Specifications. HP R7000

Add to My manuals
62 Pages

advertisement

Specifications. HP R7000 | Manualzz

Specifications

UPS physical specifications

Parameter Value

Height

Depth

Width

Weight

Ambient operation

17.1 cm (6.75 in)

73.4 cm (28.9 in)

43.7 cm (17.2 in)

75 kg (165 lb)

0~40°C

ERM physical specifications

Parameter

Height

Depth

Width

Weight

Value

12.7 cm (5 in)

71.9 cm (28.3 in)

43.8 cm (17.24 in)

63 kg (139 lb)

UPS input specifications

NOTE: An asterisk (*) indicates the default setting.

UPS model

R7000 NA/JPN

R7000 INTL

Utility voltage frequency (Hz)

50/60

50/60

Available settings utility voltage (VAC)

200/208*/220/230/

240

Dedicated branch circuit rating (A)

40

50 low input

200/208/220/230*/

240

32

Line cord

Nondetachable power cord with NEMA

CS8265C plug

Nondetachable power cord with 32 A IEC-309 plug

UPS output specifications

UPS model Load segment

Circuit breaker

R7000 NA/JPN 1 20 A¹

Output receptacles Maximum current

2 x IEC-320-C19

2 x IEC-320-C13

16 A per receptacle²

10 A per receptacle

Specifications 50

UPS model Load segment

2

Circuit breaker

20 A¹

Output receptacles Maximum current

1 x L6-30R

2 x IEC-320-C19

Up to full UPS power rating

16 A per receptacle²

2 x IEC-320-C13 10 A per receptacle

R7000 INTL 1 20 A¹ 2 x IEC-320-C19

2 x IEC-320-C13

16 A per receptacle²

10 A per receptacle

2 20 A¹

1 x IEC-309-32A

2 x IEC-320-C19

Up to full UPS power rating

16 A per receptacle²

2 x IEC-320-C13 10 A per receptacle

1

2

The circuit breakers protect the C19 and C13 outlets.

If an extension bar is connected to a C19 receptacle, the maximum current for each C13 receptacle on the extension bar is 10 A. The total maximum current for the extension bar is 12 A.

Power protection specifications

UPS model

R7000 NA/JPN

VA

7200

Nominal power rating (W)

7200

R7000 INTL 6500 6500

Nominal voltage setting

200/208, 220,

230, 240

220, 230, 240

Voltage specifications

Configuration setting (VAC)

200/208

220

230

240

Available nominal output voltage

(VAC)

204

220

230

240

Output tolerance specifications

Source of power Regulation

Utility power (nominal range)

Battery power

-10% to +6% of nominal output voltage rating

(within the guidelines of the Computer Business

Equipment Manufacturers Association)

±5% of nominal output voltage rating

Output feature specifications

Feature

Online efficiency

Specification

94% nominal input voltage

Specifications 51

Feature

Voltage wave shape

Surge suppression

Noise filtering

Specification

Sine wave; 5% THD with typical PFC load

High-energy 6500 A peak

MOVs and line filter for normal and common mode use

Battery specifications

Feature Specification

Type

Voltage

Charging

Each model contains maintenance-free, sealed, valve regulated lead-acid batteries with an 8-year minimum float service life at 25°C (77°F).

The battery modules have a battery string voltage of 216 V.

Complete charge takes no more than 48 hours.

Approximately 3 hours to 80 percent capacity at default nominal utility voltage and no load.

Average battery runtime

Average battery runtimes are approximate and vary depending on connected equipment, configuration, battery age, temperature, and so on. These estimates are based on the batteries at beginning of life.

Load % Estimated battery runtime (minutes)

NA/JPN

Runtime with one

ERM (minutes)

INTL NA/JPN

Runtime with four

ERMs (minutes)

INTL NA/JPN INTL

20

50

80

100

52

13

6

4

62

15

7

5

98

33

18

13

117 301

37 103

21 57

15 39

359

115

66

50

Minimum battery runtime

Minimum battery runtimes are at beginning of life.

Load % Internal battery runtime

(minutes)

Runtime with one

ERM (minutes)

NA/JPN INTL NA/JPN

20

50

80

100

5

3

42

10

6

4

50

12

80

27

16

11

Runtime with four

ERMs (minutes)

INTL NA/JPN

95 240

30 80

18 52

13 35

INTL

300

95

60

45

Specifications 52

Environmental specifications

Feature Specification

Operating temperature 10°C to 40°C (50°F to 104°F); UL-tested at 25°C

(77°F)

Nonoperating temperature

-25°C to 55°C (-13°F to 131°F)

Relative humidity

Operating altitude

20% to 80%; noncondensing

Up to 2,000 m (6,600 ft) above sea level

Nonoperating altitude

Audible noise

15,000 m (49,212 ft) above sea level

Less than 50 dBA, normal operation

Less than 55 dBA, on battery power

REPO port specifications

The REPO port meets the requirements of NFPA Articles 645-10 and 645-11 for a Disconnecting Means.

Specifications 53

advertisement

Key Features

  • Advanced power management capabilities
  • Robust construction
  • User-friendly operation
  • Protects critical equipment from power outages, voltage fluctuations, and other power problems
  • Ideal solution for data centers, telecom networks, and other mission-critical applications

Related manuals

Frequently Answers and Questions

What is the purpose of the REPO port?
The REPO port is used to connect an optional remote EPO (emergency power off) switch.
How do I configure the UPS Network Module?
You can configure the UPS Network Module using a terminal emulation program or through the web interface.
How do I connect the UPS to utility power?
Connect the UPS to utility power using the provided power cord.