Appendix
A
Supplemental Drive Information
For information on . .
Drive, Fuse & Circuit Breaker Ratings
See page . .
Specifications
Category
Agency
Certification
Specification c
U
L
US
Listed to UL508C and CAN/CSA-C2.2 No. 14-M91.
Marked for all applicable European Directives
(1)
EMC Directive (89/336/EEC)
EN 61800-3 Adjustable Speed electrical power drive systems
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power Installations
Certified to AS/NZS, 1997 Group 1, Class A.
N223
The drive is also designed to meet the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and
Operation of Adjustable Speed Drive Systems.
IEC 146 - International Electrical Code.
(1)
Applied noise impulses may be counted in addition to the standard pulse train causing erroneously high [Pulse Freq] readings.
Category Specification
Protection Drive
AC Input Overvoltage Trip:
AC Input Undervoltage Trip:
Nominal Bus Voltage:
All Drives
247VAC 285VAC 475VAC 570VAC 690VAC
120VAC 138VAC 233VAC 280VAC 345VAC
Bus Overvoltage Trip: 405VDC 405VDC 810VDC 810VDC 1013VDC
Bus Undervoltage Shutoff/Fault: 153VDC 153VDC 305VDC 305VDC 381VDC
281VDC 324VDC 540VDC 648VDC 810VDC
Heat Sink Thermistor:
Drive Overcurrent Trip
Software Overcurrent Trip:
Hardware Overcurrent Trip:
Line transients:
Monitored by microprocessor overtemp trip
200% of rated current (typical)
220-300% of rated current (dependent on drive rating) up to 6000 volts peak per IEEE C62.41-1991
A-2
Supplemental Drive Information
Category
Protection
(continued)
Specification
Control Logic Noise Immunity: Showering arc transients up to 1500V peak
Power Ride-Thru: 15 milliseconds at full load
Logic Control Ride-Thru:
Ground Fault Trip:
Short Circuit Trip:
Environment
Altitude:
Maximum Surrounding Air
Temperature without Derating:
IP20, NEMA Type 1:
0.5 seconds minimum, 2 seconds typical
Phase-to-ground on drive output
Phase-to-phase on drive output
1000 m (3300 ft) max. without derating
0 to 50 degrees C (32 to 122 degrees F), typical. See pages A-8
through
Storage Temperature (all const.): –40 to 70 degrees C (–40 to 158 degrees F)
Atmosphere:
Important:
Drive
must not
be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
Relative Humidity:
Shock:
Vibration:
Sound:
5 to 95% non-condensing
15G peak for 11ms duration (
±
1.0 ms)
0.152 mm (0.006 in.) displacement, 1G peak
Electrical
Voltage Tolerance:
Frequency Tolerance:
Input Phases:
Frame
0
1
2
Fan
Speed
30 CFM
Sound
Level
30 CFM 58 dB
59 dB
Note: Sound pressure level is measured at 2 meters.
3
4
50 CFM 57 dB
120 CFM 61 dB
5
6
190 CFM 59 dB
200 CFM 71 dB
300 CFM 72 dB
See page
C-24 for full power and operating range.
47-63 Hz.
Three-phase input provides full rating for all drives. Single-phase operation provides 50% of rated current.
Control
Displacement Power Factor:
Efficiency:
Maximum Short Circuit Rating: 200,000 Amps symmetrical.
Actual Short Circuit Rating: Determined by AIC rating of installed fuse/circuit breaker.
Method:
0.98 across entire speed range.
97.5% at rated amps, nominal line volts.
Carrier Frequency:
Sine coded PWM with programmable carrier frequency. Ratings apply to all drives (refer to the
Derating Guidelines
in the
PowerFlex Reference Manual). The drive can be supplied as 6 pulse or 12 pulse in a configured package.
2, 4, 8 & 10 kHz. Drive rating based on 4 kHz (see pages
through
Output Voltage Range:
Output Frequency Range:
Frequency Accuracy
Digital Input:
Analog Input:
0 to rated motor voltage
Standard Control – 0 to 400 Hz., Vector Control – 0 to 420 Hz
Within
Within
±
±
0.01% of set output frequency.
0.4% of maximum output frequency.
Supplemental Drive Information
A-3
Category
Control
(continued)
Specification
Frequency Control:
Speed Control:
Torque Regulation:
Selectable Motor Control:
Stop Modes:
Accel/Decel:
Intermittent Overload:
Current Limit Capability:
Encoder
Electronic Motor Overload
Protection:
Type:
Supply:
Quadrature:
Duty Cycle:
Requirements:
Speed Regulation - w/Slip Compensation
(Volts per Hertz Mode)
0.5% of base speed across 40:1 speed range
40:1 operating range
10 rad/sec bandwidth
Speed Regulation - w/Slip Compensation
(Sensorless Vector Mode)
0.5% of base speed across 80:1 speed range
80:1 operating range
20 rad/sec bandwidth
Speed Regulation - w/Feedback
(Sensorless Vector Mode)
0.1% of base speed across 80:1 speed range
80:1 operating range
20 rad/sec bandwidth
Speed Regulation - w/o Feedback
(Vector Control Mode)
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth
Standard
Vector
Standard
Vector
Vector
Vector
Speed Regulation - w/Feedback
(Vector Control Mode)
0.001% of base speed across 120:1 speed range
1000:1 operating range
250 rad/sec bandwidth
Torque Regulation - w/o Feedback
±
10%, 600 rad/sec bandwidth
Torque Regulation - w/Feedback
±
5%, 2500 rad/sec bandwidth
Vector
Vector
Vector
Sensorless Vector with full tuning. Standard V/Hz with full custom capability. PF700 adds Vector Control.
Multiple programmable stop modes including - Ramp, Coast,
DC-Brake, Ramp-to-Hold and S-curve.
Two independently programmable accel and decel times. Each time may be programmed from 0 - 3600 seconds in 0.1 second increments.
110% Overload capability for up to 1 minute
150% Overload capability for up to 3 seconds
Proactive Current Limit programmable from 20 to 160% of rated output current. Independently programmable proportional and integral gain.
Class 10 protection with speed sensitive response. Investigated by U.L. to comply with N.E.C. Article 430. U.L. File E59272, volume 12.
Incremental, dual channel
12V, 250 mA. 12V, 10 mA minimum inputs isolated with differential transmitter, 250 kHz maximum.
90
°, ±
27 degrees at 25 degrees C.
50%, +10%
Encoders must be line driver type, quadrature (dual channel) or pulse (single channel), 8-15V DC output, single-ended or differential and capable of supplying a minimum of 10 mA per channel. Maximum input frequency is 250 kHz. The Encoder
Interface Board accepts 12V DC square-wave with a minimum high state voltage of 7.0V DC (12 volt encoder). Maximum low state voltage is 0.4V DC.
A-4
Supplemental Drive Information
Communication Configurations
Typical Programmable Controller Configurations
Important:
If block transfers are programmed to continuously write information to the drive, care must be taken to properly format the block transfer. If attribute 10 is selected for the block transfer, values will be written only to RAM and will not be saved by the drive. This is the preferred attribute for continuous transfers. If attribute 9 is selected, each program scan will complete a write to the drives non-volatile memory (EEprom). Since the EEprom has a fixed number of allowed writes, continuous block transfers will quickly damage the EEprom. Do Not assign attribute 9 to continuous block transfers. Refer to the individual communications adapter User Manual for additional details.
Supplemental Drive Information
A-5
Logic Command/Status Words
Figure A.1 Logic Command Word
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Command Description
x Stop
0 = Not Stop
1 = Stop x Start
(1)(2)
0 = Not Start
1 = Start x x x x x
Jog
Clear
Faults
0 = Not Jog
1 = Jog
0 = Not Clear Faults
1 = Clear Faults
Direction 00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Present Direction
Local
Control
0 = No Local Control
1 = Local Control x x x x x x x x x
MOP
Increment
0 = Not Increment
1 = Increment
Accel Rate 00 = No Command
01 = Use Accel Time 1
10 = Use Accel Time 2
11 = Use Present Time
Decel Rate 00 = No Command
01 = Use Decel Time 1
10 = Use Decel Time 2
11 = Use Present Time
Reference
Select
(3)
000 = No Command
001 = Ref. 1 (Ref A Select)
010 = Ref. 2 (Ref B Select)
011 = Ref. 3 (Preset 3)
100 = Ref. 4 (Preset 4)
101 = Ref. 5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)
MOP
Decrement
0 = Not Decrement
1 = Decrement
(1)
(2)
(3)
A “0 = Not Stop” condition (logic 0) must first be present before a “1 = Start” condition will start the drive. The Start command acts as a momentary Start command. A “1” will start the drive, but returning to “0” will not stop the drive.
This Start will not function if a digital input (parameters 361-366) is programmed for 2-Wire
Control (option 7, 8 or 9).
This Reference Select will not function if a digital input (parameters 361-366) is programmed for “Speed Sel 1, 2 or 3” (option 15, 16 or 17). Note that Reference Selection is “Exclusive
Ownership” see
[Reference Owner] on page 3-52
.
A-6
Supplemental Drive Information
Figure A.2 Logic Status Word
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x x
Status
x Ready
Active
Command
Direction
Description
0 = Not Ready
1 = Ready
0 = Not Active
1 = Active
0 = Reverse
1 = Forward x Actual
Direction x x x Accel
Decel
Alarm
0 = Reverse
1 = Forward
0 = Not Accelerating
1 = Accelerating
0 = Not Decelerating
1 = Decelerating
0 = No Alarm
1 = Alarm x x x x x x x x x Fault 0 = No Fault
1 = Fault
At Speed 0 = Not At Reference
1 = At Reference
Local
Control
(1)
Reference
Source
000 = Port 0 (TB)
001 = Port 1
010 = Port 2
011 = Port 3
100 = Port 4
101 = Port 5
110 = Reserved
111 = No Local
0000 = Ref A Auto
0001 = Ref B Auto
0010 = Preset 2 Auto
0011 = Preset 3 Auto
0100 = Preset 4 Auto
0101 = Preset 5 Auto
0110 = Preset 6 Auto
0111 = Preset 7 Auto
1000 = Term Blk Manual
1001 = DPI 1 Manual
1010 = DPI 2 Manual
1011 = DPI 3 Manual
1100 = DPI 4 Manual
1101 = DPI 5 Manual
1110 = Reserved
1111 = Jog Ref
(1)
See “Owners” on page 3-50 for further information.
Supplemental Drive Information
A-7
Output Devices
Common mode cores are internal to the drive. For information on output devices such as output contactors, cable terminators and output reactors refer to the
PowerFlex Reference Manual
.
Drive, Fuse & Circuit Breaker Ratings
The tables on the following pages provide drive ratings (including continuous, 1 minute and 3 second) and recommended AC line input fuse and circuit breaker information. Both types of short circuit protection are acceptable for UL and IEC requirements. Sizes listed are the recommended sizes based on 40 degree C and the U.S. N.E.C. Other country, state or local codes may require different ratings.
Fusing
If fuses are chosen as the desired protection method
, refer to the recommended types listed below. If available amp ratings do not match the tables provided, the closest fuse rating that exceeds the drive rating should be chosen.
•
IEC – BS88 (British Standard) Parts 1 & 2
(1)
, EN60269-1, Parts 1 &
2, type gG or equivalent should be used.
•
UL – UL Class CC, T, RK1 or J must be used.
Circuit Breakers
The “non-fuse” listings in the following tables include both circuit breakers (inverse time or instantaneous trip) and 140M Self-Protecting
Motor Starters.
If one of these is chosen as the desired protection method
, the following requirements apply.
•
IEC and UL – Both types of devices are acceptable for IEC and UL installations.
(1)
Typical designations include, but may not be limited to the following; Parts 1 & 2: AC,
AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH.
Table A.A 208 Volt AC Input Protection Devices
(See page A-13 for Notes)
Drive
Catalog
Number
HP
Rating
PWM
Freq. Temp.
ND HD kHz
°
C
208 Volt AC Input
20BB2P2 0 0.5
0.33 4
20BB4P2 0 1 0.75 4
20BB6P8 1 2
20BB9P6 1 3
1.5
2
4
4
20BB015 1 5 3
20BB022 1 7.5
5
20BB028 2 10 7.5
4
20BB042 3 15 10 4
4
4
20BB052 3 20 15 4
20BB070 4 25 20 4
20BB080 4 30 25 4
20BB104 5 40 – 4
– 30 4
20BB130 5 50 – 4
– 40 4
20BB154 6 60 – 4
– 50 4
20BB192 6 75 – 4
– 60 4
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Amps kVA Cont. 1 Min. 3 Sec. Min.
(1)
Max.
(2)
1.9
3.7
6.8
9.5
0.7
2.5
1.3
4.8
2.4
7.8
3.4
11
2.8
5.6
10.4
12.1
15.7
5.7
17.5
19.3
23.0
8.3
25.3
27.8
29.6
10.7 32.2
38
44.5
16.0 48.3
53.1
51.5
17.1 56
72 25.9 78.2
64
93
84.7
30.5 92
113 40.7 120
117
132
84.7
30.5 92
122 44.1 130
138
143
98
167
35.3 104
60.1 177
156
195
141
208
167
50.9 150 225
75.0 221 243
60.1 177 266
175
175
175
266
86
124
156
175
3.8
7.0
13.8
17
26.3
38
50.6
72.5
300
308
308
125
175
125
225
80
90
110
150
20
30
40
60
3
6
10
12
200
300
225
200
275
225
350
125
175
200
250
35
50
70
100
6
10
15
20
300
450
350
125
175
125
225
80
90
110
150
20
30
40
60
3
6
10
12
200
300
225
Non-Time
Delay Fuse
Min.
(1)
Max.
(2)
Circuit
Breaker
(3)
Max.
(8)
Motor
Circuit
Protector
(4)
Max.
(8)
140M Motor Starter with Adjustable Current
Range
(5)(6)
Available Catalog Numbers - 140 . . .
(7)
350
500
400
500
200
300
350
475
70
100
125
175
10
17.5
30
40
500
600
500
150
250
150
250
100
100
150
150
30
30
50
70
3
7
15
15
250
400
250
300
375
300
500
200
300
350
350
70
100
125
175
15
15
30
40
450
600
500
–
–
–
–
–
–
–
–
–
–
–
M-C2E-B25 M-D8E-B25 –
M-C2E-B63 M-D8E-B63 –
M-C2E-C10 M-D8E-C10 M-F8E-C10 –
M-C2E-C16 M-D8E-C16 M-F8E-C16 –
–
–
–
–
M-C2E-C20 M-D8E-C20 M-F8E-C20 –
M-C2E-C25 M-D8E-C25 M-F8E-C25 -CMN-2500
–
–
M-F8E-C32 -CMN-4000
M-F8E-C45 -CMN-6300
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
-CMN-6300
-CMN-9000
-CMN-9000
–
-CMN-9000
–
–
–
–
–
–
Table A.B 240 Volt AC Input Protection Devices
(See page A-13 for Notes)
Drive
Catalog
Number
HP
Rating
PWM
Freq. Temp.
ND HD kHz
°
C
240 Volt AC Input
20BB2P2 0 0.5
0.33 4
20BB4P2 0 1
20BB6P8 1 2
0.75 4
1.5
4
20BB9P6 1 3
20BB015 1 5
2
3
20BB022 1 7.5
5 4
20BB028 2 10 7.5
4
4
4
20BB042 3 15 10 4
20BB052 3 20 15 4
20BB070 4 25 20 4
20BB080 4 30 25 4
20BB104 5 40 –
– 30
4
4
20BB130 5 50 –
– 40
4
4
20BB154 6 60 –
– 50
4
4
20BB192 6 75 –
– 60
4
4
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Amps kVA Cont. 1 Min. 3 Sec. Min.
(1)
Max.
(2)
145
122
180
145
1.7
3.3
5.9
0.7
2.2
1.4
4.2
2.4
6.8
2.4
4.8
9
8.3
3.4
9.6
10.6
13.7
5.7
15.3
16.8
19.9
8.3
22
25.7
10.7 28
24.2
33
38.5
16.0 42
47.7
19.8 52
64.2
26.7 70
73.2
30.5 80
98 40.6 104 115
73 30.5 80 120
122
98
50.7 130
40.6 104
143
156
46.2
63
78
105
60.1 154 169
50.7 130 195
74.9 192 211
60.1 154 231
175
160
175
175
63
80
105
140
231
260
288
308
3.3
6.4
12
14.4
23
33
44
125
100
175
125
50
60
90
100
200
175
225
200
12
20
25
35
3
5
10
225
175
275
225
90
100
150
180
300
275
400
300
20
30
50
60
6
8
15
125
100
175
125
50
60
90
100
200
175
225
200
12
20
25
35
3
5
10
Non-Time
Delay Fuse
Min.
(1)
Max.
(2)
Circuit
Breaker
(3)
Max.
(8)
Motor
Circuit
Protector
(4)
Max.
(8)
140M Motor Starter with Adjustable Current
Range
(5)(6)
Available Catalog Numbers - 140 . . .
(7)
400
300
500
400
150
200
275
300
600
500
600
600
10
15
25
35
60
80
100
150
100
250
150
50
100
100
100
250
250
250
250
15
30
30
50
3
7
15
300
300
375
300
150
200
275
300
450
375
575
450
15
15
25
35
60
80
100
–
–
–
–
–
–
–
–
–
–
–
–
M-C2E-B25 M-D8E-B25 – –
M-C2E-B63 M-D8E-B63 – –
M-C2E-C10 M-D8E-C10 M-F8E-C10 –
M-C2E-C10 M-D8E-C10 M-F8E-C10 –
M-C2E-C16 M-D8E-C16 M-F8E-C16 –
M-C2E-C25 M-D8E-C25 M-F8E-C25 -CMN-2500
– – M-F8E-C32 -CMN-4000
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
M-F8E-C45 -CMN-6300
– -CMN-6300
–
–
–
–
-CMN-9000
-CMN-9000
–
-CMN-9000
–
–
–
–
–
–
Table A.C 400 Volt AC Input Protection Devices
(See page A-13 for Notes)
Drive
Catalog
Number kW
Rating
PWM
Freq. Temp.
ND HD kHz
°
C
400 Volt AC Input
20BC1P3 0 0.37 0.25 4
20BC2P1 0 0.75 0.55 4
20BC3P5 0 1.5
0.75 4
20BC5P0 0 2.2
1.5
4
20BC8P7 0 4 2.2
4
20BC011 0 5.5
4 4
20BC015 1 7.5
5.5
4
20BC022 1 11 7.5
4
20BC030 2 15 11 4
20BC037 2 18.5 15 4
20BC043 3 22 18.5 4
20BC056 3 30 22 4
20BC072 3 37 30 4
20BC085 4 45 –
– 37
4
4
20BC105 5 55 –
– 45
4
4
20BC125 5 55 –
– 45
4
4
20BC140 5 75 –
– 55
4
4
20BC170 6 90 –
– 75
4
4
20BC205 6 110 –
– 90
4
4
20BC260 6 132 –
– 110
2
2
40
40
50
50
50
50
50
50
40
40
40
50
50
50
45
45
50
50
50
50
50
50
50
50
50
50
50
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Amps kVA Cont. 1 Min. 3 Sec. Min.
(1)
Max.
(2)
1.1
1.8
3.2
0.77 1.3
1.3
2.1
2.2
3.5
1.4
2.4
4.5
1.9
3.2
6.0
4.6
7.9
3.2
5.0
5.5
8.7
5.5
9.9
7.5
13.2
10.8
7.5
11.5
13 17.4
14.4
10.0 15.4
17.2
23.1
20.6
14.3 22
28.4
19.7 30
35.0
24.3 37
40.7
28.2 43
53 36.7 56
68.9
47.8 72
81.4
56.4 85
68.9
47.8 72
24.2
33
33
45
56
64
84
94
108
45
60
74
86
112
128
144
199
164
255
199
136
101
164
136
100.5
69.6 105 116
81.4
56.4 85 128
121.1
83.9 125 138
91.9
63.7 96 144
93.9 140
69.6 105
126
103
170
140
154
157
187
210
148 205
126 170
177 260
138 205
220
255
286
308
190
190
255
280
158
170
163
168
289
313
390
410
200
150
250
200
125
110
150
125
250
250
350
250
70
90
110
90
30
35
45
60
6
15
15
20
3
3
6
300
225
375
300
225
175
275
200
450
375
550
450
125
150
200
175
45
60
80
90
3
6
7
10
17.5
25
30
200
150
250
200
125
110
150
125
250
250
350
250
70
90
110
90
30
35
45
60
6
15
15
20
3
3
6
Non-Time
Delay Fuse
Min.
(1)
Max.
(2)
Circuit
Breaker
(3)
Max.
(8)
Motor
Circuit
Protector
(4)
Max.
(8)
400
300
600
550
400
300
500
375
600
600
750
600
200
250
300
275
80
120
125
150
20
30
45
60
6
8
12
400
300
500
400
300
300
375
375
600
500
750
600
200
250
300
300
80
120
125
150
20
30
45
60
15
15
15
250
150
250
250
150
150
250
150
400
250
400
400
100
100
150
100
30
50
50
60
7
15
15
20
3
3
7
140M Motor Starter with Adjustable Current
Range
(5)(6)
Available Catalog Numbers - 140 . . .
(7)
–
–
–
–
–
–
–
–
–
–
–
–
M-C2E-B16 – –
M-C2E-B25 M-D8E-B25 –
M-C2E-B40 M-D8E-B40 –
M-C2E-B63 M-D8E-B63 – –
M-C2E-C10 M-D8E-C10 M-F8E-C10 –
M-C2E-C16 M-D8E-C16 M-F8E-C16 –
M-C2E-C20 M-D8E-C20 M-F8E-C20 –
–
–
–
–
–
–
–
M-C2E-C25 M-D8E-C25 M-F8E-C25 –
– – M-F8E-C32 –
–
–
–
–
M-F8E-C45 –
– –
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Table A.D 480 Volt AC Input Protection Devices
(See page A-13 for Notes)
Drive
Catalog
Number e HP
Rating
PWM
Freq. Temp.
ND HD kHz
°
C
480 Volt AC Input
20BD1P1 0 0.5
0.33 4
20BD2P1 0 1
20BD3P4 0 2
0.75 4
1.5
4
20BD5P0 0 3
20BD8P0 0 5
2
3
20BD011 0 7.5
5 4
20BD014 1 10 7.5
4
4
4
20BD022 1 15 10 4
20BD027 2 20 15 4
20BD034 2 25 20 4
20BD040 3 30 25 4
20BD052 3 40 30 4
20BD065 3 50 40 4
20BD077 4 60 –
– 50
4
4
20BD096 5 75 –
– 60
4
4
20BD125 5 100 –
– 75
4
4
20BD156 6 125 –
– 100
4
4
20BD180 6 150 –
– 125
4
4
20BD248 6 200 –
– 150
2
2
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
40
50
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Amps kVA Cont. 1 Min. 3 Sec. Min.
(1)
Max.
(2)
Non-Time
Delay Fuse
Min.
(1)
Max.
(2)
0.9
1.6
2.6
0.7
1.1
1.4
2.1
2.2
3.4
3.9
6.9
3.2
5.0
5.7
8.0
9.5
7.9
11
12.5
10.4 14
19.9
16.6 22
24.8
20.6 27
31.2
25.9 34
36.7
30.5 40
47.7
39.7 52
59.6
49.6 65
72.3
60.1 77
59.6
49.6 65
147
131
169
147
90.1
74.9 96
72.3
60.1 77
106
116
117 97.6 125 138
90.1
74.9 96 144
233
169
122
109
141
122
194
141
156
125
180
156
248
180
273
270
172
188
198
234
1.2
2.4
4.5
1.6
3.2
6.0
5.5
8.8
7.5
12
12.1
16.5
16.5
22
60
78
85
98
24.2
33
33 44
40.5
54
51 68
80
104
116
130
234
250
270
312
144
154
163
168
372
360
60
80
100
80
25
35
40
50
3
3
4
6
10
15
17.5
200
175
225
200
125
100
150
125
300
225
110
125
170
125
50
60
70
90
10
15
20
30
3
6
8
350
250
400
350
200
170
250
200
550
400
60
80
100
80
25
35
40
50
3
3
4
6
10
15
17.5
200
175
225
200
125
100
150
125
300
225
200
250
300
250
80
100
125
150
20
30
40
50
6
8
12
600
500
600
600
350
300
500
350
700
600
200
250
300
250
80
100
125
150
20
30
40
50
15
15
15
450
375
500
450
350
300
375
350
700
500
Circuit
Breaker
(3)
Max.
(8)
Motor
Circuit
Protector
(4)
Max.
(8)
70
100
100
100
30
50
50
50
7
15
15
20
3
3
7
250
250
250
250
125
100
150
125
400
250
140M Motor Starter with Adjustable Current
Range
(5)(6)
Available Catalog Numbers - 140 . . .
(7)
–
–
–
–
–
–
–
–
–
–
M-C2E-B16 – –
M-C2E-B25 – –
M-C2E-B40 M-D8E-B40 –
M-C2E-B63 M-D8E-B63 – –
M-C2E-C10 M-D8E-C10 M-F8E-C10 –
M-C2E-C16 M-D8E-C16 M-F8E-C16 –
M-C2E-C16 M-D8E-C16 M-F8E-C16 –
–
–
–
–
–
–
–
M-C2E-C25 M-D8E-C25 M-F8E-C25 -CMN-2500
– – M-F8E-C32 -CMN-4000
–
–
–
–
M-F8E-C45 -CMN-4000
M-F8E-C45 -CMN-4000
–
–
–
–
–
–
–
–
-CMN-6300
-CMN-9000
-CMN-9000
-CMN-9000
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
-CMN-9000
–
–
–
–
Table A.E 600 Volt AC Input Protection Devices
(See page A-13 for Notes)
Drive
Catalog
Number
HP
Rating
PWM
Freq. Temp.
ND HD kHz
°
C
600 Volt AC Input
20BE1P7 0 1
20BE2P7 0 2
20BE3P9 0 3
20BE6P1 0 5
2
3
0.5
4
1 4
4
4
20BE9P0 0 7.5
5 4
20BE011 1 10 7.5
4
20BE017 1 15 10 4
20BE022 2 20 15 4
20BE027 2 25 20 4
20BE032 3 30 25 4
20BE041 3 40 30 4
20BE052 3 50 40 4
20BE062 4 60 50 2
20BE077 5 75 – 2
– 60 2
20BE099 5 100 – 2
– 75 2
20BE125 6 125 – 2
– 100 2
20BE144 6 150 – 2
– 125 2
50
50
50
40
50
50
50
50
40
50
50
50
50
50
50
50
50
50
50
50
50
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Amps kVA Cont. 1 Min. 3 Sec. Min.
(1)
Max.
(2)
1.3
2.1
3.0
5.3
1.4
1.7
2.1
2.7
3.1
3.9
5.5
6.1
7.8
9.9
8.1
9
10.2 11
15.4
16.0 17
20.2
21.0 22
24.8
25.7 27
29.4
30.5 32
37.6
39.1 41
47.7
49.6 52
58.2
60.5 62
72.3
75.1 77
58.2
60.5 63
92.9
96.6 99
72.3
75.1 77
117 122 125
116
138
93
135
117
96.6 99
141
122
144
125
149
158
188
2
3.6
4.3
6.7
2.6
4.8
5.9
9.2
9.9
13.5
13.5
18
18.7
25.5
25.5
34
78
85
94
109
33 44
40.5
54
48 64
61.5
82
104
116
126
126
138
188
198
216
250
80
90
90
125
35
40
50
60
100
150
125
175
150
10
15
20
30
6
9
2
3
125
150
125
200
60
70
90
110
175
250
200
300
275
20
25
40
50
4
6
9
12
80
90
90
125
35
40
50
60
100
150
125
175
150
10
15
20
30
6
9
2
3
Non-Time
Delay Fuse
Min.
(1)
Max.
(2)
Circuit
Breaker
(3)
Max.
(8)
Motor
Circuit
Protector
(4)
Max.
(8)
140M Motor Starter with Adjustable Current
Range
(5)(6)
Available Catalog Numbers - 140 . . .
(7)
225
300
250
375
100
125
150
200
300
375
375
400
375
35
40
60
80
6
10
15
20
100
100
100
150
50
50
100
100
100
250
150
250
250
15
15
20
30
3
3
7
15
225
300
250
375
100
125
150
200
300
375
375
400
375
30
40
50
80
15
15
15
20
–
–
–
–
–
–
–
–
–
–
–
–
–
M-C2E-B16 –
M-C2E-B25 –
M-C2E-B40 M-D8E-B40 –
M-C2E-B63 M-D8E-B63 –
–
–
–
–
–
–
M-C2E-C10 M-D8E-C10 M-F8E-C10 –
M-C2E-C10 M-D8E-C10 M-F8E-C10 –
M-C2E-C16 M-D8E-C16 M-F8E-C16 –
M-C2E-C25 M-D8E-C25 M-F8E-C25 -CMN-2500
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
M-F8E-C25 -CMN-2500
M-F8E-C32 -CMN-4000
M-F8E-C45 -CMN-4000
– -CMN-6300
–
–
–
–
–
-CMN-6300
-CMN-9000
-CMN-6300
–
-CMN-9000
–
–
–
–
Table A.F 690 Volt AC Input Protection Devices
Drive
Catalog
Number kW
Rating
ND HD
PWM
Freq.
Temp.
kHz
°
C
690 Volt AC Input
20BF052 5 45 –
–
4
37.5 4
20BF060 5 55 –
– 45
4
4
20BF082 5 75 –
– 55
2
2
20BF098 5 90 –
– 75
2
2
20BF119 6 110 –
– 90
2
2
20BF142 6 132 –
– 110
2
2
50
50
40
40
50
50
50
50
50
50
50
50
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Amps kVA Cont. 1 Min. 3 Sec. Min.
(1)
Max.
(2)
46.9
56.1 52
40.1
48.0 46
57.7
68.9 60
46.9
56.1 52
79.0
94.4 82
57.7
68.9 60
94.7
113 98
79.0
94.4 82
115 137 119 131
94.7
113 98 147
138
115
165
137
142
119
156
179
90
90
108
123
57
69
66
78
123
120
127
140
78
92
90
104
179
196
213
238
200
125
200
200
110
90
125
110
250
200
300
250
100
80
125
100
60
50
80
60
150
125
175
150
Non-Time
Delay Fuse
Min.
(1)
Max.
(2)
375
225
375
375
175
150
225
175
400
375
450
400
100
80
125
100
60
50
80
60
150
125
175
150
Circuit
Breaker
(3)
Max.
(8)
375
225
375
375
175
150
225
175
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Motor
Circuit
Protector
(4)
Max.
(8)
Notes:
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor FLA. Ratings shown are maximum.
(5)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(6)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or
600V Delta/Delta systems.
(7)
The AIC ratings of the Bulletin 140M Motor Protector may vary. See publication 140M-SG001B-EN-P.
(8)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
A-14
Supplemental Drive Information
Table A.G 540 Volt DC Input Protection Devices
Drive
Catalog
Number
540 Volt DC Input kW
Rating
DC Input
Ratings Output Amps
ND HD Amps kW Cont. 1 Min. 3 Sec.
20BC1P3
20BC2P1
20BC3P5
20BC5P0
20BC8P7
20BC011
20BC015
20BC022
20BC030
20BC037
20BC043
20BC056
20BC072
20BC085
20BH105
(1)
20BH125
20BH140
20BH170
Fuse Bussmann Style Fuse
1 0.37 0.25 1.3
1 0.75 0.55 2.1
1 1.5
0.75 3.7
0.7
1.3
1.1
2.1
2.0
3.5
1.4
2.4
4.5
1.9
3.2
6.0
1 2.2
1.5
5.3
1 4 3.0
9.3
2.9
5.0
5.0
8.7
5.5
9.9
7.5
10
13.2
20
1 5.5
4 12.6
6.8
11.5
13 17.4
25
1 7.5
5.5
16.8
9.1
15.4
17.2
23.1
30
3
6
8
1 11 7.5
24 13 22
2 15 11 33.2
17.9
30
2 18.5 15 40.9
22.1
37
3 22 18.5 47.5
25.7
43
3 30 22 61.9
33.4
56
3 37 30 80.5
43.5
72
4 – 37 80.5
43.5
72
45 – 95.1
51.3
85
24.2
33
33
45
56
64
84
108
94
45
60
74
86
112
144
128
110
150
150
200
45
60
80
90
5 – 45 95.1
51.3
85
55 – 117.4
63.4
105
5 – 45 91.9
63.7
96
55 – 139.8
75.5
125
6 – 55 117.4
63.4
105
75 – 158.4
85.6
140
158
154
6 – 75 158.4
85.6
140
90 – 192.4
103.9 170
210
187
128
116
144
138
6 – 90 192.4
103.9 170 255
110 – 232 125.3 205 220
210
210
280
255
170
158
168
163
313
289
200
300
300
350
200
200
150
225
350
400
BUSSMANN_JKS-3
BUSSMANN_JKS-6
BUSSMANN_JKS-8
BUSSMANN_JKS-10
BUSSMANN_JKS-20
BUSSMANN_JKS-25
BUSSMANN_JKS-30
BUSSMANN_JKS-45
BUSSMANN_JKS-60
BUSSMANN_JKS-80
BUSSMANN_JKS-90
BUSSMANN_JKS-110
BUSSMANN_JKS-150
BUSSMANN_JKS-150
BUSSMANN_JKS-200
BUSSMANN_JKS-200
BUSSMANN_JKS-200
BUSSMANN_JKS-225
BUSSMANN_JKS-200
BUSSMANN_JKS-300
BUSSMANN_JKS-300
BUSSMANN_JKS-350
BUSSMANN_JKS-350
BUSSMANN_JKS-400
(1)
Also applies to “P” voltage class.
Table A.H 650 Volt DC Input Protection Devices
Drive
Catalog
Number
650 Volt DC Input kW
Rating
DC Input
Ratings Output Amps
ND HD Amps kW Cont. 1 Min. 3 Sec.
20BD1P1
20BD2P1
20BD3P4
20BD5P0
20BD8P0
20BD011
20BD014
20BD022
20BD027
20BD034
20BD040
20BD052
20BD065
20BR077
(1)
0 0.5
0.33 1.0
0 1 0.75 1.9
0 2
0 3
1.5
2
3.0
4.5
0.6
1.1
1.2
2.1
2.0
3.4
2.9
5.0
0 5 3
0 7.5
5
8.1
5.2
8.0
11.1
7.2
11
1 10 7.5
14.7
9.5
14
1 15 10 23.3
15.1
22
2 20 15 28.9
18.8
27
2 25 20 36.4
23.6
34
3 30 25 42.9
27.8
40
3 40 30 55.7
36.1
52
3 50 40 69.7
45.4
65
4 – 50 67.9
45.4
65
4 60 – 84.5
54.7
77
Fuse Bussmann Style Fuse
1.2
2.4
4.5
5.5
1.6
3.2
6.0
7.5
8.8
12 15
12.1
16.5
20
16.5
22
24.2
33
30
45
6
6
6
10
78
98
85
33 44
40.5
54
51
60
68
80
104
130
116
60
70
80
100
150
150
150
BUSSMANN_JKS-6
BUSSMANN_JKS-6
BUSSMANN_JKS-6
BUSSMANN_JKS-10
BUSSMANN_JKS-15
BUSSMANN_JKS-20
BUSSMANN_JKS-30
BUSSMANN_JKS-45
BUSSMANN_JKS-60
BUSSMANN_JKS-70
BUSSMANN_JKS-80
BUSSMANN_JKS-100
BUSSMANN_JKS-150
BUSSMANN_JKS-150
BUSSMANN_JKS-150
Supplemental Drive Information
A-15
Drive
Catalog
Number
20BR096
20BR125
20BR156
20BR180
kW
Rating
DC Input
Ratings Output Amps
ND HD Amps kW Cont. 1 Min. 3 Sec.
5 – 60 84.5
54.7
77 116 154
75 –
5 – 75
105.3
105.3
68.3
68.3
96
96
100 –
6 – 100
137.1
137.1
88.9
88.9
125
125
125 –
6 – 125
171.2
171.2
110.9 156
110.9 156
150 – 204.1
132.2 180
106
144
138
188
172
234
198
144
168
163
250
234
312
270
Fuse Bussmann Style Fuse
150 BUSSMANN_JKS-150
200
200
250
250
300
300
400
BUSSMANN_JKS-200
BUSSMANN_JKS-200
BUSSMANN_JKS-250
BUSSMANN_JKS-250
BUSSMANN_JKS-300
BUSSMANN_JKS-300
BUSSMANN_JKS-400
(1)
Also applies to “J” voltage class.
Dimensions
Figure A.3 PowerFlex 700 Frames 0-3
(0 Frame Shown)
15.0 (0.59)
5.8 (0.23) dia.
A
D see below
C
B
E
CAUTION
HOT surfaces can cause severe burns
8.0
(0.31)
5.5 (0.22) - Frames 0-1
7.0 (0.28) - Frames 2-3
3 Places
Dimensions are in millimeters and (inches)
.
Weight
(2)
kg (lbs.)
A B C D E Drive
Drive &
Packaging
0 110.0 (4.33) 336.0 (13.23) 200.0 (7.87) 80.0 (3.15) 320.0 (12.60) 5.22 (11.5) 8.16 (18)
1 135.0 (5.31) 336.0 (13.23) 200.0 (7.87) 105.0 (4.13) 320.0 (12.60) 7.03 (15.5) 9.98 (22)
2 222.0 (8.74) 342.5 (13.48) 200.0 (7.87) 192.0 (7.56) 320.0 (12.60) 12.52 (27.6) 15.20 (33.5)
3 222.0 (8.74) 517.5 (20.37) 200.0 (7.87) 192.0 (7.56) 500.0 (19.69) 18.55 (40.9) 22.68 (50)
(1)
(2)
Weights include HIM and Standard I/O.
A-16
Supplemental Drive Information
Figure A.4 PowerFlex 700 Frame 4
15.0 (0.59)
7.0 (0.28) dia.
A
D
C
B
E
8.0
(0.31)
Lifting Holes
4 Places
7.0 (0.28)
3 Places
Dimensions are in millimeters and (inches)
Approx. Weight
(2)
kg (lbs.)
A
(Max.)
B C
(Max.)
D E Drive
Drive &
Packaging
4 220.0 (8.66) 758.8 (29.87) 201.7 (7.94) 192.0 (7.56) 738.2 (29.06) 24.49 (54.0) 29.03 (64.0)
(1)
(2)
Refer to
Weights include HIM and Standard I/O.
Supplemental Drive Information
A-17
Figure A.5 PowerFlex 700 Frame 5
37.6 (1.48)
A
259.1 (10.20)
D
6.5 (0.26)
Detail
15.0 (0.59)
C
B
E
CAUTION
HOT surfaces can cause severe burns
6.5 (0.26)
12.5
(0.49)
Dimensions are in millimeters and (inches)
.
Lifting Holes - 4 Places
12.7 (0.50) Dia.
A
(Max.)
B
5 308.9 (12.16) 644.5 (25.37)
(3)
Approx. Weight
(2)
kg (lbs.)
C
(Max.)
D E Drive
Drive &
Packaging
275.4 (10.84) 225.0 (8.86) 625.0 (24.61) 37.19 (82.0) 42.18 (93.0)
(1)
(2)
(3)
Weights include HIM and Standard I/O.
When using the supplied junction box (100 HP drives Only), add an additional 45.1 mm (1.78 in.) to this dimension.
A-18
Supplemental Drive Information
Figure A.6 PowerFlex 700 Frame 6
49.6 (1.95)
A
360.6 (14.20)
D
Detail
8.5 (0.33)
18.0 (0.71)
C
B
E
126.3
(4.97)
8.5 (0.33)
13.5 (0.53)
Lifting Holes
4 Places
12.7 (0.50) Dia.
Dimensions are in millimeters and (inches)
A
(Max.)
B C
(Max.)
D E
Approx. Weight
(2)
kg (lbs.)
Drive
6 403.9 (15.90) 850.0 (33.46) 275.5 (10.85) 300.0 (11.81) 825.0 (32.48) 71.44 (157.5)
(3)
Drive &
Packaging
91.85 (202.5)
(1)
(2)
(3)
Refer to
Weights include HIM and Standard I/O.
Add an additional 3.6 kg (8.00 lbs.) for 200 HP drives.
Supplemental Drive Information
A-19
Figure A.7 PowerFlex 700 Bottom View Dimensions
Frame Rating Dimensions
0
All
96.0 (3.78)
75.0 (2.95)
55.0 (2.17)
35.0 (1.38)
22.2 (0.87) Dia. – 4 Places
30.2
(1.19)
187.5
(7.38)
132.9
(5.23)
185.0
(7.28)
1
All
2
All
41.9 (1.65)
56.1 (2.21)
75.9 (2.99)
96.0 (3.78)
108.5 (4.27)
87.5 (3.44)
67.5 (2.66)
47.5 (1.87)
28.6 (1.13) Dia.
25.5
(1.00)
187.6
(7.39)
133.3
(5.25)
43.0 (1.69)
70.0 (2.76)
75.9 (2.99)
96.0 (3.78)
167.5 (6.59)
156.9 (6.18)
22.4 (0.88) Dia.
2 Places
22.2 (0.87) Dia.
3 Places
162.3
(6.39)
185.1
(7.29)
28.7 (1.13) Dia.
3 Places
184.8
(7.28)
157.5
(6.20)
150.9
(5.94)
112.1
(4.41)
39.3 (1.55)
57.2 (2.25)
72.7 (2.86)
106.0 (4.17)
139.4 (5.49)
177.4 (6.98)
A-20
Supplemental Drive Information
Frame Rating Dimensions
3
All
except
50 HP,
480V
(37 kW,
400V)
22.2 (0.87) Dia.
28.7 (1.13) Dia.
2 Places
165.1
(6.50)
151.1
(5.95)
127.7
(5.03)
105.3 (4.15)
94.7 (3.73)
37.3 (1.47) Dia.
2 Places
160.1
(6.30)
184.5
(7.26)
4
50 HP,
480V
(37 kW,
400V)
Normal
Duty
Drive
All
22.7 (0.89)
29.0 (1.14)
66.0 (2.60)
97.0 (3.82)
137.2 (5.40)
187.0 (7.36)
105.3 (4.15)
94.7 (3.73)
28.7 (1.13) Dia.
2 Places
34.9 (1.37) Dia.
2 Places
46.7 (1.84) Dia.
2 Places
165.1
(6.50)
160.1
(6.30)
184.5
(7.26)
127.7
(5.03)
Vent Plate
22.7 (0.89)
29.0 (1.14)
66.0 (2.60)
130.0 (5.12)
186.0 (7.32)
22.2 (0.87) Dia.
76.0 (2.99)
65.3 (2.57)
28.7 (1.13) Dia.
2 Places
47.0 (1.85) Dia.
2 Places
54.1 (2.13) Dia.
2 Places
189.7
(7.47)
177.9
(7.00)
157.9
(6.21)
141.9
(5.59)
105.1
(4.14)
26.8 (1.06)
36.8 (1.45)
50.7 (2.00)
63.8 (2.51)
112.0 (4.41)
180.0 (7.09)
Supplemental Drive Information
A-21
Frame Rating Dimensions
5
75 HP,
480V
(55kW,
400V)
Normal
Duty
Drive
241.9
(9.52)
229.5
(9.04)
220.0
(8.66)
184.0
(7.24)
159.5
(6.28)
96.0
(3.78)
104.0 (4.09)
93.2 (3.67)
100 HP,
480V
Normal
Duty
Drive
34.9 (1.37) Dia.
2 Places
22.2 (0.87) Dia.
2 Places
62.7 (2.47) Dia.
2 Places
28.0 (1.10)
45.0 (1.77)
42.6 (1.68)
31.9 (1.26)
85.0 (3.35)
150.0 (5.91)
215.0 (8.46)
255.0 (10.04)
34.9 (1.37) Dia.
22.2 (0.87) Dia.
2 Places
62.7 (2.47) Dia.
2 Places
Removable Junction Box
241.9
(9.52)
223.5
(8.80)
188.5
(7.42)
184.3
(7.26)
153.5
(6.04)
96.0
(3.78)
28.0 (1.10)
44.0 (1.73)
66.4 (2.61)
128.0 (5.04)
232.3 (9.15)
A-22
Supplemental Drive Information
Frame Rating Dimensions
6
All
56.2 (2.21)
45.6 (1.80)
34.9 (1.37) Dia.
3 Places
62.7 (2.47) Dia.
3 Places
22.2 (0.87) Dia.
4 Places
Removable Junction Box
242.0
(9.53)
222.3
(8.75)
148.5
(5.85)
116.6
(4.59)
47.1 (1.85)
52.1 (2.05)
69.1 (2.72)
130.1 (5.12)
230.1 (9.06)
280.1 (11.03)
330.1 (13.00)
151.8
(5.98)
185.4
(7.30)
219.0
(8.62)
Frame Cross Reference
Table A.I PowerFlex 700 Frames
AC Input
208/240 400V 480V 600V
DC Input
540V 650V
ND HP HD HP ND kW HD kW ND HP HD HP ND HP HD HP ND HP HD HP ND HP HD HP
5
7.5
2
10
–
3
15
20
–
4
25
0
0.5
1
–
–
1
2
3
–
–
30
5
40
50
6
60
75
–
10
15
–
20
3
5
7.5
–
–
–
1.5
2
–
–
0.33
0.75
25
30
40
50
60
–
22
30
37
45
–
–
15
18.5
4
5.5
7.5
11
0.37
0.75
1.5
2.2
–
55
–
75
90
110
–
–
11
15
18.5
22
30
37
2.2
4
5.5
7.5
0.25
0.55
0.75
1.5
–
45
–
55
75
90
30
40
50
60
–
–
20
25
5
7.5
10
15
2
3
0.5
1
–
75
100
125
150
–
25
30
40
50
–
–
15
20
3
5
7.5
10
0.33
0.75
1.5
2
–
60
75
100
125
–
30
40
50
60
–
–
20
25
–
–
10
15
–
–
–
–
–
–
–
75
100
–
25
30
40
50
–
–
15
20
–
–
7.5
10
–
–
–
–
–
–
–
60
75
–
22
30
37
45
–
–
15
18.5
4
5.5
7.5
11
0.37
0.75
1.5
2.2
–
55
–
75
90
110
–
–
11
15
18.5
22
30
37
2.2
4
5.5
7.5
0.25
0.55
0.75
1.5
–
45
–
55
75
90
30
40
50
60
–
–
20
25
5
7.5
10
15
2
3
0.5
1
–
75
100
125
150
–
25
30
40
50
–
–
15
20
3
5
7.5
10
0.33
0.75
1.5
2
–
60
75
100
125
–
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 9 Overview
- 9 Who Should Use this Manual?
- 9 What Is Not in this Manual
- 10 Reference Materials
- 10 Manual Conventions
- 11 Drive Frame Sizes
- 11 General Precautions
- 12 Catalog Number Explanation
- 15 Installation/Wiring
- 15 Opening the Cover
- 16 Mounting Considerations
- 16 AC Supply Source Considerations
- 18 General Grounding Requirements
- 19 Fuses and Circuit Breakers
- 19 Power Wiring
- 26 Using Input/Output Contactors
- 27 Disconnecting MOVs and Common Mode Capacitors
- 29 I/O Wiring
- 36 Reference Control
- 37 Auto/Manual Examples
- 38 Lifting/Torque Proving
- 38 Common Bus/Precharge Notes
- 39 EMC Instructions
- 41 Start Up
- 41 Prepare For Drive Start-Up
- 42 Status Indicators
- 43 Start-Up Routines
- 44 Running S.M.A.R.T. Start
- 44 Running an Assisted Start Up
- 45 Programming and Parameters
- 45 About Parameters
- 47 How Parameters are Organized
- 56 Monitor File
- 58 Motor Control File
- 65 Speed Command File
- 75 Dynamic Control File
- 82 Utility File
- 93 Communication File
- 97 Inputs & Outputs File
- 103 Applications File
- 105 Parameter Cross Reference - by Name
- 108 Parameter Cross Reference - by Number
- 111 Troubleshooting
- 111 Faults and Alarms
- 112 Drive Status
- 114 Manually Clearing Faults
- 114 Fault Descriptions
- 119 Clearing Alarms
- 120 Alarm Descriptions
- 123 Common Symptoms and Corrective Actions
- 126 Testpoint Codes and Functions
- 127 Supplemental Drive Information
- 127 Specifications
- 130 Communication Configurations
- 133 Output Devices
- 133 Drive, Fuse & Circuit Breaker Ratings
- 141 Dimensions
- 148 Frame Cross Reference
- 149 HIM Overview
- 149 External and Internal Connections
- 150 LCD Display Elements
- 150 ALT Functions
- 151 Menu Structure
- 153 Viewing and Editing Parameters
- 154 Linking Parameters (Vector Control Option Only)
- 156 Removing/Installing the HIM
- 157 Application Notes
- 157 External Brake Resistor
- 158 Lifting/Torque Proving
- 163 Minimum Speed
- 164 Motor Control Technology
- 166 Motor Overload
- 167 Overspeed
- 168 Power Loss Ride Through
- 169 Process PI for Standard Control
- 172 Reverse Speed Limit
- 173 Skip Frequency
- 175 Sleep Wake Mode
- 177 Start At PowerUp
- 178 Stop Mode
- 180 Voltage Tolerance
- 183 Numerics
- 183 A
- 184 B-D
- 185 E-F
- 187 G-J
- 188 K-O
- 189 P
- 192 R
- 193 S
- 194 T-Z