User Manual MN032006EN
Effective May 2018
415U Condor-long-range wireless I/O and gateway
Register memory map
Digital output registers (coils)
Address range
0001 – 0008
0009 – 0020
0021 – 0400
0401 – 6000
6001 – 10000
Description
Local DIO1–DIO8 as digital outputs
Spare
Space for locally attached 115s expansion I/O modules. Twenty register per module address, maximum number of modules is 19.
General purpose bit storage used for: Staging area for data concentrator; Fieldbus mappings storage; Force mapping registers
Not Available
Digital input registers (bits)
Address range
10001 – 10008
10009 – 10020
10021 – 10400
10401
10402-10405
10402
10403
10404
10405
10406 – 16000
16001 – 20000
Description
Local DIO1–DIO8 as digital inputs
Set point status from analog inputs 1 through 12
Space for locally attached 115s expansion I/O modules. Twenty register per module address, Maximum number of modules is 19.
Reserved - Used for repeater status indication
Radio hard fault status flags
Radio power amplifier over temperature
Radio general hardware fault
Radio frequency lock error
Antenna VSWR fault
General purpose bit storage used for: Staging area for data concentrator; Fieldbus mappings storage;
Not Available
Input registers (words)
Address range
30001 – 30004
30005
30006
30007
30008
30009 – 30010
30011 – 30012
30013 – 30016
30018 – 30020
30021 - 30400
30401
30402
30403
30404 – 30405
30406
30407 – 30408
Description
Local AI1–AI4 (analog inputs, current mode)
AI1 and AI2: 4–20 mA differential
AI3 and AI4: 4–20 mA sink
Local supply voltage 0–40 V scales to 0-20mA
Local 24 V loop voltage 0–40 V scales to 0-20mA
Local battery voltage 0–40 V scales to 0-20mA
115S supply voltage 0–40 V scales to 0-20mA
Local AI1, AI2, Voltage Mode. 0-24V Scales to 0-24mA.
Local AI3, AI4, Voltage Mode. 0-5V Scales to 0-20mA
Local pulse input rates: PI1–PI4
Spare
Space for locally attached 115s expansion I/O modules. Twenty registers per module address, maximum number of modules is 19.
RSSI: When configured as a Remote, MeshNode, Repeater, or Manual Client, the RSSI of the connected upstream device in (negative)dBm
Connected Time: When configured as a Remote, MeshNode, Repeater, or Manual Client, the time (in hours) that the connection to the upstream device has been made.
Generation Count: When configured as a Remote, MeshNode, Repeater, or Manual Client, the generation count of the connection to the upstream device.
This is the number of times the connection has been lost and re-established
Upstream IP Address: When configured as a Remote, MeshNode, Repeater, or Manual Client, the IP Address of the upstream device.
Most Significant Byte High byte of Register 30404
Second Byte Low byte of Register 30404
Third Byte
Least Significant Byte
High byte of register 30405
Low byte of register 30405
Current Radio Channel for frequency agility
Radio Transmit Frequency (in Hz). 32-bit. Most significant word at lower (odd) address.
68 EATON
www.eaton.com
415U Condor-long-range wireless I/O and gateway
User Manual MN032006EN
Effective May 2018
Address range
30409 – 30410
30411
30412
30413
30414
30415
30416 – 30419
30420 – 30423
30424
30425
30426 – 30490
30491
30494 – 30500
30494
30495
30496
30497
30498
30499
30500
30501 – 32000
32001 - 32255
32256 – 36000
36001 - 36008
36009 – 36040
36041 – 38000
38001 - 38032
38033 – 38040
38041 – 40000
Description
Radio Receive Frequency (in Hz). 32-bit. Most significant word at lower (odd) address. (As for Transmit Frequency)
Module uptime: The time (in hours) that this module has been up and running
Channel Utilization % (average of last 60 seconds)
Background Noise (average of last 60 seconds)
Tx retry % (average of last 60 seconds): The percentage of total transmissions that required at least one retry
Tx failed % (average of last 60 seconds): The percentage of total transmissions that failed to get an acknowledgement after all retries exhausted.
Channel Utilization, Background noise, Tx Retry % and Tx Failed % (average of the last 60 minutes)
Channel Utilization, Background noise, Tx Retry % and Tx Failed % (average of the last 60 hours)
Radio Power Amplifier Temperature. Actual temperature is reading - 100 °C. (-40 °C reads as 60, 25 °C reads as 125, 70 °C reads as 170 etc).
Radio primay connection data rate (Upstream data rate).
Spare - General purpose word storage used for: Staging area for data concentrator; Fieldbus mappings storage;
Logic Engine Execution State:. 0 -> Stopped. 256 -> Running; 32768 -> Overrun
Internal information registers: serial number, firmware version and patch level
First four digits of serial number (Encodes Manufacture Month & Year
Next three digits of serial number (Encodes Manufactured Firmware version)
Remaining four digits of the serial number
First part of Current Firmware version
Second part of Current Firmware version
Third part of Current firmware version
Patch Level of current firmware version
General purpose word storage used for: Staging area for data concentrator; Fieldbus mappings storage;
RSSI List: When configured as an Base, Repeater, or Manual AP. The RSSI of each connected downstream is added to an I/O register according to the last byte of that device’s IP Address. For example, a downstream device with IP Address 192.168.0.199 will have its RSSI stored in I/O register
32000 + 199 = 32199. If no device is connected with that IP address, the corresponding register has the value Zero.
General purpose word storage used for: Staging area for data concentrator; Fieldbus mappings storage;
Local pulsed inputs 1–4, big endian format Most significant word at lower/odd address
Spare space for 32-bit register values
Not Available
Local analog inputs as floating point values. ModScan format (sign + exponent + most significant 7 bits of significant at even/higher addressed location; lower 16 bits of significant at lower/odd addressed location)
(example: Analog input 1 at 12.3 mA gives registers 38001=CCCD, 38002=4144)
Spare space for floating point values
Not Available
Output registers (holding registers)
Address range
40001 – 40002
40003 – 40020
40021 – 40400
40401 – 46000
46001 – 46008
46009 – 46040
46041 – 48000
48001 – 48004
48005 – 48040
48041 Onwards
Description
Local AO1 and AO2:analog outputs
Spare
Space for locally attached 115s expansion I/O modules. Twenty registers per module address, maximum number of modules is 19.
General purpose word storage area used for: Staging area for data concentrator; Fieldbus mappings storage
Local pulsed outputs 1–4. Big endian format. Most significant word at lower/odd address
Spare 32-bit registers
Not Available
Local analog outputs as floating point values. ModScan format (sign + exponent + most significant 7 bits of significant at even/higher addressed location) Lower 16 bits of significant at lower/odd addressed location
(example: Analog output 1 at 12.3 mA gives registers 48001=CCCD, 48002=4144)
Spare space for floating point values
Not available
EATON
www.eaton.com
69