- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- Best Power
- Unity/I UT3K
- Installation manual
Appendix: External Bypass Switches. Best Power Unity/I UT3K
Add to My manuals34 Pages
Best Power Unity/I UT3K uninterruptible power system (UPS) safeguards your equipment from power disturbances by providing clean, reliable power. With its advanced technology, the UT3K offers superior protection for critical applications, ensuring uninterrupted operation during power outages, voltage fluctuations, and other electrical disturbances. Trust the UT3K to keep your systems up and running, preventing costly downtime and data loss.
advertisement
Appendix: External Bypass Switches
If your UPS does not have output receptacles, you may have an external UPS Bypass Switch with an
AC Line Disconnect Switch. Figure 3 on page 5 shows a Best Power bypass switch.
The UPS Bypass Switch has three positions: Line, Off, and UPS (see Table 13).
Table 13: External Bypass Switch Positions
UPS Bypass Switch Position
LINE
OFF
UPS
Explanation
Connects AC input power (line) directly to the load equipment.
Disconnects the load equipment from both UPS output power and AC input power (line).
Connects the UPS output to the load equipment.
NOTE: In all three UPS Bypass Switch positions, AC input power may still be connected to the input terminals inside the UPS. To disconnect AC input power to the UPS, you must use the AC
Line Disconnect Switch.
An external bypass switch may be “Make-Before-Break” (MBB) or “Break-Before-Make” (BBM).
• A Make-Before-Break (MBB) switch makes a new connection before it breaks the present connection. If you turn the switch from “UPS” to “Line,” the bypass switch connects the load equipment to AC input power before disconnecting the equipment from UPS output power. In other words, there is no break in power to the load equipment during the switch from UPS output power to AC input power.
• A Break-Before-Make (BBM) switch breaks the present connection before it makes the new one. When you turn the switch from “UPS” to “Line,” the switch moves through the “Off” position. The bypass switch disconnects the load equipment from UPS output power before connecting it to AC input power.
CAUTION!
Before switching an external make-before-break (MBB) bypass switch, the BYPASS light on the
UPS front panel must be lit. If you operate an external MBB bypass switch while the UPS is operating on line power or on battery power, equipment damage may result. Refer to Best Power publication TIP 410 for proper bypass switch operating instructions.
For external bypass switch models and ratings, see Section 101 .
For external bypass switch dimensions, see Section 102 .
29
advertisement
Related manuals
advertisement
Table of contents
- 7 Section 100 Before Installing the UPS
- 7 101 Pre-Installation Check
- 9 102 Equipment Dimensions
- 11 103 Finding a Location for the UPS
- 13 Section 200 Starting the AC Installation
- 13 201 Positioning the Equipment
- 13 202 Sizing the Overcurrent Protection Devices and Wires
- 16 Section 300 AC Installation
- 16 301 Removing the Covers and Knock Outs
- 17 302 Installing the Conduit and Wiring
- 29 303 Installing the Overcurrent Protection Devices
- 30 304 Voltage and Phase Check
- 33 Section 400 Additional Requirements
- 34 Appendix: External Bypass Switches