YASKAWA
FOR VARISPEED-600 SERIES INVERTER
BRAKING UNIT
BRAKING RESISTOR UNIT
INSTRUCTIONS
MODEL: BRAKING UNIT CDBR-
BRAKING RESISTOR UNIT LKEB-
Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference.
YASKAWA MANUAL NO. TOE-C726-2F
PREFACE
Braking resistor unit and braking unit are used to consume regenerative energy from motor in the braking resistor unit at deceleration and to improve the transistor inverter braking ability.
Before using the braking resistor unit and braking unit, a thorough understanding of this manual is recommended. This instruction manual will be of great help for daily maintenance, inspection and troubleshooting.
Inverters to which the braking resistor unit and braking unit can be connected are of the following series:
-
VS − 616 Series
-
VS − 676 Series
-
VS − 866 Series
3
General Precautions
: Some drawings in this manual areshown with the protective cover or shields removed, in order to describe with more clarity. Make sure all covers and shields are replaced before operating this product.
:
Since the drawings in this manual are represented examples, some are subject to differ from delivered products.
:
This manual may be modified when necessary because of improvement of the product, modification or changes in specifications. Such modifications are denoted by a revised manual No.
:
To order a copy of this manual, if your copy has been damaged or lost, contact your YASKAWA representative.
: YASKAWA is not responsible for any modification of the product made by the user since that will void your guarantee.
4
NOTES FOR SAFE OPERATION
Read this instruction manual thoroughly before installation, operation, maintenance or inspection of the braking unit and the braking resistor unit. In this manual, NOTES FOR SAFE OPERATION are classified as “WARNING” or
“CAUTION.”
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury to personnel.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury to personnel and damage to equipment.
It may also be used to alert against unsafe practices.
Even items described in
CAUTION
may result in a vital accident in some situations. In either case, follow these important notes.
NOTE : These are steps to be taken to insure proper operation.
5
RECEIVING
CAUTION
:
Do not install or operate any braking unit or braking resistor unit which is damaged or has missing parts.
Failure to observe this caution may result in personal injury or equipment damage.
(Ref. page)
15
INSTALLATION
CAUTION
:
Lift the cabinet by the base. When moving the unit, never lift by the front cover.
Otherwise, the main unit may be dropped causing damage to the unit.
(Ref. page)
16
16
:
Mount the braking unit and braking resistor unit on nonflammable material (i.e. metal).
Failure to observe this caution can result in a fire.
:
Whenmountingmultipleunitsinanenclosure,installafanor other cooling device to keep the intake air temperature below 40
E
C.
Overheating may cause a fire or damage to the unit.
16
6
WIRING
WARNING
:
Only commence wiring after verifying that the power supply is turned OFF.
Failure to observe this warning can result in an electrical shock or a fire.
(Ref. page)
27
:
High voltage exists at all terminals of braking unit and braking resistor unit.
Failure to observe this warning can result in an electrical shock.
:
Wiring should be performed only by qualified personnel.
Failure to observe this warning can result in an electrical shock or a fire.
:
When wiring the emergency stop circuit, check the wiring thoroughly before operation.
Failure to observe this warning can result in personal injury.
27
27
27
27
: Make sure to ground the ground terminal .
(Ground resistance
200V class: 100W or less, 400V class: 10W or less)
Failure to observe this warning can result in an electrical shock.
7
CAUTION
:
Verify that the rated voltage of the braking unit and the braking resistor unit coincides with the AC power supply voltage.
Failure to observe this caution can result in personal injury or a fire.
(Ref. page)
27
27 : Do not perform a withstand voltage test of the braking unit and braking resistor unit.
It may cause semi − conductor elements to be damaged.
:
Connect braking resistors, braking resistor units, and braking units as shown in the I/O wiring examples. Use properly rated wire in accordance with table 2 on page 31.
Otherwise, a fire can occur.
27
:
Tighten terminal screws to the specified tightening torque.
Failure to observe this caution can result in a fire.
27
8
OPERATION
WARNING
:
Only turn ONthe input power supply after replacing the front cover. Do not remove the cover while current is flowing.
Failure to observe this warning can result in an electrical shock.
(Ref. page)
41
CAUTION
:
Never touch the heatsink or discharging resistor since the temperature is very high.
Failure to observe this caution can result in harmful burns to the body.
(Ref. page)
41
:
Do not check signals during operation.
The machine or the inverter may be damaged.
:
Alltheconstantsofthethebrakingunitandthebrakingresistor unit have been preset at the factory. Do not change the settings unnecessarily.
41
41
9
MAINTENANCE AND INSPECTION
WARNING
:
Never touch high − voltage terminals in the the braking unit and braking resistor unit.
Failure to observe this warning can result in an electrical shock.
:
Replace all protective covers before powering up the braking unit and the braking resistor unit. To remove the cover, make sure to shut OFF the molded − case circuit breaker.
Failure to observe this warning can result in an electrical shock.
:
Perform maintenance or inspection only after verifying that the CHARGE LED goes OFF, after the main circuit power supply is turned OFF.
The capacitors are still charged and can be dangerous.
:
Only authorized personnel should be permitted to perform maintenance, inspections or parts replacement.
[Remove all metal objects (watches, bracelets, etc.) before operation.]
(Use tools which are insulated against electrical shock.)
Failure to observe this warning can result in an electrical shock.
(Ref. page)
46
46
46
46
10
CAUTION
:
The control PC board employs CMOS ICs. Do not touch the
CMOS elements.
They are easily damaged by static electricity.
:
Do not connect or disconnect wires or connectors while power is applied to the circuit.
Failure to observe this caution can result in personal injury.
(Ref. page)
46
46
OTHERS
WARNING
:
Never modify the product.
Failure to observe this warning can result in an electrical shock or personal injury and will invalidate the guarantee.
11
WARNING INDICATION
A warning label is displayed on the front cover of the braking unit, as shown below.
Follow these instructions when handling the braking unit and the braking resistor unit .
Warning
Indication
Example of Braking Unit Model CDBR − 4045B
12
Warning Indication
May cause injury or electric shock.
⋅⋅⋅⋅ Please follow the instructions in the manual before installation or operation.
⋅⋅⋅⋅ Disconnect all power before opening front cover of unit. Wait 3 minutes until DC Bus capacitors discharge.
⋅⋅⋅⋅ Use proper grounding techniques.
13
CONTENTS
NOTES FOR SAFE OPERATION
1.
RECEIVING
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
15
2.
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3
REPLACEMENT OF CONVENTIONAL BRAKING UNITS
WITH NEW UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
16
16
25
3.
WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1
REMOVING AND REPLACING THE COVERS OF THE
BRAKING UNIT (MODELS CDBR − 2015B, − 2022B,
− 4030B, − 4045B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2
SECTION NAMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3
CIRCUITS AND WIRING SPECIFICATIONS . . . . . . . . . .
3.4
WIRING PRECAUTIONS
3.5
INTERCONNECTION
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
27
28
31
32
33
4.
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
4.1
ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .
41
4.2
POWER SUPPLY VOLTAGE SELECTION CONNECTOR
SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
4.3
MASTER/SLAVE SELECTION CONNECTOR SETTING 44
4.4
PARALLEL CONNECTION OF BRAKING UNIT 44
4.5
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
45
5.
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
46
6.
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
47
6.1
BRAKING UNIT AND BRAKING RESISTOR UNIT
APPLICATION LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
47
6.2
BRAKING UNIT FOR 575V CLASS APPLICATION LIST 49
6.3
LIST OF APPLICABLE/NOT APPLICABLE
COMBINATIONS WITH CONVENTIONAL
6.4
MODELS (VS − 616HII/H3, VS − 616GII/G3, VS
BRAKING UNIT SPECIFICATIONS
− 676) . . . .
. . . . . . . . . . . . . . . . . .
6.5
BRAKING RESISTOR UNIT SPECIFICATIONS . . . . . . . .
50
51
52
14
1. RECEIVING
1. RECEIVING
The braking resistor unit and braking unit have been put through severe tests at the factory before shipment. After unpacking, however, check and see the following.
If any malfunctions are found, contact your YASKAWA representative.
: Their nameplate data meet your requirements.
:
They have sustained no damage while in transit.
: Fastening bolts and screws are not loose.
15
2. INSTALLATION
2.1 LOCATION
If the units are temporarily stored or machine stops for an extended length of time, the following precautions should be taken. Store the units under the following conditions.
:
Free from rainfall and drops of water.
:
Clean and dry.
: Free from corrosive gases and liquids.
:
Free from dirt and dust.
: Ambient temperature: 14 to 104 E F, − 10 to 40 E C.
: Humidity: 90% RH or less (no condensation)
: Free from vibration.
2.2 INSTALLATION
For full use of the braking resistor unit or braking unit functions, install the units in a location to satisfy the following conditions:
Figs. 1 to 8 show the external dimensions and the spaces from the periphery.
:
Provide the spaces shown in Figs. 1 to 8 between the units and the periphery.
:
Since the braking resistor unit generates heat, provide sufficient spaces from devices which are weak against heat.
: Install the units at such locations that all requirements described in Par.
2.1 “LOCATION” are satisfied.
: Install the units in the directions shown in Figs. 1 to 8. There will be no problem if they are installed vertically.
16
4 − M4 MTG HOLE
2.
INSTALLATION
2.83 (72) 2.73 (66.5)
1.18 ( 30 )
OR MORE
1.5 (38) 1.5 (38)
5.04 (128)
5.51 (140)
3 − LEAD WIRE OUTLET
[0.87 (20) DIA RUBBER BUSH]
1.18 ( 30 )
OR MORE
Fig. 1
4.51 (114.5)
5.45 (138.5)
Braking Unit Dimensions in inches (mm) CDBR − 2015B, − 2022B, − 4030B,
− 4045B
17
3.94 (100)
4 − M6
MTG HOLE
MAIN CIRCUIT
TERMINAL M4
2.30
(58.5)
3 − LEAD WIRE
OUTLET
1.10 (28) DIA
RUBBER BUSH
1.18 (30)
OR MORE
1.97 (50)
3.94 (100)
5.51 (140)
1.18 (30)
OR MORE
6.57 (167)
Fig. 2 Braking Unit Dimensions in inches (mm) CDBR − 5037B
18
2.
INSTALLATION
5.51 (140)
4 − M6
MTG HOLE
Fig. 3
MAIN CIRCUIT
TERMINAL M5
3.86 (98)
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2 − LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
3.94 (100)
2.32 1.97 (50)
(59)
5.51 (140)
7.09 (180)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Braking Unit Dimensions in inches (mm) CDBR − 2045B
19
5.51 (140)
4 − M6
MTG HOLE
MAIN CIRCUIT
TERMINAL M6 4.09
(104)
3.94 (100)
2.32 1.97 (50)
(59) 5.51 (140)
7.09 (180)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Fig. 4 Braking Unit Dimensions in inches (mm) CDBR − 2110B
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2 − LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
20
2.
INSTALLATION
7.09 (180)
4 − M6
MTG HOLE
MAIN CIRCUIT
TERMINAL M5
3.86 (98)
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2 − LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
5.45 (138.5)
2.70
1.97 (50)
(68.5) 7.09 (180)
8.66 (220)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Fig. 5 Braking Unit Dimensions in inches (mm) CDBR − 4090B, − 5110B
21
8.27 (210)
4 − M6
MTG HOLE
Fig. 6
MAIN CIRCUIT
TERMINAL M6 4.09
(104)
WIRE OUTLET 1.10 (28)
DIA RUBBER BUSH
2 − LEAD WIRE OUTLET
1.38 (35) DIA RUBBER
BUSH
6.16 (156.5)
4.67 (118.5) 1.97 (50)
8.27 (210)
9.84 (250)
1.18 (30)
OR MORE
1.18 (30)
OR MORE
4.37 (111)
6.14 (156)
7.87 (200)
Braking Unit Dimensions in inches (mm) CDBR − 4220B, − 5300B
22
2.
INSTALLATION
Braking Resistor
Unit Model
(LKEB −
P
)
20P7
21P5
22P2
23P7
25P5
27P5
40P7
41P5
42P2
43P7
45P5
47P5
Dimensions in inches (mm)
A B C D E
4.13 (105) 10.83 (275) 1.97 (50) 10.24 (260) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6
4.13 (105) 10.83 (275) 1.97 (50) 10.24 (260) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
5.12 (130) 13.78 (350) 2.95 (75) 13.19 (335) M5
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6
9.84 (250) 13.78 (350) 7.87 (200) 13.19 (335) M6
Fig. 7 Braking Resistor Unit Dimensions in inches (mm) [for 0.5 to 10HP (0.4 to
7.5kW)]
23
Braking Resistor
Unit Model
(LKEB −
P
)
2011
2015
2018
2022
4011
4015
4018
4022
4030
4037
4045
Dimensions in inches (mm)
A B C D E
10.48 (266) 21.38 (543) 9.69 (246) 13.39 (340) M8
14.02 (356) 21.38 (543) 13.23 (336) 13.39 (340) M8
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
13.78 (350) 16.22 (412) 12.99 (330) 12.80 (325) M6
13.78 (350) 16.22 (412) 12.99 (330) 12.80 (325) M6
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
17.56 (446) 21.38 (543) 16.77 (426) 13.39 (340) M8
14.02 (356) 37.64 (956) 13.23 (336) 29.13 (740) M8
17.56 (446) 37.64 (956) 16.77 (426) 29.13 (740) M8
17.56 (446) 37.64 (956) 16.77 (426) 29.13 (740) M8
Fig. 8 Braking Resistor Unit Dimensions in inches (mm) [for 15 to 60HP (11 to
45kW)]
24
2.
INSTALLATION
2.3 REPLACEMENT OF CONVENTIONAL BRAKING
UNITS WITH NEW UNITS
To replace conventional braking units (models CDBR − 2015, − 2022, − 4030, − 4045) with new units (CDBR − 2015B, − 2022B, − 4030B, − 4045B), an exclusive − use attachment is required. Contact your YASKAWA representative.
0.79
(2 0 )
ATTACHMENT
0.28(7)
4 − M6 MTG HOLE
3.94 (100)
0.79
(2 0 )
3.94 (100)
5.51 (140) 0.28(7)
0.39 (
5.45 (138.5)
Code No.: DACT32732 − AD
0.39 (10)
Fig. 9 Mounting Dimensions of Attachment in inches (mm)
25
The main circuit terminal symbols are different between conventional models and new models. Refer to the following table.
Table 1 Main Circuit Terminal Symbols
Conventional Models New Models
N
P
P
0
B
©
¨
¨
©
0
0
26
3. WIRING
3.
WIRING
3.1
REMOVING AND REPLACING THE COVERS OF THE
BRAKING UNIT (MODELS CDBR
−
2015B,
−
2022B,
−
4030B,
−
4045B)
(1) Removing and Replacing the Terminal Cover
For removing, grasp the terminal cover at (1) on both sides and then lift in the direction of (2). For replacing, reverse the method.
Terminal
Cover
(2) Removing and Replacing the Indicating Cover
Remove the terminal cover first. Push down on the lever in the direction of
(1) and lift the cover in the direction of (2). For replacing, reverse the method.
Indicating Cover
(2)
Lever
(1)
27
3.2
SECTION NAMES
Figs. 10, 11 and 12 show appearance and each section name of braking unit and braking resistor unit respectively.
Thermal overload relay protects the braking resistor unit for models LKEB − 20P7 to − 27P5, and thermal protector protects the braking resistor unit for models
LKEB − 2011 to − 2022 and − 4018 to − 4045.
BRAKING UNIT MODEL:CDBR − 2015B
200V CLASS FOR 15kW
May cause injury or electric shock.
Please follow the instructions in the manual before installation or operation.
Disconnect all power before opening front cover of unit. Wait 3 minutes until DC Bus capacitors discharge.
Use proper grounding techniques.
Power Supply Selection
Connector
Master/Slave
Selection Connector
Calibration Resistor
(Adjusted Prior to
Shipment)
Operation Indicator
(Lights when Discharging.)
Charge Indicator
(Charge Lamp)
© ¨ ¨ 0
© 0 1 2 5 6 Control Circuit
Terminals 1 to 6
Lead Wire Outlet
(3 Places: Rubber Bush)
Control Circuit Terminals © ¨ ¨ 0 © 0
Fig. 10 Braking Resistor Unit Model CDBR − 2015B (Terminal Cover and
Indicationg Cover Removed)
28
3. WIRING
Thermal Overload Relay
(Automatically Reset)
Lead Wire Outlet
(Rubber Bush)
Fig. 11
Control Circuit Terminals
B, P, 1, 2
Braking Resistor Unit Model LKEB − 20P7 (Front Cover Removed)
29
Resistor
Thermal
Overload
Protector
Lead Wire Outlet
(Rubber Bush)
Control Circuit Terminals
B, P, 1, 2
Fig. 12 Braking Resistor Unit Model LKEB − 2022 (Front Cover Removed)
30
3.3 CIRCUITS AND WIRING SPECIFICATIONS
Table 2 Circuits and Wiring Specifications
Name Circuit
Terminals
Wire
Size
AWG
(mm 2 )
Max.
Torque lb ⋅ in
(N ⋅ m)
Braking Unit
( (Models CDBR
− 2015B 2022B
− 4030B, − 4045B,
− 5037B)
Main
Control
¨ ¨
© ©
0
0
1 2 3
4 5 6
12
(3.5
18
−
−
−
(0.75
10
5.5)
14
− 2)
(1.50)
Braking Unit
(Model CDBR
− 2045B, − 4090B,
− 5110B)
Braking Unit
( (Model
CDBR − 2110B,
− 4220B, − 5300B)
Main
Control
Main
¨ ¨
© ©
1 2 3
4 5 6
¨
©
¨
©
0
0
0
0
1 2 3
4 5 6
(5.5
(0.75
− 2)
(8
10 − 8
18 −
− 8) 600V
14
4 (22)
8
−
− 6
14) *1
18 − 14
(0.75
− 2)
(High
Voltage) *3 vinyl sheathed wire or equivalent
M5
M4
M6
21.7
(2.45)
15.6
(1.76)
43.4
(4.90)
Braking Resistor
Unit
(Model LKEB j )
−
Control
Main
Control
B
1
P
2
12
(3.5
18
−
−
−
(0.75
10
5.5)
14
− 2)
M4
M4
(M5)
M4
*2
15.6
(1.76)
15.6 (1.76)
(21.7(2.45))
15.6 (1.76)
*1 For wire size of 8 − 6 (8 − 14), use UL1283 heat − resistant vinyl − insulated wire or equivalent.
*2 M4 for Models LKEB − 20P7 to − 27P5 or − 40P7 to − 4015.
M5 for Models LKEB − 2011 to − 2022 or − 4018 to − 4045.
*3 Models − 5037B, − 5100B, and − 5300B can reach an operating voltage of 1040 VDC.
Please select wire which is suitable for the operating voltage.
31
3.4 WIRING PRECAUTIONS
(1) Wiring Leading − in Method
Lead in the wire through the knockout hole on the unit bottom. Since the knockout hole is provided with a rubber bush, cut the rubber bush central crosswise with a blade and lead the wire through.
(2) Separation from Signal Lines
Since strong noise component is superimposed on the braking resistor unit and braking unit wiring, separate the units from signal lines which are weak against noise.
(3) Wiring Distance
Wiring distance between the braking resistor unit and braking unit or braking unit and inverter must be provided as shown in Fig. 13. Make sure to bundle the wires between the units.
Braking Resistor
Unit
Braking Unit Inverter
32.8ft
(10m) or less
Fig. 13 Wiring Distance
16.4ft
(5m) or less
32
3. WIRING
(4) Grounding Method
:
Mount the braking resistor unit on a grounded metallic plate. When it cannot be mounted on a grounded metallic plate, pull out the lead wire from the mounting screw section to ground.
: Braking unit grounding terminal must be provided with class 3 ground
(ground resistance: 100 Ω or less.)
: Use the sizes specified in “INTERNAL CONNECTION SPECIFI-
CATIONS” for grounding cables.
3.5 INTERCONNECTION
Figs. 14 to 20 show the interconnecting diagrams of the braking unit or braking resistor unit and VS − 616G5.
Refer to Par. 3.3, “Wiring Precautions” for proper wiring in actual wiring design and work.
Be sure to connect braking resistors or braking resistor units to the braking units.
Connect only braking resistors or Braking Resistor Units (LKEB − XXXX) to Braking Units.
NOTE If using another braking resistor instead of YASKAWA braking resistor unit, be sure to protect by thermal overload relay.
33
or 380
34
∼ ∼
∼ ∼
Fault Contact
3. WIRING
Level Detection
∼ ∼
∼ ∼
Fault Contact
35
Level Detection
∼ ∼
∼ ∼
Fault Contact
36
3. WIRING
Level Detection
∼ ∼
Voltage Selection 460/440/415/ 400/380V
∼ ∼
Fault Contact
37
Level Detection ∼ ∼
) Voltage Selection 460/440/415/ 400/380V
∼ ∼
Fault Contact
38
3. WIRING
Level Detection
∼ ∼
∼ ∼
Fault Contact
39
Level Detection
∼ ∼
Voltage Selection 460/440/415/ 400/380V
∼ ∼
Fault Contact
40
4.
OPERATION
4. OPERATION
4.1 ADJUSTMENT
The braking resistor unit and braking unit do not have to be adjusted.
Especially, do not readjust the braking unit except in the case described in Par. 4.2,
“Power Supply Voltage Selection Connector Setting.”
4.2 POWER SUPPLY VOLTAGE SELECTION CON-
NECTOR SETTING
It may be necessary to select power supply voltage selection connector for braking unit according to main circuit power supply type. Table 3 shows the relationship between the power supply voltage selection connector and braking start voltage.
The following is the setting prior to shipment:
: 200V class: 220V
:
400V class: 440V
:
575V class: 575V
For removing the terminal cover and the indicating cover, refer to Par. 3.1.
41
BRAKING UNIT MODEL:CDBR − 20 1 5B
200V CLASS FOR 1 5kW
May cause injury or electric shock.
Please follow the instructions in the manual before installation or operation.
Disconnect all power before opening front cover of unit. Wait 3 minutes until DC Bus capacitors discharge.
Use proper grounding techniques.
© ¨ ¨ 0 © 0 1 2 5 6
200V class
200V
208V
220V
230V
4 00V class
380V
400V
415V
440V
460V
Fig. 2 1 Braking Unit Power Supply Voltage Selection
(Models CDBR − 20 1 5B, − 2022B, − 4030B, − 4045B, Terminal Cover and
Indicating Cover Removed)
42
4.
OPERATION
200V class
200V
208V
220V
230V
575V class
500V
400V class
380V
400V
415V
440V
460V
575V
Fig. 22 Braking Unit Power Supply Voltage Selection
(Models CDBR − 2045B, − 2110B, − 4090B, − 5037B, − 5110B, − 5300B,
Indicating Cover Removed)
Table 3
200V
Class*
Power
Supply
Voltage
230V
220V
208V
200V
−
Power Supply Voltage Selection Connector and Braking Start Voltage
Braking Start
Voltage
(PN Bus − bar
Voltage)
380V (TYP)
365V (TYP)
345V (TYP)
330V (TYP)
−
400V
Class*
Power
Supply
Voltage
460V
440V
415V
400V
380V
*Allowable voltage fluctuation is ¦ 10%
Braking Start
Voltage
(PN Bus −
Voltage) bar
760V (TYP)
730V (TYP)
690V (TYP)
660V (TYP)
630V (TYP)
575V
Class*
Power
Supply
Voltage
575V
−
−
500V
−
Braking Start
Voltage
(PN Bus −
Voltage) bar
950V (TYP)
−
−
825V (TYP)
−
43
4.3 MASTER/SLAVE SELECTION CONNECTOR SETTING
Selection Connector Setting MASTER side is selected prior to shipment. Use the units without changing the setting.
SLAVE side is selected when more than one braking unit is combined to use and braking start levels must coincide. Refer to Par. 4.4, “Parallel Connection of Braking Unit” for details.
4.4 PARALLEL CONNECTION OF BRAKING UNIT
For using more than one parallel − connected braking unit, connect and select the connectors as follows. (See Fig. 23.)
:
Braking units have a MASTER/SLAVE selection connector. (See Fig.
10.) Select MASTER side only for braking unit 1 and select SLAVE side for braking units 2 and 3.
: Connect thermal protector on the braking resistor unit and thermoswitch on the braking unit in parallel. Refer to Figs. 15 and 18 for proper wiring.
: Use properly rated wire in accordance with table 2 on page 31.
: Use twisted − pair wires of 1mm or less for connection between 5, 6 and
1, 2 of the braking units.
: Parallel connection of braking unit is possible up to a maximum of 10 units.
44
4.
OPERATION
¨ 3
Inverter
Unit
©
1
2
© ¨
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
1
P
2
Braking
B
¨ 0 © 0
Resistor
Unit
© ¨
MASTER
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
1 2
B
Braking
Resistor
Unit
P
¨ 0 © 0
MASTER
©
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
1
P
2
B
Braking
Resistor
Unit
¨ ¨ 0 © 0
MASTER
Level Detection SLAVE
+15 5 1
6
P
2
SLAVE
Braking Unit 2
5 1
6
P
2
SLAVE
Braking Unit 3
5
6
Braking Unit 1 3 4
Cooling Fin
Overheat Contact
(Thermoswitch Contact)
3 4
Cooling Fin
Overheat Contact
(Thermoswitch Contact)
3 4
Cooling Fin
Overheat Contact
(Thermoswitch Contact)
Fig. 23 Example of Parallel Connection of Three Braking Units
4.5 OPERATION
Check that required deceleration characteristics can be obtained. While the braking unit is operating, BRAKE lamp lights for easy check of operation.
NOTE High voltage is applied to the braking unit. At normal operation, do not operate the unit without cover.
45
5. TROUBLESHOOTING
Only authorized personnel should be permitted to perform maintenance and inspections or replace parts.
No.
Fault Status Corrective Action
1
Braking resistor unit overload relay (or thermal p t ) t i h decelerating.
t
Inverter trips at overvoltage (OV).
Cause
:
Without braking unit
Inverter built − in main circuit discharging transistor short circuited
:
With braking unit
Braking unit main circuit discharging transistor short circuited
Improper braking unit power supply voltage selection connector setting
(Power supply voltage > power supply voltage selection position)
Insufficient braking resistor unit capacity
Braking unit fault
Replace the inverter.
Replace the unit.
Set it again.
Examine the braking conditions again.
Check and repair.
Replace the unit.
3
Braking resistor unit overload relay (or thermal protector) sometimes trips.
Insufficient braking resistor unit capacity
Examine the braking conditions again.
4
Braking unit trips by heat sink overheat.
Excessive start/stop switching frequency
Excessive load inertia
Improper combination of braking
Examine the operating conditions again.
unit and braking resistor unit
Reset.
Ambient temperature 104 E F (40 E C) Reduce it.
46
6. SPECIFICATIONS
6. SPECIFICATIONS
6.1
BRAKING UNIT AND BRAKING RESISTOR UNIT
APPLICATION LIST
200 to 230V
Inverter
Max Applicable
Motor Capacity
HP(kW)
0.5 (0.4)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
75 (55)
100 (75)
120 (90)
150 (110)
Braking Unit
Model
(CDBR
− P )
—
—
—
—
—
—
—
2015B
2015B
2022B
2022B
2015B
2015B
2022B
2022B
2110B
2110B
2110B
Unit
Q’ty
2
1
2
2
1
1
1
2
1
1
—
—
—
1
—
—
—
—
Braking Resistor Unit
Model
(LKEB
− P )
2015
2018
2022
2015
2015
2022
2022
2022
2022
2022
20P7
20P7
21P5
22P2
23P7
25P5
27P5
2011
Resistor Spec.
(per unit)
70W 200
70W 200
260W 100
260W 70
390W 40
520W 30
780W 20
3000W 10
4800W 8
3000W 10
3000W 10
Ω
Ω
Ω
Ω
Ω
Ω
2400W 13.6
Ω
4800W 6.8
4800W 6.8
4800W 6.8
4800W 6.8
4800W 6.8
4800W 6.8
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Unit
Q’ty
2
3
2
2
4
5
1
2
1
1
1
1
1
1
1
1
1
1
Approx.
Braking
Torque
(10%ED)
%
125
125
125
125
100
120
100
110
120
100
220
125
125
120
125
115
125
125
47
380 to 460V
Inverter
Max Applicable
Motor Capacity
HP(kW)
0.5 (0.4)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
75 (55)
100 (75)
150 (110)
200 (160)
300 (220)
400 (300)
800 (600)
Braking Unit
Model
(CDBR
−
P
)
—
—
—
—
4030B
4030B
4030B
4045B
—
—
—
—
—
4045B
4030B
4045B
4030B
4220B
4220B
4220B
4220B
Unit
Q’ty
1
1
1
1
—
—
—
—
—
—
—
—
—
2
3
1
2
2
4
1
1
Braking Resistor Unit
Model
(LKEB
−
P
)
40P7
40P7
41P5
42P2
43P7
45P5
47P5
4011
4015
4018
4022
4030
4037
4045
4030
4045
4030
4045
4037
4045
4045
Resistor Spec.
(per unit)
Unit
Q’ty
70W 750 Ω
70W 750 Ω
260W 400 Ω
260W 250 Ω
1
1
1
1
390W 150 Ω
520W 100 Ω
780W 75 Ω
1040W 50 Ω
1560W 40 Ω
1
1
1
1
1
4800W 32 Ω
4800W 27.2
Ω
6000W 20 Ω
1
1
1
9600W 1 6 Ω
9600W 13.6
Ω
6000W 20 Ω
9600W 13.6
Ω
1
1
2
2
6000W 20 Ω
9600W 13.6
Ω
9600W 16 Ω
9600W 13.6
Ω
3
4
5
6
9600W 13.6
Ω 12
Approx.
Braking
Torque
(10%ED)
%
135
130
135
125
125
125
125
125
230
130
125
135
135
125
135
145
100
140
110
110
110
48
6. SPECIFICATIONS
6.2
BRAKING UNIT FOR 575V CLASS APPLICATION LIST
Inverter
Max Applicable
Motor Capacity
HP(kW)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
75 (55)
100 (75)
120 (90)
150 (110)
200 (160)
Braking Unit
Model
(CDBR −
P
)
Unit Q’ty
—
—
—
—
—
—
5037B
5037B
5037B
5037B
5037B
5110B
5110B
5110B
5300B
2
2
1
1
1
—
—
—
1
—
—
—
1
1
1
Braking Resistor Unit
Resistor Spec.
560W 150 Ω
560W 150 Ω
750W 100 Ω
1100W 75 Ω
1500W 50 Ω
2300W 40 Ω
2800W 38 Ω
3900W 33 Ω
4900W 27 Ω
5900W 22
12000W 11
15000W 9
21000W 6.8
Ω
7200W 18 Ω
9800W 13.6
Ω
Ω
Ω
Ω
Approx.
Braking
Torque
(10%ED)
110
110
110
110
105
125
140
140
125
%
180
125
140
110
110
100
49
Conventional
Model
VS − 616HII/H3
VS − 616GII/G3
VS − 676
VS − 616HII/H3
VS − 616GII/G3
VS − 676
VS − 616HII/H3
VS − 616GII/G3
VS − 676
VS − 616HII/H3
VS − 616GII/G3
VS − 676
6.3
LIST OF APPLICABLE/NOT APPLICABLE COMBINA-
TIONS WITH CONVENTIONAL MODELS (VS
−
616HII/
H3, VS
−
616GII/G3, VS
−
676)
Braking
Unit
—
Model
CDBR − 15H etc.
Models
CDBR
−
−
2015,
2015B etc.
Models
CDBR
− 2015,
− 2015B etc.
Braking Resistor Unit
Applicable/
Not Applicable
Model
LKEB − 20P7 etc.
Model
LKEB etc.
Model
LKEB etc.
Model
LKEB etc.
−
−
−
2015
4.8K
2015
Applicable
Applicable
Not applicable
Applicable
Remarks
See connection examples of Fig 14.
Use sequencer to break power supply side on thermal protector of the braking resistor unit side.
No thermal protective function of braking resistor unit.
See connection examples of Figs. 15 to 18.
50
6. SPECIFICATIONS
6.4 BRAKING UNIT SPECIFICATIONS
Braking Unit Model
CDBR −
Applicable Motor Output
HP (kW)
Max. Discharge
Current(A)
Output charac-
(peak value) *
Rated Discharge
Current (A) teristics Braking Start
Voltage
Max. Hysteresis
Error
Power
Supply
VDC
Protective
Functions
Fin Overheat
Power Charge
Indication
Envionmental
Conditions
Location
Altitude
Ambient
Temperature
Storage
Transportation
Temperature
Humidity
Vibration
Protective Configuration
Heat Loss (W)
201
5B
20
(15)
40
200V to 300V
2022
B
30
2045
B
60
(22)
60
(45)
100
2110
B
150
(110)
250
4030
B
40
(30)
40
380V to 460V
4045
B
60
4090
B
120
(45) (90)
60 100
4220
B
300
(220)
250
500V to 575V
5037
B
57
5110
B
150
(37)
40
(110)
5300
B
400
(300)
15 20 30 80 15 18
¦ 6V
30
630/660/690/730/760V
Approx. 16V
80 15 30 80
330/345/365/380V
Approx. 8V
¦ 3V 825V/ 950V ¦ 8V
243 (1.35
¢
400V peak
200 ¢ 0.9) to 460 (1.35
¢ 380 ¢ 0.9) to
800V peak
Thermostat
Charge lamp stays ON until bus voltage drops below 50V.
Indoor (protected from corrosive gases and dust)
1000m max.
+14 to 104
E
F ( − 10 to +40
E
C) (not frozen)
Approx.
20V
607
(1.35
¢ 500 ¢ 0.9) to
1000V
32 38
− 4 to 140
E
F ( − 20 to +60
E
C)
90%RH (non − condensing)
1G at 10 to less than 20Hz, up to 0.2G at 20 to 50 Hz
Wall − mounted enclosed type
31 64 54 59 35 71 22
100
53
250
116
* Loading time rate can be used below 10% ED (max. 10 sec.)
51
Model
(LKEB
− P )
41P5
42P2
43P7
45P5
47P5
4011
4015
4018
4022
4030
4037
4045
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
40P7
6.5 BRAKING RESISTOR UNIT SPECIFICATIONS
Specifications
200 to
70W 200 Ω
260W 100 Ω
260W 70 Ω
390W 40 Ω
520W 30 Ω
780W 20 Ω
2400W 13.6
Ω
3000W 10 Ω
4800W 8 Ω
4800W 6.8
Ω
70W 750 Ω
260W 400 Ω
260W 250 Ω
390W 150 Ω
520W 100 Ω
780W 75 Ω
1040W 50 Ω
380 to
460 1560W 40 Ω
4800W 32 Ω
4800W 27.2
Ω
6000W 20 Ω
9600W 16 Ω
9600W 13.6
Ω
Allowable
Average
Dissipated
Power
(W)
440
600
740
880
1200
1500
1800
60
89
150
220
300
440
600
740
880
30
30
60
89
150
220
300
Allowable
Average
Current
(Effective Value)
(A)
0.39
0.60
1.0
1.5
2.0
3.0
3.9
4.8
5.7
7.7
9.7
11.5
0.39
0.77
1.1
1.9
2.7
3.9
5.7
7.7
9.6
11.4
0.20
Allowable
Ambient
Temperature
+14 to 122 E F
( ( 10 to +50 E C)
52
6. SPECIFICATIONS
6.6 MODELS AND CODE NOS. OF BRAKING UNIT AND
BRAKING RESISTOR UNIT
(1) Braking Unit
Inverter
Voltage HP ( kW )
200 to
230V
380 to
460V
500 to
575V
20 (15) CDBR − 2015B 72600 − R2150B
30 (22) CDBR − 2022B 72600 − R2220B
60 (45) CDBR − 2045B 72600 − R2450B
150 (110) CDBR − 2110B 72600 − R21100B
40 (30) CDBR − 4030B 72600 − R4300B
60 (45) CDBR − 4045B 72600 − R4450B
120 (90) CDBR − 4090B 72600 − R4900B
300 (220) CDBR − 4220B 72600 − R42200B
50 (37) CDBR − 5037B 72600 − R5370B
150 (110) CDBR − 5110B 72600 − R51100B
400 (300) CDBR − 5300B 72600 − R53000B
53
(2) Braking Resistor Unit
Inverter
Voltage HP(kW)
200 to
230V
380 to
460V
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5)
10 (7.5)
15 (11)
20 (15)
25 (18.5)
30 (22)
1 (0.75)
2 (1.5)
Resistor Spec.
(per unit)
70W 200 Ω
260W 100 Ω
260W 70 Ω
390W 40 Ω
520W 30 Ω
780W 20 Ω
2400W 13.6
Ω
3000W 10 Ω
4800W 8 Ω
4800W 6.8
Ω
70W 750 Ω
260W 400 Ω
260W 250 Ω
390W 150 Ω
520W 100 Ω
780W 75 Ω
1040W 50 Ω
1560W 40 Ω
4800W 32 Ω
4800W 27.2
Ω
6000W 20 Ω
9600W 16 Ω
9600W 13.6
Ω
LKEB − 20P7 72600 − K2P70
LKEB − 21P5 72600 − K2010
LKEB − 22P2 72600 − K2020
LKEB − 23P7 72600 − K2030
LKEB − 25P5 72600 − K2050
LKEB − 27P5 72600 − K2070
LKEB − 2011 72600 − K2110
LKEB − 2015 72600 − K2150
LKEB − 2018 72600 − K2180
LKEB − 2022 72600 − K2220
LKEB − 40P7 72600 − K4P70
LKEB − 41P5 72600 − K4010
LKEB − 42P2 72600 − K4020
LKEB − 43P7 72600 − K4030
LKEB − 45P5 72600 − K4050
LKEB − 47P5 72600 − K4070
LKEB − 4011 72600 − K4110
LKEB − 4015 72600 − K4150
LKEB − 4018 72600 − K4180
LKEB − 4022 72600 − K4220
LKEB − 4030 72600 − K4300
LKEB − 4037 72600 − K4370
LKEB − 4045 72600 − K4450
54
英文 No.4-4(A4) メカトロ製品用 TOE
FOR VARISPEED-600 SERIES INVERTER
BRAKING UNIT
BRAKING RESISTOR UNIT
INSTRUCTIONS
IRUMA BUSINESS CENTER
480, Kamifujisawa, Iruma, Saitama 358-8555, Japan
Phone 81-42-962-5696 Fax 81-42-962-6138
YASKAWA ELECTRIC AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone 1-847-887-7000 Fax 1-847-887-7370
MOTOMAN INC. HEADQUARTERS
805 Liberty Lane West Carrollton, OH 45449, U.S.A.
Phone 1-937-847-6200 Fax 1-937-847-6277
YASKAWA ELETRICO DO BRASIL COMERCIO LTD.A.
Avenida Fagundes Filho, 620 Bairro Saude-Sao Paulo-SP, Brazil CEP: 04304-000
Phone 55-11-5071-2552 Fax 55-11-5581-8795
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany
Phone 49-6196-569-300 Fax 49-6196-569-398
Motoman Robotics Europe AB
Box 504 S38525 Torsas, Sweden
Phone 46-486-48800 Fax 46-486-41410
Motoman Robotec GmbH
Kammerfeldstra β e 1, 85391 Allershausen, Germany
Phone 49-8166-90-100 Fax 49-8166-90-103
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods Cumbernauld, G68 9LF, United Kingdom
Phone 44-1236-735000 Fax 44-1236-458182
YASKAWA ELECTRIC KOREA CORPORATION
Kfpa Bldg #1201, 35-4 Youido-dong, Yeongdungpo-Ku, Seoul 150-010, Korea
Phone 82-2-784-7844 Fax 82-2-784-8495
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
151 Lorong Chuan, #04-01, New Tech Park Singapore 556741, Singapore
Phone 65-6282-3003 Fax 65-6289-3003
YASKAWA ELECTRIC (SHANGHAI) CO., LTD.
4F No.18 Aona Road, Waigaoqiao Free Trade Zone, Pudong New Area, Shanghai 200131, China
Phone 86-21-5866-3470 Fax 86-21-5866-3869
YATEC ENGINEERING CORPORATION
4F., No.49 Wu Kong 6 Rd, Wu-Ku Industrial Park, Taipei, Taiwan
Phone 886-2-2298-3676 Fax 886-2-2298-3677
YASKAWA ELECTRIC (HK) COMPANY LIMITED
Rm. 2909-10, Hong Kong Plaza, 186-191 Connaught Road West, Hong Kong
Phone 852-2803-2385 Fax 852-2547-5773
BEIJING OFFICE
Room No. 301 Office Building of Beijing International Club, 21
Jianguomenwai Avenue, Beijing 100020, China
Phone 86-10-6532-1850 Fax 86-10-6532-1851
TAIPEI OFFICE
9F, 16, Nanking E. Rd., Sec. 3, Taipei, Taiwan
Phone 886-2-2502-5003 Fax 886-2-2505-1280
SHANGHAI YASKAWA-TONGJI M & E CO., LTD.
27 Hui He Road Shanghai China 200437
Phone 86-21-6553-6060 Fax 86-21-5588-1190
BEIJING YASKAWA BEIKE AUTOMATION ENGINEERING CO., LTD.
30 Xue Yuan Road, Haidian, Beijing P.R. China Post Code: 100083
Phone 86-10-6233-2782 Fax 86-10-6232-1536
SHOUGANG MOTOMAN ROBOT CO., LTD.
7, Yongchang-North Street, Beijing Economic Technological Investment & Development Area,
Beijing 100076, P.R. China
Phone 86-10-6788-0551 Fax 86-10-6788-2878
YASKAWA ELECTRIC CORPORATION
YASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade
Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
MANUAL NO. TOE-C726-2F
○ Printed in Japan August 2002 91-3
24