ................................................................................................................................... 8
4.0 6100 ACCESS LEVELS......................................................................................................................... 9
4.1 Access Level 1 ( General User ) ..................................................................................................... 9
4.2 Access Level 2 ( Authorised / Trained User ) .................................................................................. 9
5.0 6100 INDICATIONS AND CONTROLS ............................................................................................... 10
5.1 Multifunction Display ..................................................................................................................... 10
5.2 General Indications ....................................................................................................................... 10
5.3 Multifunction Zone Status Indications ( Row 2, first 16 zones only ) ............................................. 10
5.4 Code Entry and Menu Navigation Keys ........................................................................................ 10
5.5 Sound Alarms, Silence Alarms, Reset Panel and Mute Buzzer keys............................................ 10
6.0 6100 FIRE INDICATIONS .................................................................................................................... 11
6.1 General Fire Indicator Illuminated ................................................................................................. 11
6.2 Multifunction Zone Indicator Flashing Red .................................................................................... 11
7.0 6100 FAULT INDICATIONS ................................................................................................................ 11
7.1 Zone Faults ................................................................................................................................... 11
7.2 System Faults ................................................................................................................................ 11
7.3 Alarm Fault .................................................................................................................................... 11
7.4 Supply Fault .................................................................................................................................. 12
7.5 Aux. Supply Fault .......................................................................................................................... 12
7.6 Repeat Panel Fault ........................................................................................................................ 12
7.7 Fire link Fault ................................................................................................................................. 12
8.0 6100 DISABLEMENT INDICATIONS .................................................................................................. 12
8.1 Zone Disablement ......................................................................................................................... 12
8.2 Alarm Disablement ........................................................................................................................ 12
8.3 Fire Link Disablement .................................................................................................................... 12
9.0 MISCELLANEOUS INDICATIONS ...................................................................................................... 12
9.1 Power on Indication ....................................................................................................................... 12
9.2 Pre Alarm ...................................................................................................................................... 12
9.3 Outputs Delayed ............................................................................................................................ 12
10.0 SYSTEM DELAYS ............................................................................................................................... 13
11.0 COINCIDENCE OPERATION .............................................................................................................. 13
12.0 6100 RESPONSE TO AN ALARM ...................................................................................................... 14
12.1 Automatic Detection ................................................................................................................... 14
12.2 Manual Detection ....................................................................................................................... 14
12.3 Coincidence Activation .............................................................................................................. 14
12.4 Silencing the Alarms .................................................................................................................. 14

N93-571-87 Issue 5 NH Page 4 of 34 © Protec Fire Detection plc 2019
12.5 Resetting the 6100 after an Alarm ............................................................................................. 14
12.6 New Zone in Alarm .................................................................................................................... 14
12.7 Activating the Alarms Manually.................................................................................................. 14
13.0 6100 STATUS DISPLAYS ................................................................................................................... 15
13.1 The System Normal Display ...................................................................................................... 15
13.2 The Fault, Disablement and Test Display .................................................................................. 15
13.3 The Fire Alarm Display .............................................................................................................. 16
14.0 6100 USER MENUS............................................................................................................................. 17
14.1 Entering the 6100 Menu System ............................................................................................... 17
14.2 User Menu Structure .................................................................................................................. 17
14.3 Viewing Faults and Disablements.............................................................................................. 18
14.4 Clearing System Faults .............................................................................................................. 19
14.5 Testing the Front Panel Indications ........................................................................................... 19
14.6 Setting a Zone Into Walk Test Mode ......................................................................................... 20
14.7 Disabling a Zone ........................................................................................................................ 20
14.8 Disabling Alarm and Fire Link Outputs ...................................................................................... 21
14.9 Setting the Date and Time ......................................................................................................... 21
14.10 Viewing the Alarm Counter ........................................................................................................ 22
14.11 Viewing the Fire Event Log ........................................................................................................ 22
14.12 Viewing the General Event Log ................................................................................................. 23
14.13 Exiting the Menus ...................................................................................................................... 23
15.0 6100 FIRE BRIGADE PANEL OPERATION (AUSTRALIAN MARKETS) .......................................... 24
15.1 Enable Key ................................................................................................................................ 24
15.2 Silence Buzzer Button ............................................................................................................... 24
15.3 Silence Alarms Button ............................................................................................................... 24
15.4 Reset Button .............................................................................................................................. 24
15.5 Disable Button ........................................................................................................................... 24
16.0 APPENDIX 1 - 6100 SYSTEM SET UP RECORD............................................................................... 25
17.0 APPENDIX 2 - 6100 EVENT LOG ....................................................................................................... 28
18.0 APPENDIX 3 – 6100 OPERATION QUICK REFERENCE GUIDE ...................................................... 33
18.1 Entering Access Level 2 ............................................................................................................ 33
18.2 Returning to Access Level 1 ...................................................................................................... 33
18.3 Muting the Internal Buzzer and accepting Current Faults .......................................................... 33
18.4 Sounding the Alarms ................................................................................................................. 33
18.5 Silencing the Alarms .................................................................................................................. 33
18.6 Resetting the 6100 ..................................................................................................................... 33
18.7 Testing the Indicators and Internal Buzzer ................................................................................ 33
18.8 Setting the Date and Time ......................................................................................................... 33
12.5 Resetting the 6100 after an Alarm ............................................................................................. 14
12.6 New Zone in Alarm .................................................................................................................... 14
12.7 Activating the Alarms Manually.................................................................................................. 14
13.0 6100 STATUS DISPLAYS ................................................................................................................... 15
13.1 The System Normal Display ...................................................................................................... 15
13.2 The Fault, Disablement and Test Display .................................................................................. 15
13.3 The Fire Alarm Display .............................................................................................................. 16
14.0 6100 USER MENUS............................................................................................................................. 17
14.1 Entering the 6100 Menu System ............................................................................................... 17
14.2 User Menu Structure .................................................................................................................. 17
14.3 Viewing Faults and Disablements.............................................................................................. 18
14.4 Clearing System Faults .............................................................................................................. 19
14.5 Testing the Front Panel Indications ........................................................................................... 19
14.6 Setting a Zone Into Walk Test Mode ......................................................................................... 20
14.7 Disabling a Zone ........................................................................................................................ 20
14.8 Disabling Alarm and Fire Link Outputs ...................................................................................... 21
14.9 Setting the Date and Time ......................................................................................................... 21
14.10 Viewing the Alarm Counter ........................................................................................................ 22
14.11 Viewing the Fire Event Log ........................................................................................................ 22
14.12 Viewing the General Event Log ................................................................................................. 23
14.13 Exiting the Menus ...................................................................................................................... 23
15.0 6100 FIRE BRIGADE PANEL OPERATION (AUSTRALIAN MARKETS) .......................................... 24
15.1 Enable Key ................................................................................................................................ 24
15.2 Silence Buzzer Button ............................................................................................................... 24
15.3 Silence Alarms Button ............................................................................................................... 24
15.4 Reset Button .............................................................................................................................. 24
15.5 Disable Button ........................................................................................................................... 24
16.0 APPENDIX 1 - 6100 SYSTEM SET UP RECORD............................................................................... 25
17.0 APPENDIX 2 - 6100 EVENT LOG ....................................................................................................... 28
18.0 APPENDIX 3 – 6100 OPERATION QUICK REFERENCE GUIDE ...................................................... 33
18.1 Entering Access Level 2 ............................................................................................................ 33
18.2 Returning to Access Level 1 ...................................................................................................... 33
18.3 Muting the Internal Buzzer and accepting Current Faults .......................................................... 33
18.4 Sounding the Alarms ................................................................................................................. 33
18.5 Silencing the Alarms .................................................................................................................. 33
18.6 Resetting the 6100 ..................................................................................................................... 33
18.7 Testing the Indicators and Internal Buzzer ................................................................................ 33
18.8 Setting the Date and Time ......................................................................................................... 33






























/

Download
Just a friendly reminder. You can view the document right here. But most importantly, our AI has already read it. It can explain complex things in simple terms, answer your questions in any language, and help you quickly navigate even the longest or most compilcated documents.
Advertisement
Key features
- Multifunction zone status indications for quick identification of zone status
- User-friendly controls and intuitive interface for ease of operation
- Advanced fault indications for efficient troubleshooting
- Fire link fault indication for monitoring remote fire systems
- Multifunction display for clear and concise information
- Comprehensive range of access levels for different user roles
Frequently asked questions
Protec 6100 offers advantages such as reliable fire detection, user-friendly interface, comprehensive fault indications, and tailored access levels for different users.
Multifunction zone status indications provide a clear and quick way to identify the status of each zone, aiding in efficient monitoring and response.
Protec 6100 utilizes advanced detection technology to promptly identify fire incidents and triggers alerts through various indicators and outputs.