1.3 LOCATIONS OF CONTROLS. Friedrich HQ-2051SH, KP05A10 KP06A10, KP06A10

Add to My manuals
27 Pages

advertisement

1.3 LOCATIONS OF CONTROLS. Friedrich HQ-2051SH, KP05A10 KP06A10, KP06A10 | Manualzz

1.3 LOCATIONS OF CONTROLS

LOW

FAN

HIGH

OFF

COOL

HIGH

LOW

FA

N

OFF

Off — Turns air conditioner off.

High Fan — High speed fan operation without cooling.

Low Fan — Low speed fan operation without cooling.

High Cool — Cooling with high speed fan operation.

Low Cool — Cooling with low speed fan operation.

3

THERMOSTAT

5 6

4 7

8

C

O

O

2 9

1

10

3

TEMP CONTROL

5

6

4

7

C

O

O

8

E

L

R

2

9

1 10

This automatically controls the temperature of the indoor air.

Turn the knob so that the arrow points to the larger marks for greater cooling. Point the arrow to the smaller marks for more moderate cooling.

(i.e. the higher the number, the greater the cooling)

CAUTION : After switching the air conditioner from Cool to Off or Fan, wait at least 3 minutes before switching it back to Cool.

1.4 SAFETY PRECAUTIONS

1. When servicing, set the ROTARY SWITCH to

Off and unplug the power cord.

2. Observe the original lead dress.

If a short circuit is found, replace all parts which have been overheated or damaged by the short circuit.

3. After servicing, make an insulation resistance test to prevent the customer's exposure to shock hazards.

1.5 INSULATION RESISTANCE TEST

1. Unplug the power cord and connect a jumper between 2 pins (black and white).

2. The grounding conductor (green or green and yellow) is to be open.

3. Measure the resistance value with an ohm meter between the jumpered lead and each exposed metallic part on the equipment at all positions

[except Off] of the ROTARY SWITCH.

4. The value should be over 1 M

.

—4—