Appendix Function Parameter List. Panasonic MK300
تبلیغات
تبلیغات
Appendix
Function Parameter List
99
Appendix Function Parameter List
P001
The 1st Acceleration Time
The time to accelerate from 0.2 Hz to the maximum output frequency can be set.
Data setting range (s) 0.04·0.1~3600
Increment (s)
0.1(0.1~999.9)、
1(1000~3600)
· The display code for “0.04 s” is “0.0”.
· The maximum output frequency can be set with parameter P009 and P012.
· Please note that if the acceleration time setting is too small, overcurrent may occur depending on the load.
Related parameters: P009, P012
100
Appendix Function Parameter List
P002
The 1st Deceleration Time
The time to decelerate from the maximum to 0.2 Hz output frequency can be set.
Data setting range (s) 0.04·0.1 ~ 3600
Increment (s)
0.1(0.1 ~ 999.9)、
1(1000 ~ 3600)
· The display code for “0.04 s” is “0.0”.
· The maximum output frequency can be set with parameter P009 and P012.
· Please note that if the deceleration time setting is too small, overcurrent may occur depending on the load.
Related parameters: P009, P012
101
Appendix Function Parameter List
P003
Run Command Selection
Run/stop and forward/reverse run can be selected via the operation panel, the signal input from external control device or the communication commands.
Setting value
Command status
Panel reset function
Operation method and control circuit terminal connection diagram
RUN : RUN, STOP : STOP
Enabled / (Forward/reverse): can be set in the Rotation
Direction Setting mode (dr mode)
+
RUN
: Forward Run,
Enabled
STOP
: STOP
+
RUN
: Reverse Run,
Commom terminal
(Terminal No.⑦)
ON: Run /OFF: Stop
ON: Reverse /OFF: Forward
Commom terminal
(Terminal No.⑦)
ON: Forward run/OFF: Stop
ON: Reverse run/OFF: Stop
Disabled Make run command transmitted through communication valid.
■ Panel Reset Function
After an abnormal tripping, if the stop signal from external operation cannot reset it, use the
STOP
button on the operation panel to make a reset. However, if the reset lock function is enabled, the reset lock function shall take precedence, yet the reset function is also valid.
(*1): Set the “SW1~6”Function Selection of parameters P101
~
P106 to the setting values of “16(r16): Run/Stop” and “17(r17): Forward/Reverse”.
102
Appendix Function Parameter List
■ 3-wire run/stop command
Please assign the “3-wire stop command” to any one of the input terminals of
SW1 to SW6.
Setting value
Command status
Panel reset function
Operation method and control circuit terminal connection diagram
2
3
External control
External control
Disabled
Enabled
Commom terminal
(Terminal No.⑦)
ON: Run
ON: Reverse/OFF: Forward
ON: Stop (*1)
4
5
External control
External control
Disabled
Enabled
Commom terminal
(Terminal No.⑦)
ON: Forward run
ON: Reverse run
ON: Stop (*1)
(*1) Set the “SW1~6”Function Selection of parameters P101 to P106 to the setting values of “16(r16): Run/Stop” and “17(r17): Forward/Reverse”.
(*2) If any terminal of SW1 to SW6 is used as “3-wire stop command”, please set their corresponding parameters P101 to P106 to “11 or r11”
(*3) When 3-wire mode is used, “a” contact input shall apply.
(*4) When 3-wire mode is used, “b” contact input shall apply.
When P003 is set to “2 or 3”. When P003 is set to “4 or 5”.
Forward
Forward
Time
Time
Reverse
SW1
(P101 = 16)
SW2
(P102 = 17)
SW3
(P103 = 11)
ON
ON
ON
Reverse
SW1
(P101 = 16)
SW2
(P102 = 17)
SW3
(P103 = 11)
ON
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
· The operation status will not change if the forward run and reverse run signals are both “ON”. But if it is in a stop mode, it will not operate even if the signals are both ON.
Related parameters: P101 to P106
103
Appendix Function Parameter List
P004
Frequency Setting Signal
The frequency setting signal can be set via the operation panel, the signal input from external devices or the communication command.
Setting value
0
Command status
Panel
1
2
3
4
5
External control
Panel reset function
Operation method and control circuit terminal connection diagram
Digital setting Can be set in the “Frequency Setting Mode (Fr)”
Potentiometer
VR input
0~5V
(Voltage signal)
0 ~10V
(Voltage signal)
4~20mA
(Current signal)
0~20mA
(Current signal)
Terminal AK, AL and AN, (center of potentiometer is connected to Terminal AL).
Terminals AL and AN (12: +, 14: -)
Terminals AL and AN (12: +, 14: -)
Terminals AL and AN (12: +, 14: -)
Terminals AL and AN (12:+, 14:-)
Enable the frequency command transmitted via communication.
7 PWM signal input Terminal No. 6 and No. 7 (6: +, 7: -)
External control
8 Pulse input Terminal No. 6 and No. 7 (6: +, 7: -)
· When the setting value is set to “1” to “5”, the inverter will run or stop as defined by the setting value of “P047: 0V Stop Function Selection”. If 0V Stop
Function is set to invalid, parameter P047 should be set to “0.0”.
Related parameters: P009, P012, P047, P109 to P113
104
Appendix Function Parameter List
P005
Operation Status Monitoring
The display on the panel can be changed according to its purpose.
Setting value
Function Name
LED display
Operation
Preparation Status
(in Stop mode)
Operation Status
3 Communication station No.
5
6
7
8
* The display example shown in the above Table, where the operation frequency is “50.0” , the output current is “1.0A”, the setting frequency is “50.0”, the communication station No. is
“01”, the linear speed multiplier is “0.5”, and the winding length is “10.00”.
Communication station
No./Output frequency
Communication station
No./Linear speed
Communication station No./
Output current
Winding length (the same as n022)
· When in the Operation Status Display mode, press the current display.
button to switch to
· The operation preparation status recorded in this Manual is “0000”, the display will change based on the setting value when this parameter is changed.
Related parameters: P054
105
Appendix Function Parameter List
P006
Vector Control Selection
This function is effective for the case that the load fluctuates sharply when high start-up torque or sufficient torque at lower speed is required. But it is not applicable to the load whose minor rotation may cause problems at lower speed.
Setting value
Details
If it is set to the vector control mode, please carefully read “4.15: Vector
Control” and follow the precautions to set various parameters.
P007
Carrier Frequency
To reduce the motor noise and avoid the machine resonance, you may change the carrier frequency.
■ “P006: Vector Control Selection” is set to “0” (when V/F control is selected)
Setting value (kHz) 0.8, 1.1, 1.6, 2.5, 5.0, 7.5, 10.0, 12.5, 15.0 (9 values are optional)
■ “P006: Vector Control Selection” is set to “1” (when sensorless V/F control is selected)
Setting value (kHz) 2.5, 5.0, 7.5, 10.0, 12.5, 15.0 (6 values are optional)
· Please carefully read “Chapter 7: Relationship between Carrier Frequency and Rated Current” before you change the carrier frequency.
106
Appendix Function Parameter List
P008
S-shape Acceleration/Deceleration Mode
The acceleration/deceleration mode can be switched between linear and
S-shaped (quadratic and cubic) pattern.
Setting value
0
1
2
Details
Linear acceleration/deceleration (Factory setting)
S-shaped acceleration/deceleration
(Quadratic curve)
S-shaped acceleration/deceleration
(Cubic curve)
· The acceleration/deceleration time remains the same regardless of the acceleration/deceleration mode (linear or s-shaped acceleration/deceleration).
Related parameters: P001, P002, P317 to P322
107
Appendix Function Parameter List
P009
V/F Control
V/F mode of “50· 60 Hz” and “0.2 to 400 Hz” can be set separately within the maximum output frequency band (50 ~ 400 Hz).
Setting value
Name Details
V/F mode of 50 Hz is set regardless of parameter P012 and
P013 setting.
V/F mode of 60 Hz is set regardless of parameter P012 and
P013 setting.
V/F mode can be set via parameter P012 and P013. Set the maximum output frequency via parameter P012 and the base frequency via parameter P013.
3-point V/F mode can be set via parameter P012 to P017.
Set the maximum output frequency via parameter P012 and the base frequency via parameter P013.
Set the change point frequency 1 via parameter P014 and the change point voltage 1 via parameter P015.
Set the change point frequency 2 via parameter P016 and the change point voltage 2 via parameter P017.
3C1 3-point fixed mode 1 Set value for the fixed mode via parameter P013 to P017.
3C2 3-point fixed mode 2 Set value for the fixed mode via parameter P013 to P017.
3C3 3-point fixed mode 3 Set value for the fixed mode via parameter P013 to P017.
3C4 3-point fixed mode 4 Set value for the fixed mode via parameter P013 to P017.
3C5 3-point fixed mode 5 Set value for the fixed mode via parameter P013 to P017.
3C6 3-point fixed mode 6 Set value for the fixed mode via parameter P013 to P017.
108
Appendix Function Parameter List
If 3-point V/F mode is used, please set each parameter according to the following diagram.
(Also apply to the 2nd characteristic).
109
Appendix Function Parameter List
· Settings for 3C1 to 3C6 will not affect the 2nd characteristics.
· Factory settings of maximum output frequency and base frequency are both
50Hz.
· Please consider the setting of Upper Frequency Limit (parameter P046) when changing the maximum output frequency.
· In free mode or 3-point mode, please note that sharp acceleration/deceleration or overcurrent may occur depending on setting values and load state if change point frequency and voltage are changed during operation.
· If change point frequency 1 or 2 is set to a value higher than the base frequency, the invert will still operate according to the base frequency setting.
· If change point frequency 2 is set to a value lower than change point frequency 1, it will operate according to the setting of the latter one.
· If change point voltage 1 or 2 is set below the torque boost value, it will operate according to the setting value of “P011: Torque Boost”.
· If change point voltage 2 is set to a value lower than change point voltage 1, it will operate according to the setting of the latter one.
· In 3-point mode, V/F curve (P010) corresponds to constant torque mode. Even if the setting is square torque mode, constant torque mode still applies.
· It is invalid during vector control (P006 = “1”).
Related parameters: P011 to P017, P046
110
Appendix Function Parameter List
P010
V/F Curve
Constant or square torque mode can be selected.
Setting value
0
1
Name
Constant torque mode
Square torque mode
Remarks
For machine applications, etc.
For fan and pump applications, etc.
· If “P009: V/F Mode” is set to “3C”, “3C1 to 3C6”, V/F curve will correspond to constant torque mode.
Even if the setting is square torque mode, constant torque mode will still apply.
· It is invalid during vector control (P006 = “1”).
Related parameters: P009, P013
111
Appendix Function Parameter List
P011
Torque Boost
Torque boost level corresponding to load characteristics can be set. The larger the setting value is, the higher output voltage and torque boost will be.
· After the mode is set to “auto torque boost”, the output voltage will change automatically according to the load fluctuation. To set “Auto torque boost”, please clockwiswly rotate once when the operation panel displays “40”.
Name
Auto torque boost
Manual torque boost
Data setting range
(%)
Auto
0~40%
Method of increasing torque at lower speed
· If higher torque is required at lower speed, the torque boost level can be set to a larger value, thus generating higher output voltage to increase the torque.
· If the boost level setting is too high, it may cuase overcurrent fault, overload fault, motor overheating or excessive noise.
· The motor current will rise after the boost level increases. Please carefully consider the settings for “P023: Electronic Thermal Selection” and “P024:
Thermal Current Setting”.
· Once it is set to “vector control”, the settings for parameter “P006: Vector
Control Selection =1” and parameter “P011: Torque Boost” will become invalid.
· If auto torque boost mode is selected, be sure to conduct auto-tuning and use the inverter with correct setting of the motor constants.
(Please carefully read “4.14: auto-tuning” for the details of auto-tuning.)
112
Appendix Function Parameter List
P012
P013
Max. Output Frequency
Base Frequency
Maximum output frequency and base frequency can be set.
(Parameter P009 is only valid when “FF” or “3C” is set.)
■ Parameter P012: Max. Output Frequency
Data setting range (Hz) 50.0~400.0
■ Parameter P013: Base Frequency
Data setting range (Hz) 45.0~400.0
· If “P009: V/F Mode” is set to “50”, “60” or “3C1 to 3C6”, the maximum output frequency and base frequency will be fixed values.
· A frequency higher than “P046: Upper Frequency Limit” cannot be output.
· If a general-purpose motor with rated frequency of 50/60 Hz is running at a frequency exceeding the ratings, the motor may be damaged. Therefore, please set a frequency that matches with the motor characteristics.
· If base frequency is required to be changed simutaneously with maximum output frequency for a dedicated high-speed motor etc., such change should also be made via this parameter.
· When running a general-purpose motor at a frequency higher than universal frequency, the base frequency setting should not exceed the rated output frequency (50/60 Hz) of the motor.
· When a general-purpose motor reaches a level higher than the base frequency (normally 50/60 Hz), the motor will show constant output characteristics and the generated torque will drop in reverse proportion to the frequency.
· If “P006: Vector Control Selection” is set to “Sensorless Vector Control” mode, the maximum output frequency shall range from 50.0 to 120.0Hz.
Related parameters: P009, P046
113
Appendix Function Parameter List
P014
P015
Change Point Frequency 1
Change Point Voltage 1
P016
P017
Change Point Frequency 2
Change Point Voltage 2
Change point 1 and 2 can be selected in 3C mode of “P009: V/F Mode”.
(It is only valid when parameter P009 is set to “3C”.)
■ ParameterP014:Change Point Frequency 1
Data setting range (Hz) 0.2~400.0
■ ParameterP015:Change Point Voltage1
Data setting range (%) 0.0~100.0
■ ParameterP016:Change Point Frequency 2
Data setting range (Hz) 0.2~400.0
■ ParameterP017:Change Point Voltage 2
Data setting range (%) 0.0~100.0
· Read “P009: V/F Mode” carefully before setting.
· Change point frequency 1 and 2 will operate according to the setting value of the base frequency when set to a value higher than the base frequency.
· Change point frequency 2 will operate according to the setting value of change point frequency 1 when set to a value lower than change point frequency 1.
· When setting “P011: Torque Boost”, change point voltage 1 and 2 will operate according to the setting value of torque boost if set to a value lower than torque boost level.
· Change point voltage 2 will operate according to the setting value of change point voltage 1 when it is set to below change point voltage 1.
· Please note that sharp acceleration/deceleration or overcurrent may occur depending on setting values and load status if data is changed during operation.
· When "3C1" to "3C6" of "P009: V/F Mode" is set, P010 to P013 will change to fixed value automatically, and cannot be changed.
Related parameters: P009, P046, P011 to P013
114
Appendix Function Parameter List
P018
Max. Output Voltage
The msximum output voltage can be set via this parameter.
Data setting range (V) 1~500
*When the data is set to “0”, power voltage value will be output
· A voltage exceeding power supply rating cannot be output.
· This setting has no connection with the DC brake level.
· It is invalid when vector control mode is selected.
Related parameters: P009, P012
115
Appendix Function Parameter List
P019
P020
P021
P022
JOG Frequency
JOG Acceleration
JOG Deceleration
JOG Panel Operation
The operating frequency, acceleration/deceleration time during JOG operation can be respectively set via these parameters.
■ Parameter P019: JOG Frequency
Data setting range (Hz) 0.2~400.0
■ Parameter P020: JOG Acceleration
Data setting range (s) 0.04·0.1~600
Increment (s) 0.1(0.1~999.9), 1(1000~3600)
· The display code for 0.04 is “0.0”.
■ Parameter P021: JOG Deceleration
Data setting range (s) 0.04·0.1~3600
Increment (s) 0.1(0.1~999.9), 1(1000~3600)
· The display code for 0.04 is “0.0”.
■ Parameter P022: JOG Panel Operation
Name
Panel JOG
Operation
Setting value
0
1
2
Details
Panel JOG function is invalid.
Use Panel JOG function (JOG function of the external device is invalid)
Panel JOG function (JOG function of the external device is invalid)
116
Appendix Function Parameter List
Operation Method of Panel JOG Function
① Power on the inverter.
The inverter displays “
0000
” when the power is ON.
②
Press mode.
MODE
button to enter into the Parameter Setting
③ Rotate the knob to “P0: Parameter Setting”.
MODE
④ Press the knob to display parameter P001.
⑤
Rotate the knob to “P022: JOG Panel Operation”.
⑥
Press the knob to proceed to the setting of value for P022.
⑦
Rotate the knob to adjust the value of P022 to “1”.
⑧ Press the knob to apply the setting “1” for P022 and use the Panel JOG function. (adopt the same method to respectively set P019 to “ 10.0
”, P020 to “ 5.0
” and
P021 to “5.0” ).
⑨ Press
MODE
button to enter into Forward JOG operation and display “ Jog.F
” .
( Counterclockwisely rotate the knob to switch to Reverse
JOG operation to display “ Jog.r
”)
⑩
Press RUN button to forward accelerate the motor to
10.0Hz and remain at this speed.Loosen
Loosen
RUN
button, the motor will decelerate until it stops.
RUN
· Where the external control JOG function is selected, the operation command must be set to External Control operation (Parameter P003 shall be set to
“2” to “5”).
· Where the external control JOG function is selected, please refer to the related contents of parameters P101 to P106.
· The JOG frequency used in vector control ranges from 0.5Hz to 120.0Hz.
Related parameters: P003, P101 to P106
117
Appendix Function Parameter List
P023
P024
Electronic Thermal Selection
Thermal Current Setting
Electronic thermal operation level can be set when motor overload is detected and the inverter output needs to be stopped.
Operation coasts to stop when OL is displayed.
■ Parameter P023: Electronic Thermal Selection
Setting value
Validity of function
Details of function
1
2
3
Enabled The output frequency is not derated.
Enabled The output frequency is derated.
Enabled Forced air-cooled motor specification
* About frequency derating
The function can automatically compensate operation level when motor cooling performance drops during low-speed operation.
■ Parameter P024:Thermal Current Setting
Data setting range (A) 0.1~100.0
* Please make settings according to the rated current of the applicable motor.
■ Example of setting current and thermal operation (P023=1)
· Setting current×100% Does not operate
· Setting current×125% Operate (OL trip)
118
Appendix Function Parameter List
P025
Overcurrent Stall Prevention Function
· Overcurrent Stall Prevention Function:
During acceleration/deceleration, if acceleration/deceleration time is too short for the inertial load and the output current exceeds OCS level, the parameter serves to extend acceleration/deceleration time.
· Overcurrent Trip Prevention Function:
If overcurrent occurs in the inverter during operation, output will be temporarily stopped and started again when the current drops to normal level.
Name Setting value
Overcurrent
Stall
Prevention
Function
0
1
2
3
Details
Overcurrent Stall Prevention Function: OFF
Overcurrent Trip Prevention Function: OFF
Overcurrent Stall Prevention Function: ON
Overcurrent Trip Prevention Function: ON
Overcurrent Stall Prevention Function: OFF
Overcurrent Trip Prevention Function: ON
Overcurrent Stall Prevention Function: ON
Overcurrent Trip Prevention Function: OFF
· When load fluctuates drastically or the inverter accelerates or decelerates sharply, instantaneous overcurrent may sometimes lead to a trip.
· The operation level of overcurrent stall prevention function can be set via parameter “P028: OCS Level”. The factory setting is 140% of the rated current.
· Overcurrent trip prevention function is activated regardless of the setting of parameter “P025: Overcurrent Stall Prevention Function” after parameter
“P027: Current Limit Function” is set.
· Overcurrent trip prevention function shall be disabled if the sensorless vector control function is selected.
Related parameters: P028
119
Appendix Function Parameter List
P026
Overvoltage Stall Prevention Function
During deceleration, when the deceleration time is too short for the inertial load, this parameter can be used to temporarily retard the deceleration, thus preventing overvoltage trip.
Setting value
0
1
Details
Stall prevention function disabled
Stall prevention function enabled
· When regenerative brake is used in the inverter with braking function, please set the value to “0”.
(The regenerative brake function will be disabled if the factory setting is “1”).
· The specifications of the built-in brake of the inverter are as follows. Please take them into full consideration before its use.
Please note that the braking resistor and inverter could be damaged if used beyond specifications.
(3) Maximum working time: 5s
· Only brake circuit is built in the inverter.
(1) Braking torque: 100%
(2) Maximum duty factor (%ED): 5%
120
Appendix Function Parameter List
P027
Current Limit Function
If the output current reaches the overcurrent stall level (OCS level) during overload operation, the frequency will be automatically reduced. When the load recovers to normal level, the frequency will be automatically restored to the original setting and the operation will continue. This function is effective for preventing overcurrent trips in sticky material crushing machines.
When the function becomes valid/invalid and the output current reaches the overcurrent stall level, deceleration time will be automatically set to lower the frequency.
The operation level (overcurrent stall level) can be set with the parameter
“P028: OCS Level”.
Data setting range (s) 0.0·0.1~9.9
* “0.0” corresponds to a setting without current limit.
· Overcurrent trip prevention function is activated regardless of the setting of parameter “P025: Overcurrent Stall Prevention Function” after parameter
“P027: Current Limit Function” is set.
Related parameters: P025, P028
121
Appendix Function Parameter List
P028
OCS Level
The OCS level (overcurrent stall prevention operation level) and current limit function level can be set with a ratio (%) to the rated current of inverter.
Data setting range (%) 1~200
· The factory setting of OCS level is 140 % of the rated current.
· The OCS level is equivalent to the current limit level.
· It has no connection with the electronic thermal level and the overload detection level.
Related parameters: P025, P027
122
Appendix Function Parameter List
P029
P030
Retry Function Selection
Retry Count
The retry function can automatically reset the fault and restart (run) operation after waiting time has elapsed when an inverter fault trip occurs. Please use this function to continue the operation.
When the retry function is used, the unit may automatically start (restart) suddenly, so do not approach the unit. (Please take measures to ensure personal safety.)
Failure to do so may lead to injury.
■ Parameter P029: Retry Function Selection
Setting value
0
Details
Retry function disabled (retry is not performed.)
1
2
Perform retry operation only for overcurrent fault and heat sink abnormal overheating (OC1/OC2/OC3).
Perform retry operation only for overvoltage fault (OU1/OU2/OU3).
3
Perform retry operation only for overcurrent fault and heat sink abnormal overheating (OC1/OC2/OC3) and overvoltage fault (OU1/OU2/OU3)
■ Parameter P030: Retry Count
Data Setting Range (times) 1~10
123
Appendix Function Parameter List
· The retry interval is set via the parameter “P033: Waiting Time”.
· Fault alarm is not output during retry operation. But when the fault still occurs even if retry is performed for preset times, the fault alarm will be output.
· If an unselected fault occurs during retry, the fault alarm will be output and the retry count accumulated up to now will be cleared.
· Once the power is cut off, the retry count accumulated up to now will be cleared.
· If the fault does not occur for over 5 minutes, the retry times accumulated up to now will be cleared.
· When speed search is selected via parameter “P361: Speed Search
Selection during Retry” and the time set via parameter “P033: Waiting Time” and “P359: Waiting Time to Speed Search” has elapsed, the speed search function will start to operate.
Related parameters: P033
P031
Start Mode
This parameter is used to set the start-up operation for the case that a run signal set externally is input when the power is turned ON.
Depending on the start mode setting, when the run signal is
ON, the inverter may start (restart) suddenly if the power is turned ON or restored after a power failure. Therefore, do not approach the unit. Design the machine so that personal safety can be ensured even if the inverter starts suddenly.
Depending on the start mode function setting, if the fault trip is reset with the run signal ON, the inverter may sometimes restart suddenly. (Please take measures to ensure personal safety.)
Failure to do so may lead to injury.
· The factory setting is "1" (OP stop).
· If the value is set to “0”, operation will start immediately after the power is turned ON.
· If the value is set to "2", operation will start when the power is turned ON and after the waiting time has elapsed.
124
Appendix Function Parameter List
Setting value
Operation
0 Run
Details of operation
Operation starts immediately when the low voltage level (LU level) is exceeded after the power is turned ON.
OP trip occurs when the low voltage level (LU level) is exceeded after the power is turned ON.
Turn the run signal OFF once, perform reset operation and turn the run signal ON again to start operation.
2 elapes turned ON.(The waiting time can be set via parameter P033.)
OP trip occurs when the low voltage level (LU level) is exceeded after the power is turned ON. Turn the run signal
OFF once, perform reset operation and turn the run signal ON again to start operation.
(The setting will function in the same manner as data "1" with run signal ON when the power is turned ON. However, starting after the waiting time has elapsed is possible during normal startup.)
· Waiting time can be set via parameter P033.
Related parameters: P033
125
Appendix Function Parameter List
P032
Ride-through Restart Selection
The restart pattern after constant power failure or instantaneous power supply can be selected according to the load status and system configuration.
A waiting timer function is built-in.
The inverter may suddenly start (restart) if the power is restored after a power failure with the setting of ride-through restart, so do not approach the unit.
Please take measures to ensure personal safety. Failure to do so may result in injury.
Setting value
0
1
2
3
Function
Name
Restart
Mode 1
Restart
Mode 2
Restart
Mode 3
Restart
Mode 4
Inverter operation in regard to instantaneous power failure time
≥ 15 ms
(Note 1)
Operation continues
≥ 15 ms
(Note 1)
≤ 100 ms
(Note 2)
>100 ms
(Note 2)
·LU trip occurs and the inverter operates according to the start mode setting.
·“LU” will be displayed and the fault alarm signal will be output.
·Restart from 0 Hz after the waiting time has elapsed.
·“LU” will be displayed and the fault alarm signal will not be output.
·After the waiting time has elapsed, the inverter restarts at the frequency applied before the ride-through occurrence.
·“LU” will be displayed and the fault alarm signal will be output.
The inverter operates according to the start mode
·After the waiting time has elapsed, the inverter will sense the motor rotation through speed search function and restart at the setting. corresponding frequency. (note 3)
·“LU” will be displayed and the fault alarm signal will be output.
Note 1: This is the minimum time for operation at the rated output current.
(The time may be longer depending on different models.)
Note 2: This is the minimum time. (The time may be longer with higher rated capacity.)
Even if the power failure time is relatively long (approx. 1 min.), the inverter may sometimes restart after the power is restored. Therefore, inverter, motor and load equipments should be restarted after the power is restored for more than 4 minutes (waiting time + 2 minutes).
Note 3: In sensorless vector control, speed search will not be performed and the inverter will operate according to the start frequency setting (P036).
126
Appendix Function Parameter List
· Waiting time can be set via parameter P033.
Related parameters: P033
127
Appendix Function Parameter List
P033
Waiting Time
Waiting time required by the start mode, the ride-through restart and retry function can be set.
Data setting range (s) 0.1~100.0
Related parameters: P029~P032
P034
Reverse Run Lock
When used only in forward run mode, reverse run can be disabled to avoid possible mishandling.
Setting value
0
1
Details
Reverse run operation enabled
(Both forward run and reverse run operation enabled)
Reverse run disabled
(Only forward run operation enabled)
· When disabled, reverse run cannot be performed during the operation of panel, external control and communication.
Related parameters: P004
P035
Start Frequency
The frequency at which the inverter output starts can be set during inverter start-up.
Data setting range (Hz) 0.2~60.0
· Please note that overcurrent may occur depending on setting values and load status if the data is changed during operation.
· In vector control mode, the minimum value is changed to “0.5Hz”.
128
Appendix Function Parameter List
P036
Stop Mode
Ramp-to-stop or coast-to-stop mode can be selected when stopping the inverter.
Setting value
1
Details
0 Ramp-to-stop
Details
The inverter is stopped by the stop signal depending on the frequency decreased according to the deceleration time.
Coast-to-stop The inverter output is shut off immediately by the stop signal.
P037
Stop Frequency
The frequency at which the inverter output stops can be set when the inverter ramps to stop.
Data setting range (Hz) 0.2~60.0
Related parameters: P038 to P039
129
Appendix Function Parameter List
P038
P039
DC Brake Time
DC Brake Level
DC brake can be applied when the inverter output frequency drops below “P037:
Stop Frequency” during ramp-to-stop.
In addition, positioning control can be performed combining with JOG operation.
■ Parameter P038:DC Brake Time
Data setting range (s) 0.0~120.0
* The DC brake is disabled when “0.0” is set.
■ Parameter P039:DC Brake Level
Data setting range (%) 0~100
* The larger the value is, the stronger the braking force is.
· DC brake starts at the frequency corresponding to the setting value of parameter “P037: Stop Frequency”.
· DC brake during the switching between forward run and reverse run is set via parameter “P040: Stop Frequency during Forward/Reverse Run
Operation”, “P041: DC Brake Time during Forward/Reverse Run Operation” and “P042: DC Brake Level during Forward/Reverse Run Operation”.
Related parameters: P037
130
Appendix Function Parameter List
P040
P041
P042
Stop Frequency during Forward/Reverse Run Operation
DC Brake Time during Forward/Reverse Run Operation
DC Brake Level during Forward/Reverse Run Operation
DC brake can be applied when the inverter output frequency drops below
“P040: Stop Frequency during Forward/Reverse Run Operation” during forward/reverse run operation.
■ Parameter P040:Stop Frequency during Forward/Reverse Run Operation
Data setting range (Hz) 0.2~60.0
■ Parameter P041: DC Brake Time during Forward/Reverse Run Operation
Data setting range (s) 0.0~120.0
* The DC brake is disabled when “0.0” is set.
■ Parameter P042: DC Brake Level during Forward/Reverse Run Operation
Data setting range (%) 0~100
* The larger the value is, the stronger the braking force is.
· The frequency for applying the DC brake is set by parameter “P040: Stop
Frequency during Forward/Reverse Run Operation”.
· “P040: Stop Frequency during Forward/Reverse Run Operation” is only valid when DC brake is applied during forward/reverse run operation. (It’s valid when P041 is set to a value other than “0000” )
· To stop the inverter, DC brake can be set via parameter “P037: Stop
Frequency”, “P038: DC Brake Time” and “P039: DC Brake Level”.
131
Appendix Function Parameter List
P043
P044
DC Brake Time at Start-up
DC Brake Level at Start-up
· The coast-to-stop motor can be restarted via this parameter after a pause.
■ Parameter P043: DC Brake Time at Startup
Data setting range (s) 0.0~120.0
■ Parameter P044: DC Brake Level at Startup
Data setting range (%) 0~100
*1: Set P043 to “0.0” to disable the DC brake function when not used.
*2:The larger the value is, the stronger the braking force is.
· The start frequency is specified by parameter “P035: Start Frequency”.
· Please note that sharp acceleration/deceleration or overcurrent may occur depending on the setting values and load status if data is changed during operation.
· When parameter “P357: Speed Search at Startup” is set to “enabled”, the setting value of DC brake set via this parameter is “disabled”.
132
Appendix Function Parameter List
P045
P046
Lower Frequency Limit
Upper Frequency Limit
The upper limit and lower limit of the output frequency can be set.
■ ParameterP045:Lower Frequency Limit
Data setting range (Hz) 0.2~400.0
■ ParameterP046:Upper Frequency Limit
Data setting range (Hz) 0.2~400.0
· When the upper frequency limit is lower than the maximum output frequency
(parameter P012), the upper frequency takes precedence.
· When the lower frequency limit is higher than the upper frequency limit
(reverse run setting), the latter takes precedence.
· The inverter may accelerate/decelerate depending on the setting values when data is changed during operation.
· In vector control mode, the minimum value and the maximum value shall be respectively changed to 0.5Hz and 120Hz.
Related parameters: P009, P012
133
Appendix Function Parameter List
P047
0V Stop Function Selection
When the frequency setting signal is lower than than setting value, the inverter output can be stopped by using 0V stop function.
Data setting range (Hz) 0.0·0.2~400.0
· Setting value “0.0” : 0V stop function disabled.
· Setting value “0.2~400.0” : 0V stop function enabled(0V stop function setting)
■ 0V stop function
· When the frequency signal is set to “analog setting (parameter P004 = “1”,
“2”, “3”, “4” and “5”), the inverter will stop output after the frequency setting signal reaches a value below the setting value of 0 V stop function selection.
· 0 V stop will not be performed if 0 V stop function selection is set to “0.0”.
The inverter will continuously run at the lower frequency limit if the frequency setting signal is lower than 1/100 (1%) of full scale.
134
Appendix Function Parameter List
P048
P049
P050
P051
The 1st Skip Frequency
The 2nd Skip Frequency
The 3rd Skip Frequency
Skip Frequency Band Width
If mechanical parts of the load resonate at a specific output frequency of inverter, continuous operation within frequency band width should be avoided by setting the skip frequency and the skip frequency band width.
· Up to 3 skip frequency values can be set, and the skip frequency band width can be set between 1 and 10 Hz.
■ Parameter P048: The 1st Skip Frequency
■ Parameter P049: The 2nd Skip Frequency
■ Parameter P050: The 3rd Skip Frequency
Data setting range (Hz) 0.0•0.2~400.0
* “0.0” indicates that there is no skip function setting.
■ Parameter P051: Skip Frequency Band Width
Data setting range (Hz) 0·1~10
* “0” indicates that there is no skip function setting.
135
Appendix Function Parameter List
P052
Cooling Fan ON-OFF Control Selection
· Operation modes of cooling fan in normal status and fault status can be set.
Setting value Operation of cooling fan
Details
Operation when heat sink is faulty
0
1
2
3
Fan ON when the power supply is switched ON.
Fan OFF when the power supply is switched OFF.
Fan ON at the start of the operation.
Fan OFF when the operation stops.
※ The status of the internal temperature of the inverter will be switched between
ON and OFF when in the stop status (It shall be switched to OFF when the internal temperature of the inverter is below 100℃).
Fan ON when the power supply is switched ON.
Fan OFF when the power supply is switched OFF.
Fan ON at the start of the operation.
Fan OFF when the operation stops.
※ The status of the internal temperature of the inverter will be switched between
ON and OFF when in the stop status (It shall be switched to OFF when the internal temperature of the inverter is below 100℃).
The inverter stops abnormally.
The inverter stops abnormally.
The inverter does not stop but sends out alarm.
The inverter does not stop but sends out alarm.
· The parameter is invalid to the models without cooling fans (3-phase 400
V/0.75 kW model).
·Please set the parameter “P056:—” to be “1” or “6” when the setting value “2” or “3” is used.
136
Appendix Function Parameter List
P053
Input Terminal Filter
Filter constants can be set to the control circuit terminals of the inverter to effectively remove the interference of the external signal input.
Setting value (times) 5~100
· If the setting value is too large, the interference resistance capability will be enhanced, but the response speed of the control input terminals will decrease.
· If the setting value is too small, the interference resistance capability will be weakened, but the response speed of the control input terminals will increase.
· When start/stop, forward run and reverse run signals are used to operate the inverter, internal processing time of the inverter will become longer even if the setting value is small. In this case, the response speed of the control input terminals will be slower than other terminals.
P054
Linear Speed Multiplier
When the setting value shown in “P005: Operation Status Monitor” is “1” (linear speed), multiplier relative to the output frequency can be set.
■ Parameter P054:Linear Speed Multiplier
Data setting range (times) 0.1~100.0
<Setting example> When linear speed is displayed
Linear speed (m/min) =F(Hz)×K (multiplier)
· To display the linear speed 25(m/min) at 50Hz, set the multiplier
(K) to “0.5”.
· Linear speed exceeding “9999” is displayed as “9.9.9.9”.
Related parameters: P005
137
Appendix Function Parameter List
P055
Setting Data Clear
All data can be restored to their factory settings via this parameter.
Setting value
0
1
Details
It indicates the value in normal status.
Except motor constants, all data will be restored to their factory settings.
2 All data will be restored to their factory settings.
■ Uninitialized motor constants when P055=2
Function Name
Motor Capacity
Motor Pole Number
Rated Voltage of Motor
Rated Frequency of Motor
Rated Current of Motor
Primary Resistance
Secondary Resistance
Energizing Inductance
Leakage Inductance
Energizing Current
Speed Control Percentage
Increment
Speed Control Integral Increment
Torque Limit Level
ParameterNo.
For the 1st motor
P203
For the 2nd motor
P216
P204
P205
P217
P218
P206
P207
P208
P209
P210
P211
P212
P219
P220
P221
P222
P223
P224
P225
P213 P226
P214
P215
P227
P228
· When the setting value is changed to a value other than “0” and button is pressed, the display will automatically switch to “0” afterwards to apply the change.
138
Appendix Function Parameter List
P056
Alarm LED Operation Selection
Alarm LED operation of the panel can be selected via this parameter.
Setting
Value
0
Function Name Details of Function
1
2
4
6
N/A
Full monitor alarm
Output voltage fault alarm
Abnormal temperature alarm
Abnormal cooling fan alarm
N/A (The LED lights up when fault trip occurs)
When any of the specified conditions (output voltage fault, overload, temperature abnormality, timer operation stop and cooling fan abnormality) is satisfied, the alarm LED will flicker.
When the setting value (P057) is reached, the alarm
LED will flicker.
When the setting value (P058) is reached, the alarm
LED will flicker.
When the heat sink temperature rises above 80 °C, the alarm LED will flicker.
When the timer operation is complete, the alarm LED will flicker.
(The signal is linked with the timer operation function.
When ∞ is displayed, the alarm LED will not flicker.)
When cooling fan abnormality occurs, the alarm LED will flicker.
· If fault trip occurs, the alarm LED will light up.
· Monitor function “n008: Alarm Type” can be used to identify the type of the current alarm.
· When alarm LED operation selection (parameter P056) is set to “1” and several alarms occur simultaneously, the alarm display order is as follows.
(If a higher-priority alarm is in operation, it will still be displayed even if a lower-priority alarm enters.)
· When the settings of “P124 to P126: Output TR1, TR2 and Ry Function Selection” are set to “11(r11)”, it can be output to the external devices as alarm signal.
Related parameters: P057, P058
P057
Upper Voltage Limit of Alarm LED
When alarm LED operation selection is set to “1” or “2”, the upper voltage limit applied to judge the output voltage fault alarm can be set via this parameter.
If the output voltage of inverter is higher than the setting value, the alarm LED will flicker as output voltage fault alarm.
Data setting range (V) 0.1~600.0
Related parameters: P056
139
Appendix Function Parameter List
P058
Upper Current Limit of Alarm LED
When alarm LED operation selection is set to “1” or “3”, the upper current limit applied to judge the overload fault alarm can be set via this parameter.
If the output current of inverter is higher than the setting value, the alarm LED will flicker as overload fault alarm.
Data setting range (A) 0.1~100.0
Related parameters: P056
P059
Password
To prevent accidental changes to the data after parameter setting is complete, password can be set via this parameter.
Data setting range 0000~9999
* “0000” indicates that there is no password.
To set a password, rotate the encoder to switch to the parameter setting mode to show “PS”. You may proceed to parameter setting after you enter the password and press the encoder.
140
Appendix Function Parameter List
Input and Setting of Password
Password Input
① Power ON the inverter.
The inverter shows “0000” when it is powered ON.
② Press
MODE to enter the Parameter Setting mode. MODE
③ Rotate the knob to “P0: Parameter Setting”.
④ Press the knob to display parameter P001.
⑤ Rotate the knob to “P059: Password”.
⑥ Press the knob to proceed to the setting of P055.
⑦
Rotate the knob to adjust the value of P055 to
“1234”.
⑧ Press the knob to apply the setting of “1234”.
Password Setting
⑨
Press
MODE to proceed to “P0: Parameter Setting” to show“P0--”.
⑩
Counterclockwisely rotate the knob to proceed to passwork lock mode to show“PS”.
MODE
ESC
141
Appendix Function Parameter List
P060
P061
MOP Function Selection
Acceleration/Deceleration Time for MOP Operation
Operation of frequency change can be set via these parameters when MOP function is used.
When acceleration/deceleration time is relatively short, frequency change is much easier with this function.
■ Parameter P060:MOP Function Selection
Setting
Value
0
1
Function Name
MOP operation linked with the acceleration/deceleration time
Operation linked with frequency setting
Details
Press the Left/Right rotation knob, the inverter will accelerate/decelerate according to the acceleration/deceleration time set with the parameter
P061.
Press the Left/Right rotation knob to switch to the frequency setting mode. But if operation linkage is not performed, press the knob after frequency is selected and acceleration/deceleration will be performed according to the acceleration/deceleration time set via parameter P001 and P002.
Disable the use of the MOP function. 2 MOP function disabled
■ Parameter P061: Acceleration/Deceleration Time for MOP Operation
Data setting range (s) 0.04·0.1~3600
Increment (s) 0.1(0.1~999.9), 1(1000~3600)
· When parameter P060 is set to “1”, applicable acceleration/deceleration time can be set via this parameter.
· When the data setting range is “0.04s”, the display is “0.0”.
· The maximum frequency is set via parameter P009 and P012.
142
Appendix Function Parameter List
· This function still applies even if parameter “P103 to P105: SW3 to SW5
Function Selection” is set to “20: Frequency ▲/▼ Setting”.
■ Operation when parameter P060 is set to “1: Operation Linked with
Frequency Setting”
· Rotate the Left/Right Arrow button of the rotation knob while the setting frequency is being displayed, the displayed data will flicker and proceed to a status under which the frequency setting data can be changed.
· Press the “knob” button to apply the frequency setting, the operation will start at the new frequency and implement the acceleration/deceleration operation.
· Press “ESC” button to return to its previous status while the frequency display data is flickering.
Related parameters: P001, P002, P009, P012, P060, P103 to P105
143
Appendix Function Parameter List
P062
P063
Torque Boost Increment
Torque Boost Response Increment
The boost increment and response increment can be set via these parameters in the auto torque boost mode.
■ Parameter P062: Torque Boost Increment
Data setting range (%) 0~200
· With the increase of the setting value, the voltage will rise accordingly, in this case, overcurrent will occur depending on the loads.
■ Parameter P063: Torque Boost Response Increment
Data setting range (%) 0~200
· With the increase of the setting value, response to the load change will be quickened, in this case, the motor is likely to produce vibration.
· Parameter P062 and P063 are valid only when parameter P011 and P140 are set to “Auto”.
144
Appendix Function Parameter List
P101
P102
P103
SW1 Function Selection
SW2 Function Selection
SW3 Function Selection
P104
P105
SW4 Function Selection
SW5 Function Selection
P106
SW6 Function Selection
Control function of SW1·2·3·4·5·6 (control circuit terminal No.1·2·3·4·5·6) can be set. Refer to the table below for the corresponding functions of the setting values of 1 to 18. If “b” contact input is applied, set the value with a letter “r”.
• “A” contact input =“0”: “ON” is detected when the SW signal is in a close state
(the terminal level is “L”).
• “B” contact input = “1”: “ON” is detected when the SW signal is in an oprn state (the terminal level is “H”).
SW used to set the function
SW1
Terminal No.1
SW2
Terminal No.2
SW3
Terminal No.3
SW4
Terminal No.4
SW5
Terminal No.5
SW6
Terminal No.6
0 No setting No setting No setting No setting No setting No setting
1 r1 Multi-step speed Multi-step speed Multi-step speed Multi-step speed Multi-step speed Multi-step speed
3 r3 Reset Lock
4 r4 JOG Selection
Reset Lock
JOG Selection
Reset Lock
JOG Selection
Reset Lock
JOG Selection
Reset Lock
JOG Selection
Reset Lock
JOG Selection
5 r5 External Fault Stop External Fault Stop External Fault Stop External Fault Stop External Fault Stop External Fault Stop
Parameter Setting
Disabled
Parameter Setting
Disabled
Parameter Setting
Disabled
Parameter Setting
Disabled
Parameter Setting
Disabled
Frequency Signal
Switch
Frequency Signal
Switch
Frequency Signal
Switch
Frequency Signal
Switch
Frequency Signal
Switch
Setting value
9 r9
The 2nd
Characteristics
Selection
The 2nd
Characteristics
Selection
The 2nd
Characteristics
Selection
The 2nd
Characteristics
Selection
The 2nd
Characteristics
Selection
The 2nd
Characteristics
Selection
10 r10 PID Control Switch PID Control Switch PID Control Switch PID Control Switch PID Control Switch PID Control Switch
11 r11
3-wire Stop
Command
3-wire Stop
Command
3-wire Stop
Command
3-wire Stop
Command
3-wire Stop
Command
3-wire Stop
Command
12 r12 Speed Search
14 r14
Speed Search Speed Search Speed Search Speed Search Speed Search
13 r13
Temporary Control
Stop of Winding
Mode
Temporary Control
Stop of Winding
Mode
Temporary Control
Stop of Winding
Mode
Temporary Control
Stop of Winding
Mode
Temporary Control
Stop of Winding
Mode
Temporary Control
Stop of Winding
Mode
Input Mode of
Winding Length
Input Mode of
Winding Length
Winding Length
Zero Clearing
Input Mode of
Winding Length
Winding Length
Zero Clearing
Input Mode of
Winding Length
Winding Length
Zero Clearing
Input Mode of
Winding Length
Winding Length
Zero Clearing
Input Mode of
Winding Length
Winding Length
Zero Clearing
17 r17 Forward/Reverse Forward/Reverse Forward/Reverse Forward/Reverse Forward/Reverse Forward/Reverse
18 r18 JOG Forward Run JOG Forward Run JOG Forward Run JOG Forward Run JOG Forward Run JOG Forward Run
19 r19 JOG Reverse Run JOG Reverse Run JOG Reverse Run JOG Reverse Run JOG Reverse Run JOG Reverse Run
20 r20
Frequency▲Settin g
Frequency▲Settin g
Frequency Storage
Setting
Winding Length
145
146
Appendix Function Parameter List
■ Multi-step speed SW Function
SW function is set so that it is used as multi-step speed function.
Multi-step speed function selection is set via parameter P301.
· When all SWs are set to multi-step speed function and 16-speed operation is performed, the four SWs with lower No. are valid as multi-step speed command SW.
(Set “SW1 to SW6” to multi-step speed function → Use SW1, SW2, SW3 and
SW4 as multi-step speed command.)
· Read “P301: Multi Speed Function Selection” carefully before using this function.
Related parameters: P301 to P334
■ Reset Function
Fault stop status can be reset through external control if an inverter fault trip
(stop) occurs.
When a fault trip occurs and SW signal input is turned ON, the fault trip status will be cleared if the SW signal input is turned OFF.
Appendix Function Parameter List
■ Reset Lock Function
When a fault trip occurs, clearing of fault trip status with stop signal is disabled to perform reset operation with SW signal after identifying the details of fault trip and eliminating the abnormality.
· Normally, SW signal is input with ON status.
· When a fault trip occurs, the inverter will maintain the trip status even if stop signal and reset signal are input.
· After the abnormality is identified and eliminated, the fault trip will be reset when this SW is turned OFF.
* Turn reset lock signal OFF and press
STOP
button to reset the fault.
In addition, turn the fault reset signal OFF.
147
Appendix Function Parameter List
■ JOG Function
Micro operations such as position adjustment can be performed with external control signals.
Signal input terminals for controlling micro operation from external devices can be set via parameter P101 to P106.
But Run Command Selection (parameter P003) should be set through external control.
· Turn the signal input ON, and it will enter JOG operation mode.
· JOG operation is performed according to “P019: JOG Frequency”, “P020:
JOG Acceleration Time” and “P021: JOG Deceleration Time” settings, after run/stop and forward/reverse run signals are input via terminals.
<Example> When SW1 (parameter P101) is set to “16 (Run/Stop)”; SW2
(parameter P102) is set to “17 (Forward/Reverse Run)”; SW3
(parameter P103) is set to “4 (JOG Selection)”; operations are performed as follows.
7
1
2
3
Note 1: During JOG operation, please turn the JOG selection signal ON (time
B) and then turn the run signal ON.
Note 2: During reverse run operation, please turn the reverse run signal ON
(time A) and then turn the run signal ON.
Related parameters: P019 to P021
148
Appendix Function Parameter List
■ External Fault Stop Function
Signal input terminal for applying fault stop (emergency stop) to the inverter through external devices can be set.
· The inverter will stop output immediately after the external fault stop input
(setting value = 5) turns SW signal ON and “AU” is displayed.
· Input signal logic setting can be changed by setting the SW function parameter to “r5”.
<Example> When SW1 (parameter P101) is set to “16 (Run/Stop)”; SW3
(parameter P103) is set to “r5” (fault stop input contrary to the logic) , operations are performed as follows.
7
1
3
* When external fault stop signal is set to contact B input, fault reset can be applied after run signal is turn OFF, even if external stop signal is “ON”. But fault trip will occur after the run signal is turned “ON” again. So please turn the run signal “ON” after the external fault stop signal being turned “OFF” for normal operation.
■ Parameter Setting Disabled Function
The signal input terminal for disabling the parameter setting through external control can be set.
· After signal input is turned ON, setting parameters with the operation panel and communication are disabled.
· When the signal input is turned ON, function parameters and built-in memory parameters cannot be set but be monitored.
· During data setting, data cannot be changed through the SW function even if button is pressed when the signal is ON.
149
Appendix Function Parameter List
■ Coast-to-stop Function
The signal input terminal for applying coast-to-stop through external control can be set.
· During operation, the inverter will stop output immediately after signal input is turned ON and “0.0” is displayed.
(Without fault indication and fault alarm output)
· The inverter will run immediately after signal input is turned OFF and run signal is turned ON.
[Note] The inverter will start as the signal input is turned OFF, so please ensure personal safety before operation.
· The inverter will stop normally after the run signal is turned OFF together with signal input being turned OFF.
<Example> When SW1 (parameter P101) is set to “16 (Run/Stop)”; SW3
(parameter P103) is set to “7 (coast-to-stop)”, and run command selection
(parameter P003=2) is used;
150
Appendix Function Parameter List
■ Frequency Signal Switching Function
Signal input terminal for switching frequency setting command from “The 1st
Frequency Setting Signal (command set via parameter P004)” to “The 2nd
Frequency Setting Signal (command set via parameter P118)” can be set.
This function is valid when parameter “P119: The 2nd Analog Input Function
Selection” is set to “0: The 2nd Frequency Setting Signal”.
· When signal input is OFF: The 1st Frequency Setting Signal.
· When signal input is ON: The 2nd Frequency Setting Signal.
Related parameters: P118, P119
151
Appendix Function Parameter List
■ The 2nd Characteristics Selection Function
When SW signal is ON, the inverter will run according to the 2nd
Characteristics Function settings as follows.
Switching button OFF
P001: The 1st Acceleration Time
P002: The 1st Deceleration Time
P013: Base Frequency
P011: Torque Boost
P023: Electronic Thermal Selection
P024: Thermal Current Setting
P014 Change Point Frequency1
P015: Change Point Voltage 1
P016: Change Point Frequency 2
P017: Change Point Voltage 2
P203: Motor Capacity
P204: Motor Pole Number
P205: Rated Voltage of Motor
P206: Rated Frequency of Motor
P207: Rated Current of Motor
P208: Primary Resistance
P209: Secondary Resistance
P210: Energizing Inductance
P211: Leakage Inductance
Switching button ON
P317: The 2nd Acceleration Time
P318: The 2nd Deceleration Time
P139: The 2nd Base Frequency
P140: The 2nd Torque Boost
P141: The 2nd Electronic Thermal Selection
P142: The 2nd Thermal Current Setting
P143: The 2nd Change Point Frequency 1
P144: The 2nd Change Point Voltage 1
P145: The 2nd Change Point Frequency 2
P146: The 2nd Change Point Voltage 2
P216: The 2nd Motor Capacity
P217: Pole Number of the 2nd Motor
P218: Rated Voltage of the 2nd Motor
P219: Rated Frequency of the 2nd Motor
P220: Rated Current of the 2nd Motor
P221: Primary Resistance of the 2nd Motor
P222: Secondary Resistance of the 2nd Motor
P223: Energizing Inductance of the 2nd Motor
P224: Leakage Inductance of the 2nd Motor
P212: Energizing Current
P213: Speed Control Percentage
Increment
P214: Speed Control Integral Increment
P225: Energizing Current of the 2nd Motor
P226: Speed Control Percentage Increment of the 2nd Motor
P227: Speed Control Integral Increment of the
2nd Motor
P228: Torque Limit Level 2 of the 2nd Motor P215: Torque Limit Level 1
Note: Ensure personal safety before switching characteristics.
152
Appendix Function Parameter List
■ Control Switching Function
Signal input terminal for cancelling PID control through external control can be set. When the signal input is turned ON, the inverter switches from “PID control” to the command set via parameter P004.
The function is valid when parameter “P118: The 2nd Analog Input Function
Selection” is set to “1 to 3”.
·When the signal input is OFF: PID control or control based on auxiliary frequency signal.
·When the signal input is ON: command set via parameter P004.
■ 3-wire Stop Command Function
Signal input terminal for executing 3-wire stop command can be set.
When “3-wire stop signal” is ON, “run signal” or “forward/reverse run signal” can be held automatically. Also, switching to OFF will cancel the holding status.
· Please set “Run Command Selection” via parameter P003.
· Set the SW1 to SW6 terminals to be 3-wire stop command function (contact
B input) (always be contact B input regardless of the setting value is 11 or r11).
Related parameters: P003
153
Appendix Function Parameter List
■ Frequency ▲/▼ Setting Function
When frequency and parameter “P103 to P105” are set to “digital setting with operation panel (P004 = 1)” and “20” respectively, SW3 and SW4 can be used to change frequency while SW5 is used to save this frequency.
· SW3: During ON, frequency increases. (During OFF, the existing frequency is held.)
· SW4: During ON, frequency decreases. (During OFF, existing frequency is held.)
· SW5: Turn ON once and OFF again to save the frequency at that time.
(The frequency can be saved even if the power is turned OFF.)
Note 1: The operating frequency will not be changed when both▲button (SW3) and ▼button (SW4) are turned OFF or ON (i.e. in A or B area etc).
Note 2: The operating frequency will not be saved when “frequency memory operation of SW5” and “frequency setting in frequency setting mode” on the operation panel are not performed.
· When parameter “P060: MOP Function Selection” is set to “0”, the acceleration/deceleration time set via parameter “P061:
Acceleration/Deceleration Time for MOP Operation” will be used.
Please set P106 to be “0” or “1”when using this function.
Related parameters: P004, P060, P061
154
Appendix Function Parameter List
■ Speed Search Function
· The inverter will apply minor DC voltage to the motor, detect its rotation speed and restart it at this frequency when the motor rotates freely due to inertia, which is the so-called “speed search function”.
· There are 3 methods to start the speed search.
1) Through input signal from control terminals (SW1 to SW6)
Related parameters: P101 to P106 (SW1 to SW6 Function Selection)
2) At motor startup
Related parameters: P357 (Speed Search at Startup)
3) During retry operation of inverter after fault trip occurrence
Related parameters: P029 (Retry Function), P361 (Speed Search Selection during Retry)
· Perform speed search according to the following procedures.
· Conditions of speed search can be set via parameter P359 to P364.
· The start of speed search through control input is only valid during free operation. Therefore, even if the control input assigned to speed search is
ON, the speed search will nevertheless be ignored.
· If the rotation speed is too low and the rotation direction does not match the rotation command, the rotation speed may not be sensed.
· The sensing function may fail if the speed search is performed for the motor with capacity smaller than the inverter.
· “CAL” will be displayed on the operation panel during speed search. During the displaying, there is minor DC voltage applied on the motor externally.
155
Appendix Function Parameter List
■ Winding Mode Control Function
· Winding mode control function will operate at the triangular-wave-shaped frequency as shown in the following graph.
· When parameter “P335: Winding Mode Control Selection” is set to “1” or “2”, winding mode control function will start after run command is turned ON. During startup, the inverter will keep on accelerating within the time set via parameter
“P001: The 1st Acceleration Time” until the set frequency is reached.
· The conditions of winding mode control are set via parameter P335 to P339.
· The operational mode of winding mode is set via parameter "P340:Winding Mode
Operation Selection". When parameter "P340" is set to "1" or "3", 2-point mode starts, in this case, set frequency of second point via parameter "P302: Second
Frequency", set stop length via parameter "P344: Winding Stop Length", the basic frequency will change to the second frequency with the increase of the winding length, the change of linear and when the winding length reaches the stop length.
When P340 is set to "2" or "3", random mode starts, in this case, set random change range via parameter "P341: Max Random Rise Time Coefficient" and "P342:
Minimum Random Rise Time Coefficient", yet when P342<P341, random function doesn't start. Especially, when P340 is set to "3", it will be 2-point random mode, the basic frequency will change from fixed frequency to second frequency with the change of winding length. And, rise time coefficient change randomly in the random range.
· When parameter “P101 to P106: SW1 to SW6 Function Selection” is set to “13”, and SW input of corresponding control input terminals (SW1 to SW6) are ON, the inverter will terminate winding mode control and continue to run at the frequency when SW input (SW1 to SW6) is turned ON.
· When stop command is turned ON, the deceleration will be performed to stop the inverter according to the value set via parameter “P002: The 1st Deceleration Time” regardless of the operating frequency.
156
Appendix Function Parameter List
If the following functions start together with winding mode control function, such function will take precedence. And what’s more, winding mode control will not start when the following functions operate.
· Trial operation function
· Auto-tuning function
· Timer operation function
· PID function
■ Winding Mode Input Length
When parameter “P335: Winding Mode Control Selection” is set to “1” or “2”, parameter “P106: SW6 Function Selection” is set to “20” or “14”, and pulse is input from SW6, length can be calculated based on “P343: Winding Length
Multiplier”.
· The calculated result will be displayed in n022.
Winding length=
(Pulse “n” input to SW6)×(P343: Winding Length Multiplier )
1000
When any multi-function SW is set to “14 (winding length input mode)” , the response speed will be slower.
When the input pulse band width is shorter than 15ms, set P106 to “20” and input from SW6.
157
Appendix Function Parameter List
■ JOG Forward Run/JOG Reverse Run
Micro operations such as position adjustment can be performed with external control signals.
Signal input terminals for controlling micro operation from external devices can be set via parameter P101 to P106.
JOG commands of all operations are valid, but the JOG command should take precedence.
· Turn the signal input ON, and it will enter JOG operation mode.
· JOG operation is performed according to “P019: JOG Frequency”, “P020:
JOG Acceleration Time” and “P021: JOG Deceleration Time” settings, after run/stop and forward/reverse run signals are input from terminals.
<Example> When SW1 (parameter P101) and SW2 (parameter P102) are respectively set to “18 (JOG Forward Run)” and “19 (JOG Reverse Run)”, operation are performed as follows.
Related parameters: P003, P019, P022
158
Appendix Function Parameter List
P107
Pulse Input Frequency
The number of pulses per second (pulse frequency) at the maximum output frequency can be set using this parameter.
Setting Range (kHz) 1.0~40.0
P108
Pulse Input Filter
The responsiveness to pulse input signal can be set using this parameter.
Please set at the time when diffirent frequency is sensed.
Setting Range (times) 10~100
P109
PWM Signal Average Times
The inverter measures and calculates ON time and OFF time of each PWM cycle used as frequency command.
When using this parameter, the times of each PWM cycle command should be averaged, and then the average operation times are set as final output frequency.
Data Setting Range (times) 1~100
* With the increase of the average times, the frequency command will become stable, while the response speed will decrease.
159
Appendix Function Parameter List
P110
PWM Signal Cycle
PWM signal cycle can be input via this parameter.
Data setting range(msec) 1.0~2000
· The output frequency controlled by PWM signal is “0 V stop or the minimum frequency (without ON status)” and “the maximum frequency (without OFF status)”.
· Due to the fact that the output frequency accuracy relative to input signal will decrease around the minimum frequency and maximum frequency, do not use the inverter for precise frequency control.
· The 2nd frequency setting signal takes precedence over the PWM frequency signal if the 2nd frequency setting signal is selected (ON).
· PID control function is invalid when PWM frequency signal is selected.
PWM frequency signal cannot be used as PID setting value (SP).
■ Connection and Function Descriptions of Control Circuit Terminals
■ Relationship between PWM Signal and Frequency Command Value
■ Relationship between Pulse Signal and Frequency
Please set the number of pulse input per second (pulse frequency) at the maximum output frequency using parameter “P107: Pulse Input Signal Frequency”.
· When parameter P009 is set to “50” and “60”, the maximum output frequency shall be “50Hz” and “60Hz” accordingly; when it is set to “FF” or “3C”, the maximum output frequency shall be the value of parameter P012.
Related parameters: P009, P012
160
Appendix Function Parameter List
P111
Analog Input Filter
Filter constant of analog input terminal (control circuit terminal⑫and⑭) can be set to eliminate external interference caused by external voltage or current frequency setting signals.
Data Setting Range (times) 5~200
· Filter constant of analog input signals for control circuit terminal⑬and⑭ share the same setting value.
· Frequency command will become stable with the increase of the setting value (average times), while the response speed will decrease.
Related parameters: P004, P119
161
Appendix Function Parameter List
P112
P113
Bias Frequency Setting
Gain Frequency Setting
The relationship between output frequency and frequency setting signal can be adjusted freely. Please use this function according to the applications.
■ Parameter P112: Bias Frequency Setting
Data setting range (%) -99.0~250.0
■ Parameter P113: Gain Frequency Setting
Data setting range (%) 0.0~500.0
· Bias frequency and gain frequency are set in terms of pencentage (%) of the maximum output frequency (100%) (parameter P012).
· A frequency exceeding the maximum frequency or the upper frequency limit will not be output.
Also, the frequency will not drop below the lower frequency limit.
· The inverter will not perform reverse run operation even if negative frequency setting signal is input.
■ When bias frequency is set to be “positive” ■ When bias frequency is set to be “negative”
Related parameters: P004, P009, P012
162
Appendix Function Parameter List
P114
Analog Direction Mode
Used to set the direction after the frequency command had been set to analog signal.
■ Parameter P114: Analog Direction Mode
Setting Details
0 Analog direction mode is disabled.
1
2
If frequency is controlled by the analog quantity, the forward run will switch to reverse run at the threshold value of 50% of the maximum analog quantity input.
If frequency is controlled by the analog quantity, the reverse run will switch to forward run at the threshold value of 50% of the maximum analog quantity input.
· Control the direction based on the analog quantity.
P114 is set to “0”
Output
Frequency
%
100%
P114 is set to “1”
Output
Frequency
%
100%
100%
The 1st analog input (%)
Forward run
Reverse run
100%
The 1st analog input (%)
P114 is set to “2”
Output
Frequency
%
100%
Reverse run
Forward run
The 1st analog input (%)
100%
· The direction setting mode (dr) is invalid when the setting value is “1” or “2”.
163
Appendix Function Parameter List
P115
P116
The 2nd Bias Frequency Setting
The 2nd Gain Frequency Setting
Output frequency and the 2nd analog input signal can be adjusted freely.
■ Parameter P115: The 2nd Bias Frequency Setting
Data setting range (%) -99.0~250.0
■ Parameter P116: The 2nd Gain Frequency Setting
Data setting range (%) 0.0~500.0
· The 2nd bias frequency and the 2nd gain frequency are set in terms of pencentage (%) of the maximum output frequency (100%) (parameter P012).
· A frequency exceeding the maximum frequency or the upper frequency limit will not be output.
Also, the frequency will not drop below the lower frequency limit.
· The inverter will not perform reverse run operation even if negative frequency setting signal is input.
■ Relationship between the 2nd Frequency Setting Signal and the Output Frequency
164
Appendix Function Parameter List
P117
The 2nd Analof Direction Mode
Used to set the direction after the frequency command had been set to analog signal.
■ Parameter P117: The 2nd Analog Direction Mode
Setting Details
0 Analog direction mode is disabled.
1
2
If frequency is controlled by the 2nd analog quantity, the forward run will switch to reverse run at the threshold value of 50% of the maximum analog quantity input.
If frequency is controlled by the 2nd analog quantity, the reverse run will switch to forward run at the threshold value of 50% of the maximum analog quantity input.
· Control the direction based on the analog quantity.
P117 is set to “0”
Output frequency
(%)
100%
P117 is set to “1”
Output frequency
(%)
100%
100%
The 2nd frequency input (%)
Forward run
Reverse run
100%
The 2nd frequency input (%)
P117 is set to “2”
Output frequency
(%)
100%
Reverse run
Forward run
The 2nd frequency input (%)
100%
· The direction setting mode (dr) is invalid when the setting value is “1” or “2”.
165
Appendix Function Parameter List
P118
The 2nd Analog Input Function Selection
The control function of the 2nd analog input terminal (control circuit terminal
No.16) can be selected.
Setting value
0
1
2
Details
The 2nd frequency setting signal
Measured value of PID control
Bias signal of PID control
3 Auxiliary frequency setting signal
■The 2nd frequency setting signal (setting value = “0”)
· The 2nd analog input terminal can be used as the 2nd frequency setting signal.
· Frequency setting command can be switched between the 1st frequency setting signal and the 2nd frequency setting signal depending on the input status set via parameter “P101 to P106: SW1 to SW6 Function Selection”.
SW with OFF input: the 1st frequency setting signal.
SW with ON input: the 2nd frequency setting signal.
■Measured Value of PID Control (setting value = “1”)
· The 2nd analog input terminal can be used as feedback signal of PID control
(measured value PV).
· Input signals (0 ~ 5 V, 0 ~ 10 V, 4 ~ 20 mA and 0 ~ 20 mA) are fed back as measured values (PVs) of PID control (positive values: 0
~
100%).
· After parameter P118 is set to “1”, set target value (SP) to the output frequency through parameter “P004: Frequency Setting Signal” to perform PID control so that measured value PV will approach the target value SP and the output frequency will be changed accordingly.
· Parameters for PID control can be set via parameter P345 to P354.
166
Appendix Function Parameter List
■ Bias Signal of PID Control (setting value = “2”)
· The 2nd analog input terminal can be used as measured value of PID control
(bias signal).
· Input signals (0 ~ 5 V, 0 ~ 10 V, 4 ~ 20 mA and 0 ~ 20 mA) are fed back as bias signal of PID control (setting example: -10%
~
+10%).
· Bias value can be converted inside the inverter via parameter “P115: The
2nd Bias Frequency Setting” and “P116: The 2nd Gain Frequency Setting”.
<Example> When the analog input ranges from 0 to 5 V and both the 2nd bias value and the 2nd gain are set to “10”
(%)
10
第2增益
P116=10.0
The 2nd bias
P115=10.0
P115=-10.0
0
2.5
Analog input voltage
-10
· After parameter P118 is set to “2”, conduct the target value (SP) PID control based on the bias signal input to the analog input terminal, the output frequency will change accordingly. In this case, the bias signal (PV–SP) under
PID control is the bias signal of the 2nd analog input terminal.
· Parameters for PID control can be set via parameter P345 to P354.
167
Appendix Function Parameter List
■Auxiliary Frequency Setting Signal (setting value = “3”)
· The 2nd analog input terminal can be used as auxiliary frequency setting signal.
· Input signals (0
~
5 V, 0
~
10 V, 4
~
20 mA and 0
~
20 mA) are fed back as auxiliary frequency setting signal added to the 1st frequency setting signal (%)
(setting example: -10%
~
+10%).
· The setting value of auxiliary frequency setting signal can be converted inside the inverter via parameter “P115: The 2nd Bias Frequency Setting” and
“P116: The 2nd Gain Frequency Setting”.
<Example> When the analog input ranges from 0 to 5 V and both the 2nd bias value and the 2nd gain are set to “10”
(%)
10 The 2nd gain
P116=10.0
The 2nd bias
P115=10.0
P115=-10.0
0
2.5
Analog input
voltage
-10
· It can be used when the result of PID calculation conducted by external devices such as PLC is added to the speed command value.
· The inverter’s output frequency is determined by the following formula.
Output frequency=Max. output frequency×(The 1st frequency setting signal
(%) + auxiliary frequency setting signal (%))
Related parameters: P004, P101 to P106, P115 to P116, P345 to P354
168
Appendix Function Parameter List
P119
The 2nd Analog Input Singal Selection
Setting signal of the 2nd analog input terminal (control circuit terminal⑬) can be selected.
Setting value
2
3
4
5
Details of setting signal
0~5V
(voltage signal)
0~10V
(voltage signal)
4~20mA
(current signal)
0~20mA
(current signal)
Operation method and control circuit terminal connection diagram
Terminal ⑬ and ⑭ (13: +, 14: -)
Terminal ⑬ and ⑭ (13: +, 14: -)
Terminal ⑬ and ⑭ (13: +, 14: -)
Terminal ⑬ and ⑭ (13: +, 14: -)
· The inverter will run or stop as defined by the setting value of “P047: 0V Stop
Function Selection”.
To make the 0V stop function invalid, please set parameter P047 to “0.0”.
Related parameters: P047, P115, P116
169
Appendix Function Parameter List
P120
Analog Output Function Selection
Functions of “0 to 10V voltage signal” from the control circuit terminal No. 15 can be set here.
Setting value
0
Details
Signals in proportion to output frequency are output.
1 Signals in proportion to output current are output.
■ Relationship between 0 to 10V voltage signal and output frequency/output current
<In proportion to the output frequency> < In proportion to the output current>
(V)
10
Max. output frequency
(V)
10
150% of the rated output current
0 0
Output frequency Output Current
P121
Compensation for PWM Output Duty Ratio
Compensation for output duty ratio of the “output status signal (PWM)” can be made here.
Data setting range (%) 25~100
■ Adjustable Range (full scale value)
· PWM signal: PWM signal duty ratio×Percentage set with P121
(%)
100
(%)
100
Max. output frequency
150% of the rated output current
25 25
Output frequency Output Current
Relationship between PWM duty ratio and output frequency when P121=100.
Relationship between PWM duty ratio and output frequency when P121=25
170
Appendix Function Parameter List
P122
PWM/Pulse Output Function Selection
be set here.
Setting value
0
Details
Signals in proportion to output frequency are output.
1 Signals in proportion to output current are output.
■ Relationship between PWM signal output and output frequency/output current
(%)
100
Max. output frequency
(%)
100
150% of the rated output current
Output frequency Output Current
■ Relationship between pulse signal output and output frequency/output current
(%)
100
Max. output frequency
(%)
100
150% of the rated output current
Output frequency Output Current
· The “pulse percentage” shown in the diagram refers to the percentage of the output pulse frequency in the setting value of “P147: Pulse Output
Frequency”.
P123
PWM Output Cycle
Set the output cycle for PWM when the Tr1 output function is set to be PWM output.
■ Parameter P123: PWM Output Cycle
Data setting range[msec] 1~2000
· Cycle of PWM wave output can be set.
171
Appendix Function Parameter List
P124
P125
Output TR1 Function Selection
Output TR2 Function Selection
open-collector output 2 (control circuit terminal ⑨ to ) can be set.
P124
(TR1)
0
P125
(TR2)
0
Function
Run signal
ON condtions for open-collector output
With run signal ON or during inverter output
1 1 Reverse run signal When inverter is in reverse run status
When output frequency is within ±2 Hz of setting frequency
When the output current is above 140% of the rated current or the electronic thermal level is reached.
Setting value
5
6
7
8
11
13
14
5
6
7
8
11
-
-
Current sensing (1)
Current sensing (2)
Fault alarm (1)
Fault alarm (2)
Alarm
Output status signal
(PWM)
Output status signal
(pulse)
When the output current is above the sensing current level (parameter P129 setting)
When the output current is below the sensing current level (parameter P129 setting)
When fault trip occurs in the inverter
When the inverter is in normal status (OFF for fault trip status)
When one cycle of timer operation completes
(output is available only during waiting time).
When timer operation completes (with “t.End” displayed).
Output is available with alarm LED flickering.
When speed search starts, the open-collector output is ON; when the speed search completes, the open-collector output is OFF.
PWM signals in proportion to output frequency or output current will be output.
Pulse signals in proportion to output frequency or output current will be output.
· The setting value “5” and “6” are used to set the delay time of current detection signal with “P130: Current Sensing Delay Time”.
· The setting value “10” is used to output the time set with “P326: Continuous
Waiting Time of Timer Operation”.
· Output frequency ratio or output current ratio of the setting value “13” and
“14” can be set via parameter P121. Setting value “13” and “14” can only be used to set open-collector output 1 (TR1).
Related parameters: P326, P127, P129 to P131
172
Appendix Function Parameter List
P126
Output RY Function Selection
Functions of relay output (control circuit terminal A, B and C) can be set.
· Energizing in ON status: The relay is turned ON when the coil is energized.
(Signal ON status = ON between terminals A and C, OFF between terminals B and C)
· Non-energizing in ON status: The relay is turned ON when the coil is not energized.
(Signal ON status = ON between terminals A and C, OFF between terminals B and C)
Setting value
Energizing in
ON status
0
Non-energizing in
ON status r0
1 r1
Function
Run signal
Reverse run signal
ON conditions for relay
With run signal ON or during inverter output
When inverter is in reverse run status
When the output current is above 140% of the alarm reached.
7
8
11 r7 r8 r11
Current
When the output current is above the sensing current level (parameter P129 setting)
Current
When the output current is below the sensing current level (parameter P129 setting)
Fault alarm (1) When fault trip occurs in the inverter
Fault alarm (2)
When the inverter is in normal status (OFF for fault trip status)
When one cycle of timer operation completes
(output is available only during waiting time).
When timer operation completes (with “t.End” displayed).
Alarm Output is available with alarm LED flickering. output is ON; when the speed search completes, the open-collector output is OFF.
· The setting value “5” and “6” are used to set the delay time of current detection signal with “P130: Current Sensing Delay Time”.
· The setting value “10” is used to output the time set with “P326: Continuous
Waiting Time of Timer Operation”.
Related parameters: P326, P128 to P130
173
Appendix Function Parameter List
P127
P128
Sensing Frequency[Output TR]
Sensing Frequency[Output RY]
Open-collector 1, 2 and relay output can be used to set the frequency sensed when outputting frequency sensing signals.
■ Parameter P127: Sensing Frequency [Output TR]
Data setting range (Hz) 0.0·0.2~400.0
· It is valid in open-collector output 1 and 2.
· “0.0” indicates 0V stop (0.0).
■ Parameter P128: Sensing Frequency [Output RY]
Data setting range (Hz) 0.0·0.2~400.0
· “0.0” indicates 0V stop (0.0).
■ Relationship between output frequency and each output signal
Related parameters: P124 to P126
174
Appendix Function Parameter List
P129
P130
Current Sensing Level
Current Sensing Delay Time
Open-collector 1, 2 and relay output can be used to set current sensing level and delay time when current sensing signal is output.
■ Parameter P129: Current Sensing Level
Data setting range (A) 0.1~100.0
■ Parameter P130: Current Sensing Delay Time
Data setting range (s) 0.1~10.0
· Current sensing delay time refers to the delay time for a signal to switch from
OFF to ON.
The delay time for a signal to switch from ON to OFF is about 100 ms (fixed value).
Related parameters: P124 to P126
175
Appendix Function Parameter List
P131
P132
RS485 Communication Protocol Selection
RS485 Communication Station No. Setting
P135
P136
RS485 Parity Check
RS485 Timeout Sensing
P133
RS485 Communication Speed Setting
P137
RS485 Wait-to-send Time
P134 RS485Stop Bit Length P138 RS485 Judging Time for TEXT Completion
Important parameters necessary for sending commands to inverter through communication can be set.
■ P131: RS485 Communication Protocol Selection
MK300 is based on three protocols: MEWTOCOL-COM, Modbus(RTU) and
Modbus (ASCII). Either protocol can be selected.
Setting value Details of function
0 MEWTOCOL-COM
1 Modbus(RTU)
2 Modbus(ASCII)
■ P132: RS485 Communication Station No. Setting
Data setting range 1~31
■ P133: RS485 Communication Speed Setting
Setting value Details of function
48 4800bps
96 9600bps
192 19200bps
384 38400bps
576 57600bps
1152 115200bps
■ P134: RS485 Stop Bit Length
Setting value Details of function
1 1bit
2 2bit
■ P135: RS485 Parity Check
Setting value
0
Details of function
Without parity check
176
Appendix Function Parameter List
■ P136: RS485 Timeout Sensing
If the status without communication continues for more than the allowable time when the Operation Command Selection (P003) and Frequency Setting Signal
(P004) are in the communication setting mode, the inverter will abnormally stop (displaying “OP”). Such allowable time can be set here.
Data setting range(sec) 0.0·0.1~60.0
* “0.0” indicates a setting without timeout sensing.
■ P137: RS485 Wait-to-send Time
Data setting range(msec) 1~1000
■ P138: RS485 Judging Time for TEXT Completion
Data setting range(msec) 3~200
* The setting is only valid when protocol Modbus (RTU) is used.
· Please cut off the primary power supply after the values of conmmunication-related parameter P131 to P138 had all been set.
After the power supply reset, the setting values will be applied in the inverter.
177
Appendix Function Parameter List
P139
The 2nd Base Frequency
The 2nd base frequency can be selected and set with the 2nd characteristics selection button.
(It is only valid when parameter P009 is set to “FF” or “3C”.)
■ Parameter P139:The 2nd Base Frequency
Data setting range (Hz) 45.0~400.0
· The maximum output frequency is the setting value of parameter P009 (V/F
Mode) or parameter P012 (Max. Output
Frequency)
· If “P009: V/F Mode” is set to “50” or “60”, the maximum output frequency and base frequency will be fixed values.
· A frequency value exceeding “P046: Upper Frequency Limit” cannot be output.
· If a general-purpose motor with rated frequency of 50/60 Hz is running at a frequency value exceeding the ratings, the motor may be damaged. Therefore, please set the frequency to match motor characteristics.
· If the base frequency is required to be changed together with the maximum output frequency for a dedicated high-speed motor etc., such change can also be changed via this parameter.
· When running the general-purpose motor at a frequency value exceeding the universal frequency, please set the base frequency to the rated output frequency (50/60 Hz) of general-purpose motor.
· When the general-purpose motor reaches a level exceeding the base frequency (normally 50/60 Hz), the motor will have the constant output characteristics and the generated torque will drop in reverse proportion to the frequency.
Related parameters: P009, P012, P101~P106, P046, P140, P143~P146
178
Appendix Function Parameter List
P140
The 2nd Torque Boost
The 2nd torque boost can be selected and set with the 2nd characteristics selection button. The larger the setting value is, the higher output voltage and torque boost are.
·After the mode is set to “auto torque boost”, the output voltage will be changed automatically according to the load fluctuation. To set “Auto torque boost”, please rotate the knob once more when the operation panel displays “40”.
Name
Auto torque boost
Manual torque boost
Data setting range (%)
Auto
0~40%
· If the boost level setting is too high, overcurrent fault, overload fault, motor overheating or excessive noise may occur.
· The motor current will rise after the boost level is increased. Please carefully consider the settings of “P141: The 2nd Electronic Thermal Selection” and
“P142: The 2nd Thermal Current Setting”.
· Auto-tuning is necessary when auto torque boost is selected. Please use it after the motor constants had been correctly set.
( For the auto-tuning methods, please carefully read “4.14 Auto-tuning” .)
179
Appendix Function Parameter List
P141
P142
The 2nd Electronic Thermal Selection
The 2nd Thermal Current Setting
Electronic thermal operation level can be selected and set with the 2nd characteristics selection button when the inverter output is stopped. Operation coasts to stop when OL is displayed.
■ Example for setting current and thermal operation (P141=1)
·Setting current ×100% Does not operate
·Setting current ×125% Operate (OL trip)
■ Parameter P141: The 2nd Electronic Thermal Selection
Setting value
Validity of function
Details of function
1 Enabled Without output frequency derating
2 Enabled With output frequency derating
3 Enabled Forced air-cooled motor specification
* About frequency derating
Cooling performance of the motor will be reduced at lower speed. To handle the problem, this function can automatically compensate operation level.
■ Parameter P141=1 ■ Parameter P141=2 ■ Parameter P141=3
■ Parameter P142: The 2nd Thermal Current Setting
Data setting range (A) 0.1~100.0
* Please make settings according to the rated current of the applicable motor.
Related parameters: P101 to P106
180
Appendix Function Parameter List
P143
P144
The 2nd Change Point Frequency 1
P145
The 2nd Change Point Voltage 1 P146
The 2nd Change Point Frequency 2
The 2nd Change Point Voltage 2
Change point 1 and 2 can be selected in 3-point mode of “P009: V/F Mode”.
(It is only valid when parameter P009 is set to “3C”.)
■ Parameter P143: The 2nd Change Point Frequency 1
Data setting range (Hz) 0.2~400.0
■ Parameter P144: The 2nd Change Point Voltage 1
Data setting range (%) 0.0~100.0
■ Parameter P145: The 2nd Change Point Frequency 2
Data setting range (Hz) 0.2~400.0
■ Parameter P146: The 2nd hange Point Voltage 2
Data setting range (%) 0.0~100.0
· Read “P009: V/F Mode” carefully before setting.
· The 2nd change point frequency 1 and 2 will operate according to the setting value of the base frequency when set to a value higher than the base frequency.
· The 2nd change point frequency 2 will operate according to the setting value of the 2nd change point frequency 1 when set to a value lower than the 2nd change point frequency 1.
· When setting “P140: The 2nd Torque Boost”, the 2nd change point voltage 1 and
2 will operate according to the setting value of the 2nd torque boost if set to a value lower than the 2nd torque boost level.
· The 2nd change point voltage 2 will operate according to the setting value of the
2nd change point voltage 1 when it is set to below the 2nd change point voltage 1.
· Please note that sharp acceleration/deceleration or overcurrent may occur depending on setting values and load status if data is changed during operation.
· The auto torque boost mode will take precedence if the auto torque boost mode is selected via parameter “P140: The 2nd Torque Boost”, in this case, settings related to 3-point mode (parameter P143 to P146: Change Point Voltage and Change Point
Frequency) will become invalid.
Related parameters: P009, P012, P101 to P106, P139, P140
181
Appendix Function Parameter List
P147
Pulse Output Frequency
The number of pulses per second (pulse frequency) at the maximum output frequency or 150% of the rated output current can be set using this parameter.
Setting Range (kHz) 1.0~10.0
P148
Pulse Output Duty Ratio
The pulse output duty ratio can be adjusted within the range of 25% to 75%.
Setting Range (%) 25~75
P149
Analog Output Voltage Compensation
Output compensation for “0 to 10V voltage singal” can be made.
Setting Range (%) 25~100
■ Adjustable Range (full scale value)
· Analog output voltage : Analog output voltage×Percentage set with P149
(V)
10
(V)
10
Max. output frequency
150% of the rated output current
2.5
2.5
Output frequency Output current
Relationship between analog output voltage and output frequency when P149=100.
Relationship between analog output voltage and output frequency when P149=25.
182
Appendix Function Parameter List
P201
Load Rating
Load rating types are set as the rated output current reference.
Setting value
0
1
Details
Heavy load specification
Light load specification
· For applications where requires a small variation in torque or small maximum torque and maximum speed, please select “1: Light Load
Specification” to enable the motor to operate continuously at a high output level (however, the carrier frequency should be 5kHz or less).
· The light load specification can be used when the rated output current is larger than the heavy load specification, overload current ratings are listed as below.
【 Overload Current Ratings】
Heavy load specification: 150% of the rated output current, lating for 1 minute
Light load specification: 120% of the rated output current, lating for 1 minute
· The heavy load specification has no difference with the light load specification when the carrier frequency is above 7.5kHz.
· Please carefully read Item 7 in this manual for the rated output currents of the heavy load specification and light load specification of various models and use them in their rating range.
· For applications where there is a sharp variation in torque and an instantaneous sharp increase in torque, please select “0: heavy load specification”.
If the light load specification is selected, the inverter will be forced to make a stop due to the protection function.
183
Appendix Function Parameter List
P202
Auto-tuning
Measure the motor constants used for control purpose and automatically save them to parameter P208 to P212 (the 2nd motor: P216 to P220)
The inverter will automatically drive the motor within the range of the upper frequency limit and the lower frequency limit after the auto-tuning starts.
Do not start an auto-tuning if there is a danger with the motor that is being driven.
Never approach the motor and the conductive parts during auto-tuning.
Failure to do so may result in injury and accidents.
Setting value Details
· When operating in the sensorless vector control mode, or operating the auto torque boost in the V/F control mode, be sure to perform the auto-tuning for all motores before their first operation.
Otherwise, they cannot be controlled normally.
· Do not connect loads and other objects to the motor shaft during auto-tuning.
It is suggested that it should be done in the standalone status.
The auto-tuning cannot be normally performed if loads and objects with greater inertia are connected.
Perform the auto-tuning in a free rotation state without loads as far as possible.
· Start the auto-tuning only after the motor had come to a complete stop.
· Refer to “4.14 Auto-tuning” for the auto-tuning procedures.
184
Appendix Function Parameter List
P203
P204
P205
P206
P207
Motor Capacity
Motor Pole Number
Rated Voltage of Motor
Rated Frequency of Motor
Rated Current of Motor
Motor specifications are set as the benchmarks for motor auto-tuning.
■ Parameter P203
Data setting range(kW) 0.2, 0.4, 0.7, 1.5, 2.2, 3.7, 5.5, 7.5, 11, 15
P203: The setting range of motor capacity is limited by the rated values of the inverter.
■ Parameter P204
Data setting range (poles) 2, 4, 6
■ Parameter P205
0~500 Data setting range (V)
■ Parameter P206
10.0~120.0 Data setting range (Hz)
■ Parameter P207
Data setting range (A) 0.01~99.99
· Set specifications for the motor used.
· These setting values shall be taken as benchmarks for auto-tuning, please make such setting before the start of auto-tuning (parameter P202).
· The specifications of motor are defined by the combination of various rated voltages, rated frequencies amd rated currents.
【 For example】380V/50Hz/1.0A; 400V/60Hz/1.5A
The rated voltage should be set after the AC power voltage actually used to input voltage to the MK300 inverter had been selected.
· In addition, be sure to set the rated current based on the combination due to that the rated current varies with the different rated voltage and rated frequency.
Torque limitation (parameter P215) is conducted according to the internal arithmetic of the setting value of rated current of motor (P207). The limitation operation cannot be normally performed if the setting value of P207 is incorrect.
Related parameters: P202, P215
185
Appendix Function Parameter List
P208
P209
P210
P211
P212
Primary Resistance
Secondary Resistance
Energizing Inductance
Leakage Inductance
Energizing Current
Motor constants shall be saved after the auto-tuning is done.
■ Parameter P208
Data setting range(Ω) 0.00~99.99
■ Parameter P209
Data setting range(Ω) 0.00~99.99
■ Parameter P210
Data setting range(mH) 0.0~5000
■ Parameter P211
Data setting range(mH) 0.0~999.9
■ Parameter P212
Data setting range (A) 0.01~99.99
· Various motor constants shall be automatically saved after the auto-tuning
(parameter P202) is done.
· In principle, the values saved after the auto-tuning can be used directly.
Related parameters: P202
186
Appendix Function Parameter List
P213
P214
Speed Control Percentage Increment
Speed Control Integral Increment
Set the speed control increment for the internal arithmetic of sensorless vector control.
■ Parameter P213
Data setting range 0.01~10.00
■ Parameter P214
Data setting range 0.01~10.00
· Applicable initial values of various motors had been set. Normally, such initial values can be used directly.
· In the actual operation in sensorless vector control mode, adjustment to such parameter can sometimes enhance the stability and responsiveness to the torque variation.
Adjust the values in small increments during parameter adjustment and verify their effectiveness through actual running test.
· The adjustment of such parameter will cause the normal rotation control unable to be maintained when some values are applied.
When adjusting parameters, please conduct the test by taking into account the safety in case of abnormal rotation.
187
Appendix Function Parameter List
P215
Torque Limit Level
Set the limit value for torque current in the sensorless vector control mode.
Data setting range (%) 50~400
· The inverter will be forced to come to stop because of the protection function if the torque current increases due to that the torque is too large.
Therefore, it is necessary to set a limit value for the torque current to prevent the force stop.
· The output frequency shall be automatically changed for the control when the torque current reaches the limit value.
· To disable the limitation, please set the upper limit value to “400”.
· If it is required to prevent a force stop to the utmost extent, it is suggested to set the limit value to 200 or less.
The increase of the limit value are likely to cause it to reach the force stop level before the implementation of such limitation.
· Such torque limitation is conducted according to the internal arithmetic of the setting value of rated current of motor (P207). The limitation operation cannot be normally performed if the setting value of P207 is incorrect.
Related parameters: P207
188
Appendix Function Parameter List
P216
P217
P218
P219
P220
Capacity of the 2nd Motor
Pole Number of the 2nd Motor
Rated Voltage of the 2nd Motor
Rated Frequency of the 2nd Motor
Rated Current of the 2nd Motor
Motor specifications used as benchmarks for the auto-tuning of the 2nd motor are set via these parameters.
■ Parameter P216
Data setting range(kW) 0.2, 0.4, 0.7, 1.5, 2.2, 3.7, 5.5, 7.5, 11, 15
■ Parameter P217
Data setting range (poles) 2, 4, 6
P216: The setting range of capacity of the 2nd motor is limited by the rated values of the inverter.
■ Parameter P218
Data setting range (V)
■ Parameter P219
0~500
Data setting range (Hz) 10.0~120.0
■ Parameter P220
Data setting range (A) 0.01~99.99
· Set specifications for the 2nd motor used.
· These setting values shall be taken as benchmarks for auto-tuning, please make such setting before the start of auto-tuning (parameter P202) of the
2nd motor.
· The specifications of motor are defined by the combination of various rated voltages, rated frequencies amd rated currents.
【 For example】380V/50Hz/1.0A; 400V/60Hz/1.5A
The rated voltage should be set after the AC power voltage actually used to input voltage to the MK300 inverter had been selected.
In addition, be sure to set the rated current based on the combination due to that the rated current varies with the different rated voltage and rated frequency.
· Torque limitation of the 2nd motor (parameter P228) is conducted according to the internal arithmetic of the setting value of rated current of the 2nd motor (P220).
The limitation operation cannot be normally performed if the setting value of P220 is incorrect.
Related parameters: P202, P228
189
Appendix Function Parameter List
P221
P222
P223
P224
P225
Primary Resistance of the 2nd Motor
Secondary Resistance of the 2nd Motor
Energizing Inductance of the 2nd Motor
Leakage Inductance of the 2nd Motor
Energizing Current of the 2nd Motor
Motor constants of the 2nd motor shall be saved after the auto-tuning of the
2nd motor is done.
■ Parameter P221
Data setting range(Ω)
■ Parameter P222
0.00~99.99
Data setting range(Ω)
■ Parameter P223
0.00~99.99
Data setting range(mH) 0.0~5000
■ Parameter P224
Data setting range(mH) 0.0~999.9
■ Parameter P225
Data setting range (A) 0.01~99.99
· Various motor constants shall be automatically saved after the auto-tuning
(parameter P202) of the 2nd motor is done.
· In principle, the values saved after the auto-tuning can be used directly.
Related parameters: P202
190
Appendix Function Parameter List
P226
P227
Speed Control Percentage Increment of the 2nd Motor
Speed Control Integral Increment of the 2nd Motor
Set the speed control increment of the 2nd motor for the internal arithmetic of sensorless vector control.
■ Parameter P226
Data setting range 0.01~10.00
■ Parameter P227
Data setting range 0.01~10.00
· Applicable initial values of various motors had been set. Normally, such initial values can be used directly.
· In the actual operation in sensorless vector control mode, adjustment to such parameter can sometimes enhance the stability and responsiveness to the torque variation.
Adjust the values in small increments during parameter adjustment and verify their effectiveness through actual running test.
· The adjustment of such parameter will cause the normal rotation control unable to be maintained when some values are applied.
When adjusting parameters, please conduct the test by taking into account the safety in case of abnormal rotation.
191
Appendix Function Parameter List
P228
Torque Limit Level of the 2nd Motor
Set the limit value for torque current of the 2nd motor in the sensorless vector control mode.
Data setting range (%) 50~400
· The inverter will be forced to come to stop because of the protection function if the torque current increases due to that the torque is too large.
Therefore, it is necessary to set a limit value for the torque current to prevent the force stop.
· The output frequency shall be automatically changed for the control when the torque current reaches the limit value.
· To disable the limitation, please set the upper limit value to “400”.
· When it is required to prevent a force stop to the utmost extent, it is suggested to set the limit value to 200 or less.
The increase of the limit value are likely to cause it to reach the force stop level before the implementation of such limitation.
· Such torque limitation is conducted according to the internal arithmetic of the setting value of rated current of the 2nd motor (P220).
The limitation operation cannot be normally performed if the setting value of
P220 is incorrect.
Related parameters: P220
192
Appendix Function Parameter List
P301
Multi-step speed Function Selection
Each control function can be set when using parameter P101 to P106 to set
SW1 to SW6 to be used as multi-step speed functions.
Setting value
0
Details
Set to “multi-step speed frequency operation”
1
2
Set to “2nd/3rd/4th acceleration/deceleration operation”
Set to “acceleration/deceleration linked with multi-step speed frequency operation”
Set to “timer controlled multi-step speed frequency operation” 3
4
Set to “timer controlled acceleration/deceleration linked with multi-step speed frequency operation”
If the setting value is “0” to “2”, SW1 to SW6 can only be used after they have been set to “multi-step speed function” via parameter P101 to P106.
If the setting value is “3” or “4”, SW1 to SW6 are invalid even if they have been set to “multi-step speed function” via parameter P101 to P106.
Multi-step speed frequency operation (setting value = “0”)
The 2nd/3rd/4th acceleration/deceleration operation (setting value = “1”)
Acceleration/deceleration linked with multi-step speed frequency operation
(setting value = “2”)
■ Setting value = “0”: multi-step speed frequency operation
Up to 16 steps can be set by SW in multi-step speed frequency operation.
Acceleration/deceleration time is fixed to “the 1st Acceleration/Deceleration
Time” (parameter P001, P002).
When functions of SW1 to SW6 are all set to “1” and “r1” (multi-step speed SW input function), 4 SWs (starting from the one with the smallest No.) can be valid as multi-step speed command SW.
The 2nd to the 16th speed frequencies are set via parameter P302 to P316.
■ Setting value = “1”: The 2nd/3rd/4th acceleration/deceleration operation
When the frequency is fixed to the 1st speed, up to 4 acceleration/deceleration times can be changed through SW.
The 2nd to the 4th acceleration/deceleration times can be set via parameter
P317 to P322.
193
Appendix Function Parameter List
■ Setting value = “2”: Acceleration/deceleration linked with multi-step speed frequency operation
4 SWs can be used to link up to 16 speed steps and 4 acceleration/deceleration times to perform multi-step speed frequency operation.
SW1
(Note
1)
SW2
(Note
1)
SW3
(Note
1)
SW4
(Note
1)
ON
OFF
ON
OFF
OFF
ON
OFF
OFF multi-step speed frequency operation
Frequency
The 4th speed
The 5th speed
P301=0
Acceleration
/deceleration time
2nd/3rd/4th acceleration/deceleration operation
P302=1
Acceleration/deceleration linked with multi-step speed frequency operation
P303=2
Frequency
Acceleration
/deceleration time
The 1st acceleration
/deceleration
The 2nd acceleration
/deceleration
The 3rd acceleration
/deceleration
The 4th acceleration
/deceleration
Frequency
The 1st speed
The 2nd speed
The 3rd speed
The 4th speed
Acceleration
/deceleration time
The 1st acceleration
/deceleration
The 2nd acceleration
/deceleration
The 3rd acceleration
/deceleration
The 4th acceleration
/deceleration
The 5th speed
OFF ON ON OFF The 7th speed The 1st acceleration
/deceleration
The 1st speed
ON ON ON OFF The speed
The speed
The 7th speed
ON OFF OFF ON The 10th speed
ON ON
OFF OFF
OFF ON
ON ON
The 12th speed
The 13th speed
The 1st acceleration
/deceleration
The 10th speed The 1st acceleration
/deceleration
The 12th speed
The 13th speed
OFF ON ON ON The 15th speed The 15th speed
The 16th speed
(Note 1) When the functions of any 4 SWs of SW1 to SW6 are set to “1” and “r1”
(multi-step speed SW input function), the four SWs (starting from the one with the smallest No.) can be valid as multi-step speed command SW.
< Example > When SW1, SW2, SW4 and SW5 are set to multi-step speed SW input function, SW4 and SW5 will be allocated to the column (see Table above) previously occupied by SW3 and SW4.
194
Appendix Function Parameter List
■ Example of multi-step speed frequency operation (setting value = “0”)
Up to sixteen levels of frequency can be selected, switched and controlled by 4 button signals.
(The 1st speed: setting signal of P004, the 2nd to 16th speed: setting frequency of P302 toP316)
· Set any 4 buttons of SW1 to SW6 to multi-step speed function buttons.
(Set P101 to P106 to “1” or “r1”.)
· With this function, 1 button, 2 buttons and 3 buttons are used to input 2-step speed, 4-step speed and 8-step speed respectively.
· The inverter will stop (0 V stop) when the 2nd to 16th speed frequency (P302 to P316) are set to “0” and this multi-step speed frequency is selected.
195
196
Appendix Function Parameter List
■ Example of the 2nd/3rd/4th acceleration/deceleration operation (setting value = “1”)
Four groups of acceleration/deceleration times can be selected, switched and controlled with two SW signals.
(The 1st acceleration/deceleration time: P001 and P002, the 2nd to 4th acceleration/deceleration time: P317 to P322)
· Set any two buttons of SW1 to SW6 to multi-step speed function buttons.
(Set P301 to P306 to “1” or “r1”)
Appendix Function Parameter List
■ Example of Acceleration/deceleration linked with multi-step speed frequency operation (setting value = “2”)
The 2nd, 3rd and 4th speed can be linked (combined) with the 2nd, 3rd and 4th acceleration/deceleration by using two SW signals.
· Set any two buttons of SW1 to SW6 to multi-step speed function buttons.
(Set P101 to P106 to “1” or “r1”)
· The 1st speed is the command value of frequency setting signal set via parameter P004.
· The 1st acceleration time is set via parameter P001.
The 1st deceleration time is set via parameter P002.
· The 2nd to 16th speed frequency are set via parameter P302 to P316.
The 2nd to 4th acceleration/deceleration time are set via parameter P317 to
P322.
Related parameters: P101 to P106, P302 to P322
197
Appendix Function Parameter List
Timer controlled multi-step speed frequency operation (setting value = “3”)
Timer controlled acceleration/deceleration linked with multi-step speed frequency operation (setting value = “4”)
■ Setting Value = “3”: Timer controlled multi-step speed frequency operation
During timer controlled multi-step speed frequency operation, the acceleration/deceleration time can be fixed to 8 steps. Upon the input of the run command, the inverter will automatically switch to the next speed after running for a period of the time set.
When SW1 to SW6 are set to “multi-step speed SW input function”, even if signals are input during the timer controlled multi-step speed operation, such signals will be invalid and the multi-step speed operation will continue.
Rotation direction and continuous operation times of timer during one cycle can be set via parameter “P323: Rotation Direction of Timer Operation” and “P324: Continuous
Operation Times of Timer” respectively. Operation mode and waiting time for timer operation from the end of one cycle to the next one can be set via parameter “P325:
Continuous Operation Mode of Timer” and “P326: Continuous Waiting Time of Timer
Operation”. Runtime for the 1st to 8th speed can be set via parameter “P327 to P334: The
1st to 8th Speed Runtime”.
■ Setting Value = “4”: Timer controlled acceleration/deceleration linked with multi-step speed frequency operation
Up to 8 steps of speeds and 4 acceleration/deceleration times can be linked to perform the timer controlled mullt-speed operation.
P301=3
Rotation
Direction
(selected bit)
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Frequency Runtime
The 1st speed
①
The 6th speed
⑥
The 7th speed
⑦
The 8th speed
⑧
The 2nd speed
②
The 3rd speed
③
The 4th speed
④
The 5th speed
⑤
The 1st speed runtime T1
The 2nd speed runtime T2
The 3rd speed runtime T3
The 4th speed runtime T4
The 5th speed runtime T5
The 6th speed runtime T6
The 7th speed runtime T7
The 8th speed runtime T8
Acceleration/ deceleration time
The 1st acceleration time A1
The 1st deceleration time D1
Rotation
Direction
(selected bit)
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Forward run/
Reverse run
0/1
Frequency
The 5th speed
⑤
The 6th speed
⑥
The 7th speed
⑦
The 8th speed
⑧
The 1st speed
①
The 2nd speed
②
The 3rd speed
③
The 4th speed
④
P301=4
Runtime
The 1st speed runtime T1
The 2nd speed runtime T2
The 3rd speed runtime T3
The 4th speed runtime T4
The 5th speed runtime T5
The 6th speed runtime T6
The 7th speed runtime T7
The 8th speed runtime T8
Acceleration/ deceleration time
The 1st acceleration/ deceleration time
A1/D1
The 2nd acceleration/ deceleration time
A2/D2
The 3rd acceleration/ deceleration time
A3/D3
The 4th acceleration/ deceleration time
A4/D4
The 1st acceleration/ deceleration time
A1/D1
198
Appendix Function Parameter List
■ Example: Mode for one cycle of timer operation
After the timer runs one cycle for times set via parameter “P324: Continuous
Operation Times of Timer”, “tEnd” will be displayed. Then the timer will return to “0000” (operation status mode) after stop command is input with “tEnd” displayed.
· During timer operation, forward/reverse run commands input from operation panel, external control and communication are invalid.
· During timer operation, operation will be stopped immediately even in cycle operation when the stop command is input.
Related parameters: P001, P002, P101 to P106, P317 to 334
199
Appendix Function Parameter List
P302
P303
P304
P305
P306
The 2nd Speed
Frequency
The 3rd Speed
Frequency
The 4th Speed
Frequency
The 5th Speed
Frequency
The 6th Speed
Frequency
P307
P308
P309
P310
P311
The 7th Speed
Frequency
The 8th Speed
Frequency
The 9th Speed
Frequency
The 10th Speed
Frequency
The 11th Speed
Frequency
P312
P313
P314
P315
P316
The 12th Speed
Frequency
The 13th Speed
Frequency
The 14th Speed
Frequency
The 15th Speed
Frequency
The 16th Speed
Frequency
The 2nd to 16th speed frequency can be set to perform the multi-step speed operation.
Data setting range (Hz) 0.0·0.2~400.0
· “0.0” indicates 0V stop.
· When under vector control, the frequency is 0.5Hz to 120.0Hz.
Related parameters: P101 to P106, P301, , P317 to P334
P317
P318
The 2nd
Acceleration
Time
The 2nd
Deceleration
Time
P319
P320
The 3rd
Acceleration
Time
The 3rd
Deceleration
Time
P321
P322
The 4th
Acceleration Time
The 4th
Deceleration Time
The 2nd to 4th acceleration/deceleration time can be set to perform the 4-step acceleration/deceleration control operation.
The 2nd to 4th acceleration/deceleration time corresponds to the frequency band of 0.2 Hz to the max. output frequency.
Data setting range (s) 0.1~3600
Increment (s)
0.1(0.1~999.9)、
1(1000~3600)
Related parameters: P101 to P106, P301 to 304, P323 to P334
200
Appendix Function Parameter List
P323
Rotation Direction of Timer Operation
Rotation direction at each level from the 1st to 8th speed can be set in “P301:
Multi-step Speed Function Selection” with the setting value of “3” or “4”.
“0” and “1” indicate forward run and reverse run respectively, while the 1st to
8th speed indicate different levels. After rotation direction is determined (“0”
(forward run) or “1” (reverse run)), the sum of 0 or 1 multiplied by addition value corresponding to each level can be acquired and used as the setting value.
(Refer to the following table. The sum of rotation direction (“0” or “1”) multiplied by addition value of each speed level is used as the setting value.)
■ Example of setting: The 1st speed=forward run, the 2nd speed=forward run, the 3rd speed=forward run, the 4th speed=forward run, the 5th speed= reverse run, the 6th speed=reverse run, the 7th speed=reverse run, the 8th speed=forward run
Speed
Rotation direction
Set value
The 1st speed forward run
The
2nd speed forward run
The
3rd speed forward run
The 4th speed forward run
The 5th speed reverse run
The
6th speed reverse run
The 7th speed reverse run
The 8th speed forward run
0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
Addition value
(0×1)+(0×2)+(0×4)+(0×8)+(1×16)+(1×32)+
(1×64)+(0×128)= 112
So the setting value is “112”.
· This function is only valid when “3” or “4” is set with “P301: Multi-step Speed
Function Selection”.
· Please note that rotation direction varies depending on the setting.
Related parameters: P001, P002, P301 to P308, P317 to P322
201
Appendix Function Parameter List
P324
Cntinuous Operation Times of Timer
Continuous operation times of timer in one cycle can be set by using the 1st to
8th speed operation as “timer operation cycle” when the setting is “3” or “4” in
“P301: Multi-step Speed Function Selection”.
Data Setting Range (times) 0·1~9999
* “0” indicates that there is no limit to operation times. After run command is input, the operation will keep on until stop command is input.
· This function is only valid when “3” or “4” is set with “P301: Multi-step Speed
Function Selection”.
· If data is changed during operation, the changed data will become valid from the next cycle.
Related parameters: P301, P325 to P326
202
Appendix Function Parameter List
P325
Continuous Operation Mode of Timer
P326
Continuous Waiting Time of Timer Operation
Operation mode and continuous waiting time of timer operation from the end of the 1st cycle to the 2nd cycle can be set when “3” or “4” is set with “P301:
Multi-step Speed Function Selection”.
If the continuous operation mode of timer is set to “1”, the continuous waiting time of timer operation will become invalid.
■ Parameter P325: Continuous Operation Mode of Timer
Setting value Details
0
After one cycle of operation, the operation returns to the 0 V stop status within the 1st deceleration time and enters the next cycle.
1
After one cycle of operation, the operating frequency will change to the 1st speed frequency of the next cycle within the 1st deceleration time.
■ Parameter P326: Continuous Waiting Time of Timer Operation
Data setting range (s) 0.0·0.1~6553
Increment (s)
0.1(0.1~999.9)、
1(1000~6553)
* “0.0” indicates that there is no waiting time.
· If mode is changed during operation, the changed mode will become valid from the next cycle.
· If data is changed during the waiting time, the changed data will become valid from the next cycle.
Related parameters: P002, P301 to P308, 317 to P324
203
Appendix Function Parameter List
P327
P328
P329
P330
The 1st Speed Runtime
The 2nd Speed Runtime
The 3rd Speed Runtime
The 4th Speed Runtime
P331
P332
P333
P334
The 5th Speed Runtime
The 6th Speed Runtime
The 7th Speed Runtime
The 8th Speed Runtime
Runtime at the 1st to 8th speed frequency can be set when “3” or “4” is set with
“P301: Multi-step Speed Function Selection”.
Data setting range (s) 0.0·0.1~6553
Increment (s)
0.1(0.1~999.9)、
1(1000~3600)
* “0.0” indicates that no operation will be performed at the set speed.
· Each function is only valid when “3” or “4” is set with “P301: Multi-step Speed
Function Selection”.
· The inverter will not operate at the set speed when the setting is “0.0”. Timer controlled multi-step speed operation will be performed only at the speed for which time is set with P327 to P334.
If data is changed during operation, the changed data will become valid from the next cycle.
Related parameters: P301 to P308, P317 to P326
204
Appendix Function Parameter List
P335
Winding Mode Control Selection
Select ON status for the winding mode control operation and the amplitude during such control.
Setting
0
Details
Winding mode control is OFF.
1
2
Amplitude is set based on the setting frequency.
Amplitude is set based on the maximum frequency.
P336
Amplitude in Winding Mode
Frequency amplitude under winding mode control can be set via this parameter.
Setting Range (%) 0.0~100.0
When P335=1, frequency amplitude (Hz) = setting frequency (Hz) × amplitude in winding mode (%)
When P335=2, frequency amplitude (Hz) = maximum frequency (Hz) ×amplitude in winding mode (%)
For the details of the winding mode control function, please refer to P335.
P337
Recoil Frequency Band Width in Winding Mode
Percentage of the recoil frequency for frequency amplitude set via parameter P336 can be set via this parameter.
Setting Range (%) 0.0~100.0
P338
Winding Mode Cycle
P339
Rise Time Coefficient of Winding Mode
Time required for one cycle of winding mode control operation and the acceleration time in one cycle can be set via these parameters.
■ Winding Mode Cycle
Setting range (sec) 0.0~3600
■ Rise Time Coefficient of Winding Mode
Setting Range (%) 0.0~100.0
The formulas of acceleration/deceleration time below can be acquired via the setting of
P338 and P339.
Rise time of triangular-wave frequency = winding mode cycle (s) × rise time coefficient of winding mode (%)
Drop time of triangular-wave frequency = winding mode cycle (s) × (100 - rise time coefficient of winding mode (%))
205
Appendix Function Parameter List
P340
Winding Mode Operation Selection
It is used for setting the winding mode operation selection.
Setting value Name
1 2-point normal mode
3 2-point random mode
■ Random Mode
When “P340: Winding Mode Operation Selection” is set to “2” or “3”, the winding mode is a random mode. And the rise time shall swing between “P341:
Max.Random Rise Time” and “P342: Min.Random Rise Time”.
■ 2-point Mode
When “P340: Winding Mode Operation Selection” is set to “1” or “3”, and “P344:
Winding Stop Length” is not set to “0”, the winding mode is a 2-point mode. In this case, the setting frequency will vary with the increase of the winding length and finally become “P302: The 2nd Speed Frequency”
Especially, when P340 is set to “3”, namely the 2-point mode is selected, in this case, the base frequency will change from the setting frequency to the 2nd speed frequency (P344 is not set “0”) with the change of the winding length, at the same time, the rise time coefficient will vary in a random range.
206
Appendix Function Parameter List
P341
Max. Random Rise
Time Coefficient
P342
Min. Random Rise Time
Coefficient
Set the maximum and minimum values of rise time for random function.
Setting Range (%) 0.0~100.0(setting unit: 0.1%)
P343
Winding Length Multiplier
When function of SW input pulse for winding length counts is set, the winding length can be calculated based on “P343: Winding Length Multiplier”.
Setting range 1~9999
P344
Winding Stop Length
The winding mode will stop when the winding length accumulates to the stop length.
Setting range (m) 0·1~600000(setting unit: 1m)
· The winding length stop function will be disabled when the setting value is
“0”.
· The relationship between the setting value and the display is as follows.
When the setting value is “1m
~
9,999m” , it will display “1
~
9999”.
When the setting value is “10,000m
~
99,999m”, it will display “1.000
~
9.999”
When the setting value is “100,000m ~ 600,000m”, it will display “10.00
~
60.00”.
207
Appendix Function Parameter List
PID control is a control method enabling the feedback value (measured value) to be consistent with the set target value. In MK300, PID control can be applied after the setting values of P118, P101 to P106 are changed to “10(r10)”. Related parameters of PID control: P345 to P356.
■ P Control (Proportional Control)
Output the operation amount (output frequency) that is in direct proportion to the deviation.
■ I Control (Integral Control)
Output the operation amount (output frequency) of the deviation integral. Which can be used to effectively control the consistence of the feedback value and the target value, however, a sharp change cannot be traced.
■ D Control (Derivative Control)
It is controlled via the value, which is obtained by derivative (slope deviation) multiplied by the time constant, to judge the deviation of the signal. Transient characteristics such as overshoot or vibration can be reduced through the derivative control.
■ PID Control Flow Chart
PID target value (SP)
P348: PID
P348: PID偏置值
Invalid: PID control switch signal = ON
Valid: PID control switch signal = OFF
(P101 to P106 = 10)
Frequency command value (set with P004)
(P345 = 0)
P345: PID target value
(P345 = 0.1~100.0%)
PID measured value (PV)
The 2nd analog input signal (set with P119 )
+
-
Deviation
(P118 = 1 or 2)
0
(P118 = 0)
PID arithmeticn
K p
( 1
T i
1
S
T d
S )
P349: proportional gain [Kp]
P350: integral time [Ti]
P349: derivative time [Td]
P349: control cycle [Ts]
+
+
PID output
P354: PID output reverse characteristic
P347: PID lower limit
P355: sleep mode operation frequency
+
-
P346: PID upper limit Invalid
Valid
P356: sleep mode operation delay
Operation amount
(output frequency)
Output
ON/OFF
P345
PID Target Value
Target value used in PID control can be set via this parameter. When the setting value is “0.0”, the frequency setting signal set with P004 shall be used as the target value.
Data setting range[%] 0.0, 0.1~100.0
P346
PID Upper Limit
Set the value obtained from the PID arithmetic not exceeding the setting value.
Set “P012: Max. Output Frequency” to “100%”.
Data setting range[%] 0.0~100.0
208
Appendix Function Parameter List
P347
PID Lower Limit
Set the value obtained from the PID arithmetic not lower than the setting value.
Set “P012: Max. Output Frequency” to “100%”.
Data setting range[%] 0.0, 0.1~100.0
P348
PID Bias
Bias corresponding to the PID output can be adjusted via this parameter. Set
“P012: Max. Output Frequency” to “100%”.
Data setting range[%] -100~100.0
P349
PID Proportional Gain(Kp)
Proportional gain used in PID arithmetic can be set via this parameter.
The larger the setting value is, the smaller the deviation is, however, instability phenomenon such as vibration will be produced if it is too large.
The smaller the setting value is, the larger the deviation between the target value (SP) and the measured value (PV) is.
Data setting range 0.1~1000
P350
PID Integral Time (Ti)
Integral time (time constant for integral computation) used in PID arithmetic can be set via this parameter.
If the deviation cannot be reduced to zero through proportional control, then this parameter must be set to eliminate the deviation.
It can quickly reach a stable status by shortening the integral time, however, overshoot or vibration will occur if the setting time is too short.
Data setting range[sec] 0.00, 0.01~360.0
※ “0.00” indicates that there is no proportional control.
P351
PIDDerivative Time (Td)
Derivative time used in in PID arithmetic can be set
The larger the setting value is, the greater the responsiveness is, but vibration will be produced accordingly. The decrease of the setting value can inhibit the overshoot, but on the other hand, the responsiveness will be weakened.
Data setting range[sec] 0.00, 0.01~10.0
※ “0.00” indicates that there is no proportional control.
209
Appendix Function Parameter List
P352
PID Control Cycle (Ts)
Execution cycle required in PID control can be set.
Data setting range[sec] 0.00, 0.01~60.0
P353
PID Output Characteristics
Forward or reverse operation output from PID arithmetic can be set via this parameter.
Setting value Details
■ Reverse Operation
Increase the operation amount (output frequency) if the deviation (SP-PV) is positive; decrease the operation amount if the deviation is negative.
<Example> Heating
Deviation >0, operation amount (output frequency) Cold operation amount UP
PID target value (SP)
+
-
PID measured value (PV)
Deviation <0, operation amount (output frequency) Hot operation amount DOWN
■ Forward Operation
Increase the operation amount (output frequency) if the deviation (SP-PV) is negative; decrease the operation amount if the deviation is positive.
<Example> Cooling
PID target value (SP)
+
-
PID measured value (PV)
Deviation <0, operation amount (output frequency)
Deviation > 0, operation amount (output frequency)
Hot operation amount UP
Undercolling operation amount
DOWN
P354
PID Output Reverse Selection
Set whether the rotation direction can be reversed or not when the PID output is negative.
Setting range
0
1
Reverse operation is disabled.
Reverse operation is enabled.
Details
Set the output frequency to “0”, when PID output
< 0.
Perform the reverse operation according to the output value when PID output <0.
· It is invalid when P118=2.
210
Appendix Function Parameter List
P355
Sleep Mode Operation Frequency
P356
Sleep Mode Operation Delay
■ Parameter P355: Sleep Mode Operation Frequency
Data setting range (Hz) 0.0•0.2~400.0
■ Parameter P356: Sleep Mode Operation
Data setting range (s) 0.0~25.0
When output frequency < sleep mode operation frequency is set,
The inverter will stop the output after the elapse of the sleep mode operation delay.
When output frequency > sleep mode operation frequency is set,
The output will be resumed after the elapse of the sleep mode operation delay.
Output frequency
Sleep mode operation frequency
Run command
RUN STOP RUN
Sleep mode operation delay
Sleep mode operation delay
P357
Speed Search Selection at Startup
To set whether the speed search is enabled or disabled at the startup.
Setting
0
1
Details
Speed search at startup is disabled.
When speed search is selected via parameter “P101 to P106: SW1 to
SW6 Function Selection”, speed search will be performed if relevant SWs are turned ON.
Speed search at startup is enabled.
· It is disabled in sensorless vector control mode.
211
Appendix Function Parameter List
P359
Waiting Time for Speed Search
The time to start the speed search can be set via this parameter during speed search.
Setting range 0.0~100.0
· If “P033: Waiting Time” is set and the waiting time has elapsed, the inverter will enter the waiting status according to the setting value of “Waiting Time for Speed Search” and then start the speed search.
P360
Voltage Recovery Time for Speed Search
The voltage can be applied gradually at the frequency detected during speed search.
Setting range 0.1~10.0
· If the setting value is too low, overcurrent trip may occur.
P361
Speed Search Selection During Retry
When retry function is set to “enabled” via parameter “P029: Retry Function”, whether speed search is performed or not during retry after fault occurrence can be set via this parameter.
Setting Details
0
1
Disabled: speed search is not performed during retry after fault occurrence.
Enabled: speed search is performed during retry after fault occurrence.
· It is disabled in sensorless vector control mode.
P362
Speed Search Retry Selection
Whether speed search is performed again after speed search selection failure can be set via this parameter.
Setting
0
1
Details
When speed search fails or the upper limit of retry times for speed search is exceeded, “SEr” will be displayed on the operation panel and operation will be stopped.
When speed search fails or upper limit of retry times for speed search is exceeded, operation will start at the start frequency.
212
Appendix Function Parameter List
P363
Speed Search Retry Times
Speed search retry times can be set when “Speed Search Retry Selection” is selected.
Setting Range (times) 0~10
P364
Upper Limit Frequency Selection for Speed Search
Frequency range for speed search can be set via this parameter.
Setting
0
1
Details
Speed search is performed at a frequency below the maximum frequency.
Speed search is performed at a frequency lower than the previous frequency operating before the normal stop of the operation.
213
دانلود