advertisement
![Glossary. Watlow SERIES D8, Gateway & DeviceNet | Manualzz Glossary. Watlow SERIES D8, Gateway & DeviceNet | Manualzz](http://s1.manualzz.com/store/data/001928493_1-829582717754281b405967c18ba0139c-360x466.png)
Series D8 User’s Guide Glossary
Glossary
A
AC
See Alternating Current.
AC Line Frequency
The frequency of the ac line power measured in Hertz
(Hz), usually 50 or 60 Hz.
Accuracy
Closeness between the value indicated by a measuring instrument and a physical constant or kno wn standards.
Action
The response of an output when the process v ariable is changed. See also Direct Action, Reverse Action.
Address
A numerical identifier for a controller when used i computer communications.
Alarm
A signal that indicates that the process has e xceeded or fallen below a certain range around the set point.
For example, an alarm may indicate that a process is too hot or too cold. See also Failed Sensor Alarm,
Global Alarm, High De viation Alarm, High Alarm,
Loop Alarm, Low Deviation Alarm, Low Alarm.
Alarm Delay
The lag time before an alarm is activated.
Alternating Current (AC)
An electric current that re verses at re gular intervals, and alternates positive and negative values.
Ambient Temperature
The temperature of the air or other medium that sur rounds the components of a thermal system.
American Wire Gauge (AWG)
A standard of the dimensional characteristics of wire used to conduct electrical current or signals. AWG is identical to the Brown and Sharpe (B&S) wire gauge.
Ammeter
An instrument that measures the magnitude of an electric current.
Ampere (Amp, A)
A unit that defines the rate of f w of electricity (current) in the circuit. Units are one coulomb (6.25 x
1018 electrons) per second.
Analog Output
A continuously v ariable signal that is used to represent a v alue, such as the process v alue or set point value. Typical hardw are configurations are 0 t
20mA, 4 to 20mA or 0 to 5 Vdc.
Automatic Mode
A feature in which the controller sets PID control outputs in response to the process v ariable and the set point.
Automatic Reset
The integral function of a PI or PID temperature controller that adjusts the process temperature to the set point after the system stabilizes. The inverse of integral.
Autotune
A feature that automatically sets temperature control
PID values to match a particular thermal system.
AWG
See American Wire Gauge.
B
Baud Rate
The rate of information transfer in serial communications, measured in bits per second.
BCD
Binary coded decimal. F or BCD job loading, the binary states of three digital inputs are decoded as decimal numbers 1 to 8.
Bumpless Transfer
A smooth transition from automatic (closed loop) to manual (open loop) operation. The control output does not change during the transfer.
C
Calibration
The comparison of a measuring de vice (an unknown) against an equal or better standard.
Doc. 0600-3120-2000 Watlow Anafaze 197
Glossary Series D8 User’s Guide
Celsius
A temperature scale in which w ater freezes at 0° C and boils at 100° C at standard atmospheric pressure.
The formula for conversion to the F ahrenheit scale is
°F = (1.8 x °C) + 32. Formerly known as Centigrade.
Central Processing Unit (CPU)
The unit of a computing system that includes the cir cuits controlling the interpretation of instructions and their execution.
Circuit
Any closed path for electrical current. A configuratio of electrically or electromagnetically-connected components or devices.
Class
The model for a software object. Objects of a class are similar to one another. DeviceNet classes define wha attributes and services objects of that type have. Class services are used to e xamine and change class attributes.
Closed Loop
A control system that uses a sensor to measure a process variable and makes decisions based on that feedback.
Cold Junction
Connection point between thermocouple metals and the electronic instrument.
Common Mode Rejection Ratio
The ability of an instrument to reject electrical noise, with relation to ground, from a common voltage. Usually expressed in decibels (dB).
Communications
The use of digital computer messages to link components. See also Serial Communications, Baud Rate.
Control Action
The response of the PID control output relati ve to the difference between the process v ariable and the set point. See also Direct Action, Reverse Action.
Current
The rate of fl w of electricity. The unit of measure is the Ampere (A). 1 Ampere = 1 coulomb per second.
Cycle Time
The time required for a controller to complete one onoff-on cycle. It is usually expressed in seconds.
Cyclic Redundancy Check (CRC)
An error checking method in communications that provides a high level of data security.
D
DAC
See Digital-to-Analog Converter.
Data Logging
A method of recording a process v ariable o ver a period of time. Used to review process performance.
DC
See Direct Current.
Default Parameters
The programmed instructions that are permanently stored in the microprocessor software.
Derivative Control (D)
The last term in the PID algorithm. Action that anticipates the rate of change of the process and compensates to minimize o vershoot and undershoot.
Derivative control is an instantaneous change of the control output in the same direction as the propor tional error. This is caused by a change in the process variable that decreases over the time of the derivative.
The derivative is expressed in seconds.
Deutsche Industrial Norms (DIN)
A set of technical, scientific and dimensional stan dards de veloped in German y. Man y DIN standards have worldwide recognition.
Deviation Alarm
See High Deviation Alarm, Low Deviation Alarm.
DeviceNet
DeviceNet is a netw ork that connects industrial devices. De viceNet is designed to pro vide a costeffective and rob ust solution to de vice netw orking.
DeviceNet is designed to transport control-oriented information associated with lo w-level de vices and other information related to the system being controlled, such as configuration parameters
Digital-to-Analog Converter (DAC)
A device that con verts a numerical input signal to a signal that is proportional to the input in some way.
DIN
See Deutsche Industrial Norms.
198 Watlow Anafaze Doc. 0600-3120-2000
Series D8 User’s Guide Glossary
Direct Action
An output control action in which an increase in the process variable causes an increase in the output. Usually used with cooling applications.
Direct Current (DC)
An electric current that fl ws in one direction.
Distributed Zero Crossing (DZC)
A form of digital output control in which the output on/off state is calculated for e very ac line c ycle.
Power is switched at the zero cross, which reduces electrical noise. See also Zero Cross.
DZC
See Distributed Zero Crossing.
Emissivity
The ratio of radiation emitted from a surf ace compared to radiation emitted from a blackbody at the same temperature.
Engineering Units
Selectable units of measure, such as de grees Celsius or F ahrenheit, pounds per square inch, ne wtons per meter, gallons per minute, liters per minute, cubic feet per minute or cubic meters per minute.
E
Earth Ground
A metal rod, usually copper , that provides an electrical path to the earth, to pre vent or reduce the risk of electrical shock.
EIA/TIA
Electronic Industries Alliance (EIA) and Telecommunications Industry Association (TIA). See also Serial
Communications.
EIA/TIA-232
—
A standard for interface between data terminal equipment and data communications equipment for serial binary data interchange. This is usually for communications over a short distance
(50 feet [15 m] or less) and to a single device.
EIA/TIA-485
—
A standard for electrical characteristics of generators and recei vers for use in balanced digital multipoint systems. This is usually used to communicate with multiple de vices over a common cable or where distances o ver 50 feet (15 m) are required.
Electrical Noise
See Noise.
Electromagnetic Interference (EMI)
Electrical and magnetic noise imposed on a system.
There are many possible causes, such as switching ac power inside the sine w ave. EMI can interfere with the operation of controllers and other devices.
Electrical-Mechanical Relays
See Relay, Electromechanical.
F
Fahrenheit
The temperature scale that sets the freezing point of water at 32° F and its boiling point at 212° F at standard atmospheric pressure. The formula for con version to Celsius is °C = 5/9 (°F - 32).
Failed Sensor Alarm
Warns that an input sensor no longer produces a v alid signal.
Filter
Filters are used to handle v arious electrical noise problems.
Digital Filter
—
A filter that sl ws the response of a system when inputs change unrealistically or too fast. Equi valent to a standard resistor -capacitor
(RC) filte
Digital Adaptive Filter
—
A filter that reject high frequency input signal noise (noise spikes).
Heat/Cool Filter
—
A filter that sl ws the change in the response of the heat or cool output. The output responds to a step change by going to approximately 2/3 its final alue within the numbers of scans that are set.
Frequency
The number of cycles over a specified period of time usually measured in c ycles per second. Also referred to as Hertz (Hz).
G
Gain
The amount of amplification used in an electrical ci cuit. Gain can also refer to the proportional (P) mode of PID.
Doc. 0600-3120-2000 Watlow Anafaze 199
Glossary Series D8 User’s Guide
Global Alarm
Warns that one or more alarm conditions exist by activating a digital output.
Ground
An electrical line with the same electrical potential as the surrounding earth. Electrical systems are usually grounded to protect people and equipment from shocks due to malfunctions. Also referred to as
“safety ground.”
Input Scaling
The con verting of input signals to the engineering units of the process variable.
Input Type
The signal type that is connected to an input, such as thermocouple, RTD or process.
H
Hertz (Hz)
Frequency, measured in cycles per second.
Instance
An object that is an occurance of a class. Each instance of a DeviceNet object can have unique values for its attrib utes and can be e xamined or changed using the instance services. Class services are used to examine and change class attrib utes, which af fect all instances. Instance services are used to e xamine and change instance attributes which affect only that par ticular instance.
High Deviation Alarm
Warns that the process has risen more than a certain amount abo ve set point. It can be used as either an alarm or control function.
Integral Control (I)
Control action that automatically eliminates of fset, or droop, between set point and actual process temperature.
High Power
(As defined by Watlow Anafaze) Any voltage above
24 Vac or Vdc and any current level above 50 mAac or mAdc.
High Alarm
A signal that is associated with a set maximum v alue that can be used as either an alarm or boost control function.
HMI
Human-machine interface.
J
Job
A set of operating conditions for a process that can be stored and recalled in a controller’ s memory . Also called a recipe.
Junction
The point where two dissimilar metal conductors join to form a thermocouple.
Hysteresis
Control Hysteresis
—
The range through which a variation of the input produces no noticeable change in the output. In the hysteresis, specific con ditions can be placed on control output actions.
Operators select the hysteresis. It is usually abo ve the heating proportional band and belo w the cooling proportional band.
Process Hysteresis
—
In heat/cool applications, the +/- dif ference between heat and cool. Also known as process deadband.
K
Keypad Lock
A feature that pre vents operation of the k eypad by unauthorized people.
L
Lag
The delay between the output of a signal and the response of the instrument to which the signal is sent.
I
Input
Analog Input
— An input that accepts process variable information.
Digital Input
— An input that accepts on and of f signals.
200 Watlow Anafaze
Linearity
The deviation in response from an e xpected or theoretical straight line v alue for instruments and transducers. Also called linearity error.
Load
The electrical demand of a process, e xpressed in power (Watts), current (Amps) or resistance (Ohms).
Doc. 0600-3120-2000
Series D8 User’s Guide Glossary
The item or substance that is to be heated or cooled.
Low Deviation Alarm
Warns that the process has dropped more than a cer tain amount belo w set point. It can be used as either an alarm or control function.
On/Off Control
A method of control that turns the output full on until set point is reached, and then off until the process differs from the set point by more than the hysteresis.
Open Loop
A control system with no sensory feedback.
Low Alarm
A signal that is associated with a set minimum v alue that can be used as either an alarm or boost control function.
M
Manual Mode
A selectable mode that has no automatic control aspects. The operator sets output levels.
Optical Isolation
Two electronic netw orks that are connected through an LED (Light Emitting Diode) and a photoelectric receiver. There is no electrical continuity between the two networks.
Output
Control signal action in response to the dif ference between set point and process variable.
Manual Reset
A parameter that allows the user to eliminate offset or droop between set point and actual process temperature. See also Integral.
Output Type
The form of control output, such as time proportioning, distributed zero crossing, Serial D AC or analog.
Also the description of the electrical hardw are that makes up the output.
Milliampere (mA)
One thousandth of an ampere.
Overshoot
The amount by which a process v ariable exceeds the set point before it stabilizes.
N
Noise
Unwanted electrical signals that usually produce signal interference in sensors and sensor circuits. See also Electromagnetic Interference.
P
PID
Proportional, Inte gral, Deri vative. A control mode with three functions: Proportional action dampens the system response, inte gral corrects for droops, and derivative prevents overshoot and undershoot.
Noise Suppression
The use of components to reduce electrical interfer ence that is caused by making or breaking electrical contact, or by inductors.
Polarity
The electrical quality of ha ving tw o opposite poles, one positive and one negative. Polarity determines the direction in which a current tends to fl w.
O
Object
An object is a softw are programming concept in which data and functionality are associated with vir tual objects. DeviceNet objects consists of data called attributes and functions called services. Services are used to examine or change attribute values.
Process Input
A v oltage or current input that represents a straight line function.
Process Variable (PV)
The parameter that is controlled or measured. Typical examples are temperature, relative humidity, pressure, fl w, fluid l vel, events, etc.
Offset
The difference between the set point and the actual value of the process variable. Offset is the error in the process v ariable that is typical of proportional-only control.
Doc. 0600-3120-2000
Proportional (P)
Output effort proportional to the error from set point.
For example, if the proportional band is 20° and the process is 10° belo w the set point, the heat propor tioned effort is 50 percent. The lower the PB v alue, the higher the gain.
Watlow Anafaze 201
Glossary Series D8 User’s Guide
Proportional Band (PB)
A range in which the proportioning function of the control is acti ve. Expressed in units, de grees or per cent of span. See also PID.
Proportional Control
A control using only the P (proportional) value of PID control.
Pulse Input
Digital pulse signals from de vices, such as optical encoders.
PV
See Process Variable.
R
Ramp
A programmed increase in the temperature of a set point system.
Range
The area between tw o limits in which a quantity or value is measured. It is usually described in terms of lower and upper limits.
Recipe
See Job.
Relay
A switching device.
Electromechanical Relay
—
A power switching device that completes or interrupts a circuit by physically mo ving electrical contacts into contact with each other. Not recommended for PID control.
Solid State Relay (SSR)
— A switching de vice with no moving parts that completes or interrupts a circuit electrically.
Reset
See Automatic Reset, Manual Reset.
Resistance
Opposition to the fl w of electric current, measured in
Ohms.
Resistance Temperature Detector (RTD)
A sensor that uses the resistance temperature characteristic to measure temperature. There are tw o basic types of RTDs: the wire RTD, which is usually made of platinum, and the thermistor , which is made of a semiconductor material. The wire R TD is a positi ve temperature coef ficient sensor onl , while the ther mistor can have either a negative or positive temperature coefficient
Reverse Action
An output control action in which an increase in the process variable causes a decrease in the output. Heating applications usually use reverse action.
RTD
See Resistance Temperature Detector.
S
Serial Communications
A method of transmitting information between devices by sending all bits serially o ver a single communication channel.
Set Point (SP)
The desired v alue of the process v ariable. For example, the temperature at which a system is to be maintained.
Shield
A metallic foil or braided wire layer surrounding conductors that is designed to pre vent electrostatic or electromagnetic interference from external sources.
Signal
Any electrical transmittance that conveys information.
Solid State Relay (SSR)
See Relay, Solid State.
Span
The difference between the lower and upper limits of a range expressed in the same units as the range.
Stability
The ability of a de vice to maintain a constant output with the application of a constant input.
T
Thermistor
A temperature-sensing device made of semiconductor material that exhibits a large change in resistance for a small change in temperature. Thermistors usually have negative temperature coefficients, although th y are also a vailable with positi ve temperature coef fi cients.
202 Watlow Anafaze Doc. 0600-3120-2000
Series D8 User’s Guide
Thermocouple (T/C)
A temperature sensing de vice made by joining tw o dissimilar metals. This junction produces an electrical voltage in proportion to the dif ference in temperature between the hot junction (sensing junction) and the lead wire connection to the instrument (cold junction).
Thermocouple Extension Wire
A grade of wire used between the measuring junction and the reference junction of a thermocouple. Extension wire and thermocouple wire have similar properties, but extension wire is less costly.
Transmitter
A device that transmits temperature data from either a thermocouple or RTD by way of a two-wire loop. The loop has an e xternal po wer supply . The transmitter acts as a variable resistor with respect to its input signal. Transmitters are desirable when long lead or extension wires produce unacceptable signal degradation.
U
Undershoot
The amount by which a process v ariable falls below the set point before it stabilizes.
V
Volt (V)
The unit of measure for electrical potential, voltage or electromotive force (EMF). See also Voltage.
Voltage (V)
The dif ference in electrical potential between tw o points in a circuit. It is the push or pressure behind current fl w through a circuit. One volt (V) is the difference in potential required to mo ve one coulomb of charge between two points in a circuit, consuming one joule of energy. In other w ords, one volt (V) is equal to one ampere of current (I) fl wing through one ohm of resistance (R), or V = IR.
Z
Zero Cross
Action that provides output switching only at or near the zero-voltage crossing points of the ac sine wave.
Doc. 0600-3120-2000 Watlow Anafaze
Glossary
203
Glossary Series D8 User’s Guide
204 Watlow Anafaze Doc. 0600-3120-2000
advertisement
Related manuals
advertisement
Table of contents
- 1 Cover
- 2 Warranty
- 3 Table of Contents
- 11 List of Figures
- 15 List of Tables
- 19 System Overview
- 19 Manual Contents
- 20 Getting Started
- 20 Safety Symbols
- 20 Initial Inspection
- 20 Product Features
- 23 D8 Parts List
- 24 Technical Description
- 24 D8
- 26 TB50
- 26 D8 Cabling
- 26 Safety
- 26 External Safety Devices
- 27 Power-Fail Protection
- 29 Installation
- 30 Typical Installation
- 30 Mounting Controller Components
- 31 Recommended Tools
- 31 Mounting the Controller
- 34 Mounting the TB50
- 36 Mounting the Power Supply
- 37 Mounting the Dual DAC or Serial DAC Module
- 38 System Wiring
- 38 Wiring Recommendations
- 39 Noise Suppression
- 40 Ground Loops
- 41 Power Connections
- 41 Wiring the Power Supply
- 43 Connecting the TB50 to the D8
- 44 Testing the System
- 44 TB50 or TB18 Test
- 44 Digital Output Test
- 45 Digital Input Test
- 45 Sensor Wiring
- 46 Input Wiring Recommendations
- 47 Thermocouple Connections
- 48 RTD Input Connections
- 48 Voltage Input Connections
- 48 Current Input Connections
- 49 Wiring Control and Digital I/O
- 49 Output Wiring Recommendations
- 49 Cable Tie Wraps
- 49 Digital Outputs
- 53 Digital Inputs
- 54 TB18 Connections
- 55 TB50 Connections
- 56 Analog Outputs
- 56 Wiring the Dual DAC
- 57 Wiring the Serial DAC
- 58 Connecting the D8 to a DeviceNet Network
- 58 Connector Type
- 59 Pinout
- 60 Network Length
- 60 Baud Rate (Data Rate)
- 60 Node Address (MAC ID)
- 61 Status Indicators
- 63 Communicating by DeviceNet
- 63 Accessing Data with a DeviceNet Master
- 63 Software
- 64 About The Electronic Data Sheet (EDS)
- 64 Configuring a D8 Using RSNetWorx
- 65 Registering the D8 without an EDS File
- 66 Registering the D8 with the Watlow EDS File
- 68 Mapping Polled I/O Data
- 68 Adding the D8 to the Master's Scanlist
- 69 Assigning PLC Addresses
- 71 Sample Ladder Logic
- 71 Accessing Polled I/O Data
- 73 Setting a Value with an Explicit Message
- 75 Reading a Value with an Explicit Message
- 76 Setting Parameters via DeviceNet
- 76 Non-Numeric Settings
- 77 Bit-Wise Values
- 77 Decimal Placement for Numeric Values
- 78 Decimal Placement for Percentage Values
- 78 D8 DeviceNet Overview
- 78 Master/Slave Connections
- 79 Addressing
- 79 Data Types
- 79 DeviceNet Objects
- 79 Identity Object
- 80 Message Router Object
- 81 DeviceNet Object
- 81 Assembly Object
- 84 Connection Object
- 85 Input Object
- 86 Output Object
- 88 Control Object
- 89 Alarm Object
- 90 PV Retransmit Object
- 91 Ratio Object
- 92 Cascade Object
- 93 Global Object
- 95 Operation and Setup
- 95 General Navigation Map
- 97 Keypad
- 98 Displays
- 98 Loop Display
- 99 Alarm Displays
- 101 Job Display
- 102 Changing the Set Point
- 102 How to Manually Change the Set Point
- 102 Other Methods of Changing the Set Point
- 103 Changing the Control Mode and Output Power
- 104 Accessing and Navigating the Setup Menus
- 104 How to Access the Setup Menus
- 104 How to Edit a Setup Parameter
- 105 Setting Up Closed-Loop Control
- 105 Feedback
- 105 Control Algorithm
- 105 Control Output Signal Forms
- 105 Heat and Cool Outputs
- 106 How to Set Up Closed-Loop Control
- 106 Setting Up a Process Input
- 106 Input Scaling
- 107 Input Scaling Example: 4 to 20 mA Sensor
- 108 Input Scaling Example: 0 to 5 Vdc Sensor
- 109 Autotuning
- 109 How Does Autotuning Work?
- 110 Prerequisites
- 110 How to Autotune a Loop
- 111 Setting Up Alarms
- 111 Failed Sensor Alarms
- 113 Process Alarms
- 115 Global Alarm
- 115 Setting Up Process Variable Retransmit
- 116 How to Set Up Process Variable Retransmit
- 116 Process Variable Retransmit Example: Data Logging
- 118 Setting Up Cascade Control
- 118 How the Secondary Set Point is Determined
- 119 Proportional-Only Control on the Primary Loop
- 120 How To Set Up Cascade Control
- 120 Cascade Control Example: Water Tank
- 122 Setting Up Ratio Control
- 123 How to Set Up Ratio Control
- 123 Ratio Control Example: Diluting KOH
- 124 Setting Up Differential Control
- 125 How to Set Up Differential Control
- 125 Differential Control Example: Thermoforming
- 125 Setting Up Remote Analog Set Point
- 126 How to Set Up a Remote Analog Set Point
- 126 Remote Analog Set Point Example: Changing a Set Point with a PLC
- 129 Tuning and Control
- 129 Control Algorithms
- 130 On/Off Control
- 130 Proportional Control (P)
- 131 Proportional and Integral Control (PI)
- 132 Proportional, Integral and Derivative Control (PID)
- 132 Heat and Cool Outputs
- 133 Setting Up and Tuning PID Loops
- 133 Proportional Band Settings
- 133 Integral Settings
- 134 Derivative Settings
- 135 General PID Constants by Application
- 135 Proportional Band Only (P)
- 135 Proportional with Integral (PI)
- 135 Proportional and Integral with Derivative (PID)
- 136 Control Outputs
- 136 Output Control Signals
- 138 Output Filter
- 138 Reverse and Direct Action
- 139 Menu and Parameter Reference
- 139 Operator Parameters
- 140 Set Point
- 140 Mode
- 140 Heat/Cool Output
- 141 Process Variable
- 141 Overview of the Setup Menus
- 143 Global Setup Menu
- 143 Load Setup From Job
- 143 Save Setup As Job
- 144 BCD Job Load
- 144 BCD Job Load Logic
- 145 Mode Override
- 146 Mode Override Digital Input Active
- 146 Power Up Alarm Delay
- 146 Power Up Loop Mode
- 147 Keypad Lock
- 147 Thermocouple Short Alarm
- 147 AC Line Frequency
- 147 Digital Output Alarm Polarity
- 148 MAC ID
- 148 Baud Rate
- 148 Module LED
- 148 Network LED
- 148 Bus Off Count
- 149 Model and Firmware Version
- 149 Input Menu
- 149 Input Type
- 150 Loop Name
- 150 Input Units
- 150 Calibration Offset
- 151 Reversed Thermocouple Detection
- 151 Display Format
- 152 Input Range High
- 152 Input High Signal
- 153 Input Range Low
- 153 Input Low Signal
- 153 Input Filter
- 154 Control Menu
- 154 Heat/Cool Proportional Band
- 155 Heat/Cool Integral
- 155 Heat/Cool Derivative
- 155 Heat/Cool Manual Reset
- 155 Heat/Cool Filter
- 156 Hysteresis
- 156 Restore Automatic Mode
- 157 Output Menu
- 157 Heat/Cool Output Type
- 158 Heat/Cool Cycle Time
- 158 Heat/Cool SDAC Signal
- 158 Heat/Cool SDAC Low Signal
- 158 Heat/Cool SDAC High Signal
- 159 Heat/Cool Action
- 159 Heat/Cool Power Limit
- 159 Heat/Cool Power Limit Time
- 160 Sensor Fail Heat/Cool Output
- 160 Open Thermocouple Heat/Cool Output Average
- 161 Heat/Cool Output Curve
- 161 Alarms Menu
- 161 Alarm High Set Point
- 162 Alarm High Function
- 162 Alarm High Output
- 163 High Deviation Value
- 163 High Deviation Function
- 163 High Deviation Output
- 163 Low Deviation Value
- 163 Low Deviation Function
- 164 Low Deviation Output
- 164 Alarm Low Set Point
- 164 Alarm Low Function
- 164 Alarm Low Output
- 165 Alarm Hysteresis
- 165 Alarm Delay
- 166 Process Variable Retransmit Menu
- 166 Heat/Cool Output Retransmit
- 166 Heat/Cool Retransmit Low Process Variable
- 166 Heat/Cool Retransmit High Process Variable
- 167 Cascade Menu
- 167 Cascade Primary Loop
- 167 Cascade Low Set Point
- 167 Cascade High Set Point
- 168 Ratio Menu
- 168 Ratio Master Loop
- 168 Ratio Low Set Point
- 169 Ratio High Set Point
- 169 Control Ratio
- 169 Ratio Set Point Differential
- 169 I/O Tests Menu
- 170 Digital Inputs
- 170 Keypad Test
- 170 Display Test
- 171 Test Digital Output 1 to 20
- 171 Parameters Only Available via Communications
- 171 Alarm Acknowledge
- 171 Alarm Enable
- 172 Alarm Function
- 172 Alarm Status
- 173 Ambient Sensor Reading
- 174 Heat/Cool Output Action for Watchdog Inactivity Fault
- 175 Troubleshooting and Reconfiguring
- 175 When There is a Problem
- 176 Returning a Unit
- 176 Troubleshooting the Controller
- 177 Process Alarms
- 178 Ambient Warning
- 178 Failed Sensor Alarms
- 178 System Alarms
- 179 Other Behaviors
- 180 Reading the DeviceNet Indicator Lights
- 181 Corrective and Diagnostic Procedures
- 181 Low Power
- 181 Battery Dead
- 182 H/W Error: Gain or Offset
- 183 H/W Error: Ambient
- 184 Keys Do Not Work
- 184 Checking Analog Inputs
- 185 Earth Grounding
- 186 Testing Control Output Devices
- 186 Testing the TB18 and TB50
- 186 Testing Control and Digital Outputs
- 187 Testing Digital Inputs
- 187 Clearing the RAM
- 188 Replacing the Flash Memory Chip
- 190 Installing Scaling Resistors
- 190 Input Circuit
- 191 Current Inputs
- 192 Voltage Inputs
- 193 RTD Inputs
- 194 Scaling and Calibration
- 194 Configuring Serial DAC Outputs
- 195 Configuring Dual DAC Outputs
- 197 Specifications
- 197 System Specifications
- 197 Physical Specifications
- 203 Inputs
- 205 Outputs
- 207 Power Supply
- 209 Dual DAC Specifications
- 210 Dual DAC Inputs
- 210 Dual DAC Analog Outputs
- 211 Serial DAC Specifications
- 212 Serial DAC Inputs
- 213 Serial DAC Analog Outputs
- 215 Glossary
- 223 Index
- 231 Menu Structure