Addendum- Nominal curent up to 50A and shortwave infrared applications. Eurotherm TE10S DC Input, TE10
Add to my manuals
20 Pages
advertisement
Solid State Contactors TE10S
Power Controllers TE10A
ADDENDUM
TE10S User Manual Part N
°
:
HA174780ENG, HA174782ENG,
HA174784ENG, HA175436ENG
TE10A User Manual Part N
°
:
HA175247ENG, HA175548ENG
NOMINAL CURRENT UP TO 50 A and
SHORT WAVE INFRARED APPLICATIONS
ε
E U R O T H E R M
© Copyright Eurotherm Automation S.A. 1997
All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm Automation
SA.
Part N
°
. HA175600 ENG - Issue 2.0 - 12/98
TECHNICAL SPECIFICATION
2
MAXIMUM CURRENT
In order to take into account supply voltage variations and heating element resistance dispersion (all types of heating elements including short wave infrared), a 0.8 safety coefficient must be used on the thyristor unit current rating to determine the maximum value of the load nominal current which the unit can safely control.
SHORT WAVE INFRARED (SWIR) APPLICATIONS
Applications using short wave infrared heaters in Single Cycle,
Fast Cycle or Advanced Single Cycle are reserved to 16 A, 25 A and 40 A current rating.
With a safety coefficient of 0.8 the maximum current for SWIR which can be controlled is:
TE10 rating SWIR maximum
controlled current
16 A
25 A
40 A and 50 A
13 A
20 A
32 A
Addendum TE10 (50A/SWIR)
RANGE DIMENSIONS AND WEIGHT
Height 115 mm / Depth 92.5 mm
Models Nominal
current
Width
(mm)
TE10S/DC, TE10S/AC
TE10S/PDSIO
16 A
25 A
40 A
50 A
35
52.5
87.5
105
TE10S/PLF
TE10A/Burst
TE10A/PA
16 A
25 A
40 A
50 A
52.5
70
105
122.5
Weight
(g)
350
500
850
1100
550
700
900
1200
THYRISTOR PROTECTION FUSE
TE10 rating
16 A
25 A
40 A
50 A
Fuse rating
20 A
32 A
50 A
63 A
Fuse & fuse-holder
Code Dimensions(mm)
FU1038/16A/00
FU1038/25A/00
FU1451/40A/00
FU2258/50A/00
81 x 17.5 x 68
81 x 17.5 x 68
95 x 26 x 86
140 x 35 x 90
Attention!
For SWIR applications, the high-speed fuse must not be used
Addendum TE10 (50A/SWIR) 3
4
60
I
RMS (A)
50
I N = 50 A
I N = 40 A
40
30 I
N
= 25 A
20
I
N
= 16 A
10
0
20 25 35 40 45 50 55 60
Operation tempereature (°C)
65 70 30
Current derating as a fonction of ambient temperature (I
N
45 ° C)
= nominal current at
Dotted line : limit due to recommended fuse
Addendum TE10 (50A/SWIR)
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 6 INSTALLATION AND USE SAFETY
- 7 TECHNICAL SPECIFICATIONS
- 8 MOUNTING SPECIFICATIONS
- 9 INPUT SIGNAL
- 10 FRONT VIEW
- 11 TERMINALS AND CONNECTORS
- 12 SINGLE-PHASE WIRING
- 13 THREE-PHASE WIRING 2 phase control
- 14 3 phase control
- 15 ORDERING CODE
- 16 DERATING CURVES
- 17 Addendum- Nominal curent up to 50A and shortwave infrared applications