Default System Display screen (shown):

Displays the Shelf output voltage, the

AC input voltage, and the total output current. (Numerically, and with a graphical indication of relative magnitude of system output current level) The screen will also show any active alarm conditions, and the current reading will flash to indicate when the unit is operating at its current limit.

Up/Down Buttons:

Use to scroll through display screens, and to adjust selected settings

Enter Button:

Press to select a screen for adjustment, or to enter a new value after adjustment

Back

X

Button:

Press to return to the previous higher level menu item, or to exit from a setting without making any change

See the complete menu structure in the following diagram. Navigate through the various screens using the up and down arrows, the back button, and the

Enter button.

Note that output voltage and current limit settings apply to the combined output of all installed power modules. The ICM treats the combined modules as a single high power supply. Adjust the system output Voltage and Current Limit

(see System Settings section) to match the battery type and system load requirements if required.

LEVEL 1:

(STATUS)

SYSTEM STATUS

INPUT VOLTAGE

OUTPUT VOLTAGE

OUTPUT CURRENT

ADVANCED OPTIONS

Enter

\/

120V

13.8V

20.0A

\/ Scroll /\

(if installed)

BMM MODULE X

BATT VOLTAGE

BATT CURRENT

BATT SOC

Enter

\/

13.8V

0.0A

100%

\/ Scroll /\

(if installed)

LDM MODULE X

CHANNEL 1 STATUS

CHANNEL 2 STATUS

CHANNEL 3 STATUS

CHANNEL 4 STATUS

Enter

\/

10.0A

5.0A

DISABLED

5.0A

\/ Scroll /\

ALARM INPUTS

ALARM INPUT 1 STATUS TRIGGERED

ALARM INPUT 2 STATUS

ALARM INPUT 3 STATUS

ALARM INPUT 4 STATUS

Enter

READY

READY

READY

\/

\/ Scroll /\

ALARM HISTORY

MODULE #4 ALARM

Battery Breaker Open

Set: 4/20/15 12:33

Clr: 4/21/15 16:05

Enter

\/

\/ Scroll /\

NETWORK STATUS

DEVICE NAME

CONNECTION STATUS

IP ADDRESS

Enter

\/

/\

Back

LEVEL 3:

(SELECT SETTING)

SYSTEM SETTINGS

OUTPUT VOLTAGE

OUTPUT CURRENT

DC OUTPUT ENABLE

Enter

\/

/\

Enter / Back

LEVEL 4:

(ADJUST SETTING)

SET OUTPUT VOLTAGE

/\ 13.8V

\/

13.8V

100A

ON

/\

Back

BMM MODULE X SETTINGS

DISC VOLTAGE 10.5V

RECON VOLTAGE

OVERCURRENT

BAT CAPACITY

BAT RATE

LOW SOC ALARM

TEMP-CO/cell

EQUALISE CHARGE

DISCHARGE TEST

Enter

\/

12.0V

80A

100Ah

10hr

25%

-8mV/C

/\

Enter / Back

SET DISCON VOLTAGE

/\ 10.5V

\/

/\

Back

LDM MODULE X SETTINGS

CHANNEL ENABLE

CHANNEL OVERCURRENT

CHANNEL UNDERCURRENT

Enter

\/

\/

\/ >

/\

Back

>

ALARM HISTORY 1 / 10

MODULE #4 ALARM

Battery Breaker Open

Set: 4/20/15 12:33

Clr: 4/21/15 16:05

/\

Back

ADVANCED OPTIONS

SET LCD PASSWORD

CLEAR LCD PASSWORD

SET LOCKOUT TIMER

RESET COMM SETTINGS

Enter

\/

/\

Enter / Back

SET LCD PASSWORD

/\ 0 * * *

\/

SUB-MENUS: BMM EQUALISE CHARGE

VOLTAGE

DURATION

INTERVAL

STATUS

15.0V

30 min

7 days

READY

BMM DISCHARGE TEST

MAX TIME

STOP VOLTAGE

INTERVAL

STATUS

Enter

\/

60 min

10.5V

30 days

READY

/\

Enter / Back

SET EQUALISE VOLTAGE

/\ 15.0V

\/

LDM MODULE X CHANNEL ENABLE

CHANNEL 1

CHANNEL 2

ON

ON

CHANNEL 3

CHANNEL 4

OFF

ON

LDM MODULE X OVERCURRENT

CHANNEL 1

CHANNEL 2

CHANNEL 3

CHANNEL 4

ON

ON

OFF

ON

LDM MODULE X UNDERCURRENT

CHANNEL 1

CHANNEL 2

CHANNEL 3

ON

ON

OFF

ON CHANNEL 4

Enter

\/

/\

Enter / Back

SET CHANNEL 1

/\ [] Enabled

\/ [] Disabled

Figure 8: ICM Menu Structure