Replacing GFDI fuse
Safety
WARNING! An electric shock can be fatal. Danger from grid voltage and DC voltage from solar modules.
The connection area should only be opened by a licensed electrician.
Never work with live wires! Prior to all connection work, make sure that the
AC and DC wires are not charged.
The DC main switch is used only to switch off power to the power stage set.
When the DC main switch is turned off, the connection area is still energized.
These servicing instructions are for use by qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that specified in the operating instructions.
WARNING! An electric shock can be fatal. Danger from residual voltage from capacitors.
You must wait until the capacitors have discharged. Discharge takes 5 minutes.
WARNING! An electric shock can be fatal. Normally grounded conductors may be ungrounded and energized when a ground fault is indicated. The ground fault has to be repaired before operation is resumed.
Preparation
1
2
NOTE! Disconnect AC and DC supply from the inverter.
2
1 on off
OFF
AC
3
4
1
2
148
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 102 Navigation in the Menu Level
- 102 Activating display illumination
- 102 Accessing the Menu Level
- 103 The Display Modes
- 103 Selecting a Display Mode
- 104 Overview of Display Values
- 105 Display Values in "Now" Display Mode
- 105 Selecting the "Now" Display Mode
- 105 Display values in the ‘Now’ display mode
- 106 Options
- 107 Display Values in "Day / Year / Total" Display Modes
- 107 General
- 107 Selecting "Day / Year / Total" Display Mode
- 108 Display values in the ‘Day / Year / Total’ display modes
- 109 Options
- 110 The Setup Menu
- 110 Presetting
- 110 Accessing the Setup Menu
- 111 Scrolling through Menu Items
- 112 Menu Items in the Setup Menu
- 112 STANDBY
- 112 CONTRAST
- 113 LIGHT MODE
- 114 YIELD
- 114 IG no
- 115 DAT COM
- 115 STATE PS
- 116 VERSION
- 117 Setting and Displaying Menu Items
- 117 Setting Menu Items - General
- 117 Examples of Setting and Displaying Menu Items
- 118 Setting the currency and rate
- 120 Displaying and Setting Parameters in the "DATCOM" Menu Item
- 121 Setting Time and Date
- 124 Setup Lock function
- 124 General
- 124 Activating/deactivating the "Setup Lock" function
- 129 Status Diagnosis and Troubleshooting
- 129 Displaying Status Codes
- 129 Normal Operation Status Codes
- 129 Total Failure
- 129 Status Codes on Fronius IG Plus with Several Power Stage Sets
- 130 Class 1 Status Codes
- 132 Class 2 Status Codes
- 133 Class 3 status codes
- 134 Class 4 status codes
- 141 Class 5 status codes
- 144 Customer Service
- 145 Maintenance
- 145 Safety
- 145 General
- 145 Operation in Dusty Environments
- 146 Opening Fronius IG Plus for service/maintenance
- 147 Replacing String Fuses
- 147 Safety
- 147 Preparation
- 148 Replacing string fuses
- 149 Closing Fronius IG Plus
- 150 Replacing GFDI fuse
- 150 Safety
- 150 Preparation
- 151 Replacing GFDI fuse
- 152 Closing Fronius IG Plus
- 155 Technical Data
- 155 Fronius IG Plus V
- 161 Fronius IG Plus V
- 175 Field adjustable trip points
- 176 Relevant Standards and Directives
- 176 Relevant standards and directives
- 176 Grid Failure
- 177 Warranty and Disposal
- 177 FRONIUS USA limited 10-year warranty
- 177 Policy and procedure for warranty returns and repairs
- 178 Disposal