Tower Wiring Installation. Eaton 9130L-3000T-XL, 9130-1000RM 2U, 9130-1000L, 9130i700T-XL, 9130-2000RM 2U, 9130-1500RM 2U, 9130i1500R-XL2U, 9130i1500T-XL, 9130i1000R-XL2U, 9130i1000T-XL
Advertisement
Advertisement
INSTALLATION
Tower Wiring Installation
This section explains:
S
Installing the UPS, including connecting the UPS internal batteries
S
Connecting any optional EBMs
Installing the UPS
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty.
NOTE Do not connect the UPS power cord to utility until after installation is completed.
To install the UPS:
1.
Remove the UPS front cover (see Figure 14).
To remove the cover, push down on the top of the cover and pull the cover toward you to unclip it from the cabinet.
NOTE A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it.
NOTE Leave ribbon cable connected.
30
Figure 14. Removing the UPS Front Cover
Eaton ® 9130 UPS (700–3000 VA) User's Guide
S
164201718 Rev 3 www.eaton.com/powerquality
INSTALLATION
C A U T I O N
A small amount of arcing may occur when connecting the internal batteries. This is normal and will not harm personnel. Connect the cables quickly and firmly.
2.
Connect the internal battery connector (see Figure 15).
Connect the white connectors together, connecting red to red, and black to black. Press the two parts tightly together to ensure a proper connection.
Figure 15. Connecting the UPS Internal Batteries
3.
Remove the two screws from the screw mounts and retain (see
4.
Place the battery connector between the screw mounts. Reinstall the two screws to hold the connector in place.
5.
Replace the UPS front cover.
To replace the cover, verify that the ribbon cable is protected, then insert the clips on the back of the cover into the cabinet and push firmly to snap the cover into place.
Eaton ® 9130 UPS (700–3000 VA) User's Guide
S
164201718 Rev 3 www.eaton.com/powerquality 31
INSTALLATION
32
6.
If you are installing power management software, connect your computer to one of the communication ports or optional
connectivity card (see page 53). For the communication ports, use
an appropriate cable (not supplied).
7.
If an emergency power-off (disconnect) switch is required by local
codes, see “Remote Emergency Power-off” (REPO) on page 56 to
install the REPO switch before powering on the UPS.
8.
If you are installing EBM(s), continue to the following section,
“Connecting the EBM(s).” Otherwise, continue to “UPS Initial
Connecting the EBM(s)
To install the optional EBM(s) for a UPS:
1.
On the rear of the UPS, remove the cable retention clip covering
the battery connector. Retain the clip and screws. See Figure 16.
2.
Installations with one EBM only. Remove the cable retention clip covering the right (for 1000–1500 VA models) or upper (for
2000–3000 VA models) battery connector. Retain the clip and screws.
3.
Installations with more than one EBM. For all EBMs except the last
EBM, remove the cable retention clips covering both battery connectors. Do not remove the clip from the second battery connector on the last EBM. Retain the clips and screws.
C A U T I O N
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.
4.
Plug the EBM cable(s) into the battery connector(s) as shown in
Figure 16. Up to four EBMs may be connected to the UPS.
5.
For each cable retention clip removed, rotate the clip and install it under each EBM cable connection using the retained screws.
6.
Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable.
7.
Continue to “UPS Initial Startup” on page 34.
Eaton ® 9130 UPS (700–3000 VA) User's Guide
S
164201718 Rev 3 www.eaton.com/powerquality
INSTALLATION
Remove cable retention clip.
Plug in EBM cable. Rotate clip.
Reinstall cable retention clip.
1000–1500 VA Models
2000–3000 VA Models
Figure 16. Connecting the EBMs
Eaton ® 9130 UPS (700–3000 VA) User's Guide
S
164201718 Rev 3 www.eaton.com/powerquality 33
Download
Advertisement