INSTALLATION. Johnson Controls W)036 THRU 060, B1HA036, B1HA048, B1HA060, B1HA042

Add to My manuals
20 Pages

advertisement

INSTALLATION. Johnson Controls W)036 THRU 060, B1HA036, B1HA048, B1HA060, B1HA042 | Manualzz

341849-YIM-A-0108

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the following national and local safety codes.

1.

National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions).

2.

Local plumbing and waste water codes and other applicable local codes.

Refer to Table 1 for unit application data and to Table 4 for electric heat application data.

If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and/or the customer's expense.

Size of unit for proposed installation should be based on heat loss/heat gain calculations made in accordance with industry recognized procedures identified by the Air Conditioning Contractors of America.

TABLE 1: Unit Application Data

Voltage Variation,

Min./Max.

1

208/230 V

2

460 V

575 V

Wet Bulb Temperature ( ° F) of Air on

Evaporator Coil, Min./Max.

Dry Bulb Temperature ( ° F) of Air on

Condenser Coil, Min.

3

/Max.

187/253

414/504

518/630

57/72

45/120

1. Rated in accordance with ARI Standard 110, utilization range “A”.

2. “T1" transformer primary tap must be moved from the 230 volt connection to the 208 volt connection for low voltage applications of 208 volt and below.

3. A low ambient accessory is available for operation down to

0°F.

LOCATION

Use the following guidelines to select a suitable location for these units.

1.

Unit is designed for outdoor installation only.

2.

Condenser must have an unlimited supply of air.

Where a choice of location is possible, position unit on either north or east side of building.

3.

For ground level installation, a level pad or slab should be used. The thickness and size of the pad or slab used should meet local codes and unit weight. Do not tie the slab to the building foundation.

4.

For roof top installation, be sure the structure will support the weight of the unit plus any field installed components. Unit must be installed on a level roof curb or appropriate angle iron frame providing adequate support under the compressor/ condenser section.

5.

Maintain level tolerance of unit to 1/8" maximum.

RIGGING AND HANDLING

Care must be exercised when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig unit with slings placed under the unit.

Spreader bars of sufficient length should be used across the top of the unit.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS

WEIGHT IS DISTRIBUTED EQUALLY ON THE

CABLES SO THAT IT WILL LIFT EVENLY.

Units may also be moved or lifted with a fork-lift. Slotted openings in the skid are provided for this purpose.

Forks must pass completely through the base.

Refer to Table 2 for unit weights and to Figure 1 for approximate center of gravity.

TABLE 2: Unit Dimensions

Size

036

042

048

060

Shipping

Weight

(lbs.)

367

394

445

490

Operating

Weight

(lbs.)

362

389

440

485

Dimensions

“A” “B” “C” “D”

100

107

121

133

96

103

117

129

84

90

102

112

87

93

105

116

“D”

FRONT

OF

UNIT

“A”

CENTER OF GRAVITY

“C”

“B”

49 1/8

25

22 49 1/4

FIGURE 1 - Center of Gravity

CLEARANCES

All units require certain clearances for proper operation

and service. Refer to Figure 4 for the clearances

required for construction, servicing and proper unit operation.

Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlets.

4 Johnson Controls Unitary Products

341849-YIM-A-0108

DUCTWORK

These units are adaptable to downflow use as well as rear supply and return air duct openings. To convert to downflow, use the following steps:

1.

Remove the duct covers found in the bottom return and supply air duct openings. There are four (4) screws securing each duct cover (save these screws to use later).

2.

Install the duct covers, removed in step one, to the rear supply and return air duct openings. Secure with the four (4) screws used in step one.

3.

Seal duct covers with silicone caulk.

Downflow units must have an “L”-shaped supply duct without any outlets or registers located below the outlet of the unit.

Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of

America (ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not preclude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to minimize the transmission of noise.

When fastening ductwork to side duct flanges on unit, insert screws through duct flanges only. DO NOT insert screws through casing.

Outdoor ductwork must be insulated and waterproofed.

NOTE: Be sure to note supply and return openings.

Refer to Figure 4 for information concerning rear and

bottom supply and return air duct openings.

FILTERS

A filter rack and high velocity filters are standard on three phase units.

Filters must always be used and must be kept clean.

When filters become dirt laden, insufficient air will be delivered by the blower, decreasing your units efficiency and increasing operating costs and wear-andtear on the unit and controls.

Filters should be checked monthly especially since this unit is used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is required to be installed in the condensate drain. The plumbing must conform to local codes. Use a sealing compound on male pipe threads.

Install the condensate drain line (3/4“ NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the following removable panels:

• Blower service access

• Electrical/Filter access

• Compressor service access

Refer to Figure 4 for location of these access panels

and minimum clearances.

THERMOSTAT

The room thermostat should be located on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with the thermostat for general installation procedure. Six color coded insulated wires

(minimum #18 AWG) should be used to connect ther-

mostat to unit. See Figure 2.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the current N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.E.C./C.E.C. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on

the unit Rating Plate and Table 4.

The wiring entering the cabinet must be provided with mechanical strain relief.

A fused disconnect switch should be field provided for the unit. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram.

Electrical line must be sized properly to carry the load.

Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.

Refer to Figure 2 for typical field wiring and to the

appropriate unit wiring diagram for control circuit and power wiring information.

Johnson Controls Unitary Products 5

341849-YIM-A-0108

COMPRESSORS

Units are shipped with compressor mountings factoryadjusted for shipping.

Loosen compressor bolts half turn before operating unit.

CONTROL WIRING

THERMOSTAT

** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire.

**

UNIT TERMINAL STRIP

NOTE:

HEAT ANTICIPATOR

SHOULD BE SET AT 0.25

AMPS FOR ALL MODELS.

*

24 VOLT TRANSFORMER

PROGRAMMABLE

THERMOSTAT ONLY

* = Only required on units with supplemental electric heat.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

POWER WIRING

REFER TO ELECTRICAL DATA

TABLES TO SIZE THE

DISCONNECT SWITCH,

WIRING & OVERCURRENT

PROTECTION.

FIGURE 2 - Typical Field Wiring DIagram

TABLE 3: Physical Data

Indoor

Blower

Indoor

Coil

Outdoor

Fan

Outdoor

Coil

Charge

Filter

Compressor

Models

Centrifugal Blower (Dia. X Wd. In.)

Fan Motor Hp

Rows Deep

Fins Per Inch

Face Area (Sq. Ft.)

Propeller Dia. (In.)

Fan Motor Hp

Nom. CFM Total

Rows Deep

Fins Per Inch

Face Area (Sq. Ft.)

Refrigerant 22 (Lbs./oz.)

Face Area (Sq. Ft./qty./size)

Hermetic Type, (Qty. = 1)

1/4

2,400

1

20

11.7

5/5

036

10 x 8

3/4

3

15

4.38

22

Scroll

BHA

042

11 x 10

3/4

3

15

4.38

22

1/4

2,400

1

20

1/4

2,800

1

16

11.7

6/0

16.4

9/0

4.28/2/14" x 22"

Recip.

Scroll

048

11 x 10

3/4

3

16

5.62

22

060

11 x 10

1

3

16

5.62

22

1/4

2,800

1

20

16.4

10/0

Scroll

6 Johnson Controls Unitary Products

341849-YIM-A-0108

TABLE 4: Electrical Data (Heat Pump / Electric Heat)

Size

036

042

048

060

036

042

048

060

036

042

048

060

Volt

208/230-3-60

208/230-3-60

208/230-3-60

208/230-3-60

460-3-60

460-3-60

460-3-60

460-3-60

575-3-60

575-3-60

575-3-60

575-3-60

Compressors

(each)

RLA LRA

OD Fan

Motors

(each)

FLA

10.9

78.0

12.8

88.0

14.1

105.0

16.0

125.0

5.8

5.8

7.1

8.0

4.5

5.8

5.6

6.4

40.0

42.0

55.0

67.0

32.0

44.0

44.0

50.0

1.1

1.1

1.5

1.5

0.6

0.6

0.8

0.8

0.4

0.4

0.6

0.6

Supply

Blower

Motor

FLA

3.5

3.5

4.0

7.0

1.8

1.8

2.0

3.5

1.5

1.5

1.6

2.8

Model

2NH04501025

2NH04501525

2NH04501025

2NH04501525

2NP04501025

2NP04501525

2NP04502025

2NH04502525

2NH04501025

2NH04501525

2NH04502025

2NH04502525

2NH04501046

2NH04501546

2NH04501046

2NH04501546

2NP04501046

2NH04501546

2NH04502046

2NH04502546

2NH04501046

2NH04501546

2NP04502046

2NP04502546

2NH04501058

2NH04501558

2NH04501058

2NH04501558

2NH04501058

2NH04501558

2NH04502058

2NH04502558

2NH04501058

2NH04501558

2NP04502058

2NP04502558

Electric Heat Option

1

1

1

1

1

2

2

2

1

1

2

1

1

1

1

2

1

1

2

1

2

2

1

1

2

2

2

1

1

2

1

Stages

1

1

1

1

1

10.0

15.0

5

5

10.0

5

15.0

5

10.0

5

15.0

5

20.0

5

25.0

5

10.0

5

15.0

5

20.0

5

25.0

5

10.0

15.0

4

4

10.0

4

15.0

4

10.0

4

15.0

4

20.0

4

25.0

4

10.0

4

15.0

4

20.0

4

25.0

4

kW

7.5/10.0

3

11.3/15.0

3

7.5/10.0

3

11.3/15.0

3

7.5/10.0

3

11.3/15.0

3

15.0/20.0

3

18.8/25.0

3

7.5/10.0

3

11.3/15.0

3

15.0/20.0

3

18.8/25.0

3

24.1

30.1

9.6

14.4

9.6

14.4

9.6

12.0

18.0

12.0

18.0

24.1

30.1

12.0

18.0

MCA

(Amps)

Amps

20.8/24.1

31.3/36.1

20.8/24.1

31.3/36.1

20.8/24.1

44.3/48.3

57.3/63.3

46.9/50.7

59.7/65.7

49.2/53.2

31.3/36.1

41.7/48.1

52.1/60.1

20.8/24.1

31.3/36.1

62.2/68.2

75.3/83.3

88.3/98.3

54.6/58.6

67.6/73.6

41.7/48.1

80.7/88.7

52.1/60.1

93.7/103.7

12.8

18.0

24.6

32.2

14.4

19.2

24.1

9.6

14.4

19.2

24.1

27.3

33.3

39.3

23.4

29.5

35.5

41.5

44.4

51.9

19.6

25.6

21.1

27.2

21.3

24.7

32.2

26.7

34.2

41.7

49.3

29.4

36.9

Max Fuse/

Breaker Size

1

(Amps)

Max HACR

2

Breaker Size

45

60

20

30

25

30

25

25

35

30

35

45

50

30

40

30

35

40

25

30

40

45

45/50

60/70

50/60

60/70

50/60

70/70

80/90

90/100

60/60

70/80

90/90

100/110

25

35

45

60

20

30

25

30

25

25

35

30

35

45

50

30

40

30

35

40

25

30

40

45

45/50

60/70

50/60

60/70

50/60

70/70

80/90

90/100

60/60

70/80

90/90

100/110

25

35

1. Dual element, time delay type.

2. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

3. KW listed is for 240 volts, use table at top of next page for 208 or 230 volts.

4. KW listed is for 480 volts, use table at top of next page for 460 volts.

5. KW listed is for 600 volts, use table at top of next page for 575 volts.

TABLE 5: Electrical Data (Basic Unit)

Size

036

042

048

060

036

042

048

060

036

042

048

060

Volt

208/230-3-60

208/230-3-60

208/230-3-60

208/230-3-60

460-3-60

460-3-60

460-3-60

460-3-60

575-3-60

575-3-60

575-3-60

575-3-60

Voltage

Limitations

1

Compressors

(each)

414

414

518

518

518

518

Min.

Max.

RLA LRA

187

187

253

253

10.9

12.8

78.0

88.0

187

187

414

414

253

253

504

504

14.1

105.0

16.0

125.0

5.8

5.8

40.0

42.0

504

504

630

630

630

630

7.1

8.0

4.5

5.8

5.6

6.4

55.0

67.0

32.0

44.0

44.0

50.0

0.4

0.4

0.6

0.6

0.6

0.6

0.8

0.8

OD Fan

Motors

(each)

FLA

1.1

1.1

1.5

1.5

1.5

1.5

1.6

2.8

1.8

1.8

2.0

3.5

Supply

Blower

Motor

FLA

3.5

3.5

4.0

7.0

1. Rated in accordance with ARI Standard 110, utilization range “A”.

2. Dual element, time delay type.

MCA

(Amps)

18.2

20.6

23.1

28.5

9.6

9.7

11.7

14.3

7.6

9.1

9.3

11.4

Max Fuse

Size

2

(Amps)

15

15

15

20

25

25

30

40

15

15

15

15

Max HACR

Breaker Size

Unit Power

Factor

15

15

15

20

25

25

30

40

15

15

15

15

.96

.96

.96

.96

.96

.96

.96

.96

.96

.96

.96

.96

Transformer

Size (VA)

75

75

75

75

75

75

75

75

75

75

75

75

Johnson Controls Unitary Products 7

341849-YIM-A-0108

Electric Heat

Correction

Factors

Nominal Voltage

240

480

600

Voltage

208

230

460

575 kW. Capacity

Multiplier

.75

.92

.92

.92

TABLE 6: Side & Bottom Supply Air Blower Performance 230/460/575 Volts

Size

036

042

048

036

Blower

Speed

High

Medium

Low

High

Medium

Low

0.1

0.2

0.3

0.4

External Static Pressure (Inch Water Gauge)

0.5

0.6

0.7

0.8

0.9

1.0

1.1

CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W

-

-

-

-

-

-

-

-

1472

-

647

1414 617 1317

1394 626 1297 495 1199

688

465

1219

1102

660

435

1462 526 1400 506 1337 486 1275 467 1167 440 1100 414 1012 387

1116 533 1013

985

-

397

-

-

-

507

-

-

910

-

-

480

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1697 740 1580

1673 830 1566 594 1439

706

558

1463

1322

672

522

1339 640 1216

1182 476

1680 607 1608 584 1630 660 1425 528 1320 496 1214 464 1050 420 -

-

608

-

-

1092

-

-

576

-

-

-

-

-

-

-

High 1947 882 1867 857 1786 832 1706 807 1637 782 1569 757 1500 732

Medium 1876 792 1829 772 1783 753 1736 733 1668 706 1599 680 1531 653 1434 622 1337 591 1240 560

Low 1544 620 1508 610 1472 600 1436 590 1375 573 1313 557 1252 540 -

High

Medium

Low

-

-

-

2499 1290 2391 1233 2283 1177 2175 1120 2067 1080 1958 1040 1850 1000

2454 1163 2387 1117 2320 1070 2229 1023 2137 977 2046 930 1950 887 1854 843 1758 800

2242 1090 2201 1053 2161 1017 2120 980 2041 927 1962 873 1883 820 1797 787 1711 753 1625 720

-

-

-

-

-

-

-

-

-

-

-

-

TABLE 7: Side & Bottom Supply Air Blower Performance 208 Volts

Size

036

042

048

036

Blower

Speed

External Static Pressure (Inch Water Gauge)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W

1440 608 1381 571 1273 656 1185 530 1097 604 1004 480 912 456 High

Medium 1465 631 1395 512 1325 492 1255 473 1167 446 1079 419 952 392

Low 1316 473 1260 455 1204 438 1148 420 1069 396 990 372 911 348

High -

-

-

-

-

-

-

-

-

1728 725 1633 697 1527 666 1422 636 1317 606 1205 676 1094 547

-

-

-

-

-

-

-

-

-

-

-

-

Medium

Low

High

1674 614 1590 590 1506 567 1400 636 1296 602 1190 470 1063 428

1679 867 1612 646 1449 526 1377 504 1282 476 1188 447 1093 418 -

-

-

-

-

-

-

-

-

-

1982 870 1939 850 1897 830 1813 800 1728 770 1644 740 1559 707 1474 673 1389 640

-

-

-

-

-

-

Medium 1694 690 1662 673 1629 657 1597 640 1542 623 1486 607 1431 590 1336 563 1240 537

Low 1385 520 1349 510 1312 500 1276 490 1235 480 -

High -

-

-

-

-

2450 1213 2366 1165 2282 1117 2198 1068 2114 1020 1989 993 1864 967 1739 940

Medium 2339 1170 2275 1118 2211 1067 2147 1015 2083 963 2019 912 1955 860 1854 824 1753 788 1652 752

Low 1929 940 1877 903 1824 867 1772 830 1720 793 1667 757 1615 720 1586 706 1557 691 1528 677

-

-

-

-

-

-

-

-

-

-

TABLE 8: Additional Static Pressure Resistance

1

,

2

Description

Wet Indoor Coil

Economizer

Filter/Frame Kit

Electric Heat

Resistance, IWG

CFM

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000

0.01

0.01

0.01

0.02

0.02

0.03

0.03

0.04

0.04

0.04

0.04

0.04

0.05

0.05

0.06

0.07

0.00

0.01

0.02

0.00

0.02

0.03

0.00

0.02

0.03

0.01

0.02

0.03

0.01

0.02

0.04

0.01

0.02

0.04

0.01

0.03

0.05

0.02

0.03

0.06

0.03

0.03

0.07

0.04

0.03

0.08

0.05

0.04

0.09

0.06

0.05

0.10

0.07

0.05

0.01

0.07

0.06

0.11

0.08

0.06

0.11

0.08

0.07

0.12

1. Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table.

2. The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than

0.25 IWG, the unit will deliver less CFM during full economizer operation.

8 Johnson Controls Unitary Products

341849-YIM-A-0108

CHECKING SUPPLY AIR CFM

To check the supply air CFM after the initial balancing has been completed:

1.

Remove the two ¼ inch dot plugs in the duct panel.

2.

Insert at least 8 inches of ¼ inch tubing into each of these holes for sufficient penetration into the airflow on both sides of the indoor coil.

3.

Using an inclined manometer, determine the pressure drop across the dry evaporator coil. Since the moisture on an evaporator coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be inaccurate. To ensure a dry coil, the compressors should be deactivated while the test is being run.

4.

Knowing the pressure drop across a dry coil, the actual CFM through the unit can be determined from the curve in Coil Delta P vs. Supply Air CFM

Figure 3.

Failure to properly adjust the total system air quantity can result in extensive system damage.

After readings have been obtained, remove the tubes and reinstall the two ¼ inch plugs removed in Step 1.

NOTE: De-energize the compressors before taking any test measurements to ensure a dry indoor coil.

B1HA Coil Delta

B1HA036 B1HA048-60

B1HA042

Linear B1HA036

Linear B1HA042

Linear B1HA048-60

Airflow (CFM)

FIGURE 3 - Coil Delta P vs. Supply Air CFM

Johnson Controls Unitary Products 9

341849-YIM-A-0108

TABLE 9: Cooling Superheat at Compressor Suction, Airflow = 1,200 CFM (B1HA036)

Outdoor

Temperature

°F

65

70

75

80

85

90

95

100

105

110

115

55

7.0

5.6

-

-

12.8

11.4

9.9

8.5

-

-

-

57

8.9

7.1

5.3

-

16.1

14.3

12.5

10.7

-

-

-

59

19.3

17.2

15.0

12.9

10.8

8.6

6.5

5.1

-

-

-

61

22.5

20.1

17.6

15.1

12.6

10.1

7.7

6.0

-

-

-

Indoor WB Temperature, °F

63 65 67

25.8

22.9

20.1

17.3

14.5

11.7

8.8

6.9

-

-

-

29.0

25.8

22.7

19.5

16.3

13.2

10.0

7.8

5.6

-

-

32.2

28.7

25.2

21.7

18.2

14.7

11.2

8.7

6.2

-

-

69

35.0

31.6

28.2

24.8

21.4

18.0

14.6

11.7

8.7

5.8

-

71

37.7

34.4

31.1

27.9

24.6

21.3

18.1

14.7

11.3

7.9

-

TABLE 10: Heating Superheat at Compressor Suction, Airflow = 1,200 CFM (B1HA036)

Indoor DB

Temperature

°F

55

70

80

-10

9.7

-

-

0

10.1

-

-

Heating Superheat at Compressor Suction, °F

10 20 30 40

10.7

-

-

11.8

-

-

13.7

4.6

-

17.0

7.8

-

50

22.6

13.4

7.3

60

32.2

23.0

16.9

TABLE 11: Cooling Superheat at Compressor Suction, Airflow = 1,400 CFM (B1HA042)

Outdoor

Temperature

°F

65

70

75

80

85

90

95

100

105

110

115

55

34.0

31.1

28.3

25.4

22.6

19.7

16.9

14.5

12.2

9.9

7.6

57

34.2

31.5

28.8

26.1

23.5

20.8

18.1

15.6

13.1

10.5

8.0

59

34.4

31.9

29.4

26.9

24.4

21.9

19.4

16.6

13.9

11.1

8.4

61

34.6

32.2

29.9

27.6

25.3

23.0

20.6

17.7

14.7

11.7

8.8

Indoor WB Temperature, °F

63 65 67

34.8

32.6

30.5

28.3

26.2

24.0

21.9

18.7

15.5

12.3

9.1

35.0

33.0

31.0

29.1

27.1

25.1

23.2

19.7

16.3

12.9

9.5

35.2

33.4

31.6

29.8

28.0

26.2

24.4

20.8

17.1

13.5

9.9

69

36.2

34.8

33.4

32.0

30.6

29.2

27.8

24.4

20.9

17.4

14.0

71

37.3

36.3

35.3

34.3

33.2

32.2

31.2

27.9

24.6

21.3

18.1

TABLE 12: Heating Superheat at Compressor Suction, Airflow = 1,400 CFM (B1HA042)

Indoor DB

Temperature

°F

55

70

80

-10

5.1

-

-

0

5.5

-

-

10

6.2

-

-

Outdoor Temperature, °F

20

7.4

-

-

30

9.6

5.0

-

40

13.5

8.9

5.4

50

20.3

15.7

12.2

60

32.4

27.8

24.3

73

40.4

37.3

34.1

31.0

27.8

24.7

21.5

17.7

13.9

10.0

6.2

75

43.1

40.1

37.1

34.0

31.0

28.0

25.0

20.7

16.4

12.2

7.9

73

38.4

37.7

37.1

36.5

35.9

35.2

34.6

31.5

28.4

25.3

22.1

75

39.4

39.2

39.0

38.7

38.5

38.3

38.0

35.1

32.1

29.2

26.2

10 Johnson Controls Unitary Products

341849-YIM-A-0108

TABLE 13: Cooling Superheat at Compressor Suction, Airflow = 1,600 CFM (B1HA048)

Outdoor

Temperature

°F

65

70

75

80

85

90

95

100

105

110

115

55

7.2

6.5

5.9

-

11.4

10.3

9.3

8.2

-

-

-

57

7.7

7.0

6.3

5.5

12.4

11.2

10.0

8.8

-

-

-

59

8.1

7.4

6.8

6.1

13.5

12.2

10.8

9.4

5.4

-

-

61

8.5

7.9

7.2

6.6

14.6

13.1

11.6

10.0

6.1

5.5

-

Indoor WB Temperature, °F

63

9.0

8.3

7.7

7.2

15.7

14.0

12.3

10.6

6.8

6.3

5.9

65

9.4

8.8

8.1

7.8

16.8

14.9

13.1

11.2

7.5

7.2

6.9

67

9.8

9.2

8.6

8.4

17.9

15.9

13.9

11.8

8.2

8.0

7.8

69

19.3

17.4

15.4

13.5

11.6

10.6

9.6

9.3

9.1

8.9

8.7

71

20.7

18.9

17.0

15.2

13.4

12.0

10.6

10.3

10.1

9.8

9.5

TABLE 14: Heating Superheat at Compressor Suction, Airflow = 1,600 CFM (B1HA048)

Indoor DB

Temperature

°F

55

70

80

-10

8.3

-

-

0

8.4

-

-

Heating Superheat at Compressor Suction, °F

10 20 30 40

8.6

-

-

9.0

-

-

10.1

-

-

12.4

4.2

-

50

17.4

9.2

5.7

60

28.6

20.4

16.9

TABLE 15: Cooling Superheat at Compressor Suction, Airflow = 2,000 CFM (B1HA060)

Outdoor

Temperature

°F

65

70

75

80

85

90

95

100

105

110

115

55

7.3

7.2

7.0

7.2

26.7

21.9

17.0

12.2

7.4

7.6

7.8

57

9.1

8.3

7.5

7.6

27.6

23.0

18.3

13.7

7.7

7.8

7.8

59

28.5

24.1

19.7

15.3

10.8

9.4

8.0

8.0

7.9

7.9

7.9

61

29.4

25.2

21.0

16.8

12.6

10.6

8.5

8.3

8.2

8.1

7.9

Indoor WB Temperature, °F

63 65 67

30.3

26.3

22.3

18.4

14.4

11.7

9.0

8.7

8.5

8.2

8.0

31.2

27.4

23.7

19.9

16.2

12.8

9.5

9.1

8.7

8.4

8.0

32.1

28.5

25.0

21.5

17.9

13.9

9.9

9.5

9.0

8.5

8.1

69

33.0

30.0

27.0

24.0

20.9

17.3

13.6

12.4

11.2

10.0

8.8

71

33.9

31.4

28.9

26.5

24.0

20.6

17.2

15.3

13.4

11.5

9.6

TABLE 16: Heating Superheat at Compressor Suction, Airflow = 2,000 CFM (B1HA060)

Indoor DB

Temperature

°F

55

70

80

-10

5.5

-

-

0

5.7

-

-

10

6.2

-

-

Outdoor Temperature, °F

20 30

6.8

-

-

8.0

-

-

40

9.9

4.8

-

50

13.1

8.0

5.6

60

18.6

13.4

11.0

73

22.1

20.4

18.6

16.9

15.1

13.4

11.6

11.3

11.0

10.7

10.4

75

23.5

21.9

20.2

18.5

16.9

14.8

12.6

12.3

11.9

11.6

11.2

73

34.8

32.8

30.9

29.0

27.0

23.9

20.8

18.2

15.6

13.0

10.3

75

35.7

34.3

32.9

31.4

30.0

27.2

24.4

21.1

17.8

14.4

11.1

Johnson Controls Unitary Products 11

HIGH VOLTAGE CONN.

" DIA. KNOCKOUT

HIGH VOLTAGE CONN.

" DIA. KNOCKOUT

LOW VOLTAGE CONN.

" DIA. KNOCKOUT

SIDE SUPPLY

AIR OPENING

SIDE RETURN

AIR OPENING

49

(OVERALL)

LOW VOLTAGE

CONN.

" DIA. KNOCK-

341849-YIM-A-0108

FRONT

2

“A”

COMPRESSOR

SERVICE ACCESS

COMPARTMENT PANEL

(OVERALL)

UNIT SIZE

DIMENSION

“A”

036 - 042

048 - 060

33

41

(OVERALL)

REFRIGERANT

CONNECTIONS

ELECTRICAL/FILTER

SERVICE ACCESS

COMPARTMENT PANEL

HIGH VOLTAGE CONN.

" DIA. KNOCKOUT

2

FRONT

4

1

HIGH VOLTAGE

CONN.

" x " DIA.

KNOCKOUT

UNIT CONDENSATE

CONNECTION " NPTI

(TRAP REQUIRED)

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.

SIDE SUPPLY

AIR OPENING

6

OUTDOOR

COIL

CONDENSATE

DRAIN " NPTI

BOTTOM SUPPLY

AIR OPENING

Front

Back

CLEARANCES

(Minimum)

12"

0"

Left Side (Filter Access) 24"

Right Side 24"

Below Unit 1

Above Unit 2

0"

36"

(For Condenser Air Discharge)

1. Units may be installed on combustible floors made from wood or

class A, B or C roof covering material.

2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.

FIGURE 4 - Dimensions and Clearances

1

15

15

BACK

SIDE RETURN

AIR OPENING

2

1

1

15

4

BOTTOM RETURN

AIR OPENING

12 Johnson Controls Unitary Products

advertisement

Related manuals

advertisement