Connect Refrigerant Lines. Whirlpool W4GH6, GOLD W4GH6

Add to My manuals
20 Pages

advertisement

Connect Refrigerant Lines. Whirlpool W4GH6, GOLD W4GH6 | Manualzz

17. Install the valve cores.

A

B

18. Install the R-410A thermal expansion valve specified for this system in the indoor coil.

NOTE: R-410A systems use only thermal expansion valves.

19. Pressurize the lines and indoor coil with a pressure not to exceed 20 psig.

20. Leak test the lines with a pressure not to exceed 20 psig.

21. Open the suction and liquid service valves fully.

22. Insulate the suction line with refrigerant line insulation material of ¹⁄₄" or more wall thickness.

23. Pack insulating material around refrigerant lines where they penetrate the structure to protect the lines and to minimize vibration transmission.

A. Suction pressure tap

B. Liquid pressure tap

Connect Refrigerant Lines

Refrigerant lines must be connected by a licensed, EPA certified refrigerant technician in accordance with established procedures.

Thermal Expansion Valve Installation

A

IMPORTANT:

■ Connecting refrigerant lines must be clean, dehydrated, refrigerant-grade copper lines. Heat pumps should be installed only with specified line sizes for approved system combinations with elevation differences up to 15 ft and total length of up to 50 ft. See the Suction Line Sizes and Liquid

Line Sizes charts later in this section.

F

Avoid sharp bends or possible kinking in the refrigerant lines during installation as this may cause a reduction in performance.

Use care with the refrigerant lines during the installation process. Sharp bends or possible kinking in the lines will cause a reduction in performance.

A. Distributor

B. Teflon ® seal

C. Thermal expansion valve

E

■ To avoid contamination of the refrigerant system, do not remove the caps from the lines or system connection points until connections are ready to be completed.

To install the thermal expansion valve:

1. Separate the distributor assembly.

D

B

D. Liquid line stub

E. Strainer

F. Teflon ® seal

Install Thermal Expansion Valve

C

2. If a piston orifice is installed, remove the piston orifice and old

Teflon ® seal and discard.

W4GH6 heat pumps are designed for use with thermal expansion valve systems only. An R-410A system will not operate properly with an R-22 thermal expansion valve.

Thermal expansion valves equipped with Chatleff-type fittings are available from the manufacturer. See Thermal Expansion Valve

Kits chart in “System Requirements.”

3. Insert nozzle end of the thermal expansion valve along with a new Teflon ® seal into the distributor.

4. Tighten to 20 to 30 ft lbs. Use backup wrench on all wrench flats.

NOTE: Overtightening may crush the Teflon ® seal and cause a leak.

5. Attach liquid line portion of distributor assembly along with new Teflon ® seal to the inlet of the thermal expansion valve.

®Teflon is a registered trademark of E.I. Dupont de Nemours and

Company.

6

6. Tighten to 20 to 30 ft lbs. Use backup wrench on all wrench flats.

NOTE: Overtightening may crush the Teflon ® seal and cause a leak.

7. Connect the external equalizer line to the equalizer port on the suction line.

8. Tighten to 8 ft lbs.

9. Attach the superheat sensing bulb to the suction header with the strap provided with the thermal expansion valve.

A B

F

E

D

C

A. Equalizer port

B. Superheat sensing bulb

C. Thermal expansion valve

D. Liquid line

E. Suction line

F. Equalizer line

NOTE: If installing a thermal expansion valve on an indoor coil that previously used a fixed orifice, be sure to remove the existing fixed orifice. Failure to remove a fixed orifice when installing a thermal expansion valve to the indoor coil may result in improper operation and damage to the system.

Connect Liquid and Suction Lines

1. Route the suction and liquid lines from the fittings on the indoor coil to the fittings on the heat pump. Run the lines in as direct a path as possible, avoiding unnecessary turns and bends.

2. For product efficiency, be sure that the suction line is insulated over the entire exposed length and that both suction and liquid lines are not in direct contact with floors, walls, ductwork, floor joists, or other piping.

3. Remove valve cores.

4. Wrap the service valves with a wet rag.

5. Connect the suction and liquid lines, using a brazing compound. Braze with an alloy of silver or copper and phosphorus with a melting point above 1,100°F.

NOTE: Do not use soft solder.

6. Make sure indoor coil has been put in place according to the

Installation Instructions and is connected to the refrigerant lines.

7. Replace valve cores.

8. Pressurize the lines and indoor coil with a pressure not to exceed 20 psig.

9. Leak test the lines with a pressure not to exceed 20 psig.

10. Evacuate the indoor coil and lines to a minimum of

500 microns to remove contamination and moisture, then disconnect the vacuum pump.

11. Open the suction and liquid service valves fully.

12. Insulate the suction line with refrigerant line insulation material of ¹⁄₄" or more wall thickness.

13. Pack insulating material around refrigerant lines where they penetrate the structure to protect the lines and to minimize vibration transmission.

Refrigerant Charge

Refrigerant lines must be connected by a licensed, EPA certified refrigerant technician in accordance with established procedures.

IMPORTANT:

Refrigerant charge adjustment will be required for line set lengths greater than 15 ft and for evaporator coils not matched to the systems.

The heat pump is factory charged with the proper refrigerant charge amount for a matching evaporator and 15 ft of refrigerant line. Refer to the heat pump rating plate for the exact amount of this factory charge.

Adjustment of the refrigerant charge will be necessary based on the system combination and line length. To adjust the refrigerant size for increased line lengths, add the following amount of refrigerant.

For line set lengths greater than 15 ft, add refrigerant by weighing in 0.60 oz per ft of ³⁄₈" O.D. liquid line.

If necessary, adjust the refrigerant charge for compatibility with the evaporator coil.

In heat pump systems, horizontal suction lines should be slightly sloped toward the heat pump. Piping must avoid dips or low spots, which can collect oil.

Check Charge Using Normal Operating Pressures

Use Normal Operating Pressures chart to perform maintenance checks.

NOTES:

■ The Normal Operating Pressures chart is not a procedure for charging the system.

Minor variations in these pressures may be due to differences in installations.

Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.

7

Normal Operating Pressures

NOTE: Values provided in chart are typical pressures. Indoor unit matchup, indoor air quality and indoor load will cause pressures to vary.

Model

Temperature of the Air

Entering the Outdoor Coil

-24

Liquid

Cooling—1st Stage (Low Capacity)

Suction

-36

Liquid Suction

-48

Liquid Suction

-60

Liquid Suction

65ºF

75ºF

85ºF

95ºF

105ºF

232

264

307

353

403

115ºF 460

Cooling—2nd Stage (High Capacity)

146

148

149

151

153

155

225

261

302

349

397

461

144

147

149

151

153

157

235

268

310

356

407

466

144

145

147

148

150

152

225

264

305

352

405

459

138

141

142

146

148

150

65ºF

75ºF

85ºF

95ºF

105ºF

240

279

322

371

423

115ºF 485

Heating—1st Stage (Low Capacity)

40ºF 337

143

145

147

149

151

154

239

278

322

367

426

489

139

141

143

146

148

151

244

283

326

374

427

491

140

141

144

147

148

151

241

280

324

373

425

486

134

136

137

138

142

146

93

117

328

333

98

118

369

366

75

114

351

335

63

92 50ºF 322

Heating—2nd Stage (High Capacity)

20º

30ºF

40ºF

50ºF

279

288

302

306

62

76

93

112

296

309

322

336

62

75

92

113

311

334

354

381

58

72

89

108

308

323

318

329

59

70

69

82

8

advertisement

Related manuals