advertisement
![6.8 Data Map List. RKC INSTRUMENT HA930 | Manualzz 6.8 Data Map List. RKC INSTRUMENT HA930 | Manualzz](http://s3.manualzz.com/store/data/053366330_1-37797c2b6d460a9c678afaa7743175d8-360x466.png)
6. MODBUS COMMUNICATION PROTOCOL
6.8 Data Map List
In this communication, the variable is handled as 4 bytes data.
In this communication, one variable use two register addresses (Address of high-order word,
Address of low-order word).
Tow-word data is read and written from low-order words to high-order words in order.
*
* If Modbus 1 is selected in the communication protocol selection of the engineering mode, data is read and written from high-order words to low-order words in order.
Register address 0500H to 0535H handles it when I do confirmation and change of set value belonging to memory area except control area. (See P. 97)
RO: Read only R/W: Read and Write
Name
Input 1_measured value
(PV1) monitor
Input 2_measured value
(PV2) monitor
Unused
Unused
Unused
Input 1_ set value (SV1) monitor
Register address
Hexadecimal Decimal
Attri-
Low- High- Low- High- bute order order order order
Data range
0000 0001 0 1 RO Input 1_input scale low to
Input 1_input scale high
0002 0003 2 3 RO Input 2_input scale low to
Input 2_input scale high
0004 0005 4 5
0006 0007 6 7
0008 0009 8 9
Factory set value
Refer- ence page
P.
P.
P.
Input 2_ set value (SV2) monitor
Remote input value monitor
000A 000B 10 11 RO Input 1_setting limiter
(low) to
Input 1_setting limiter
(high)
000C 000D 12 13 RO Input 2_setting limiter
(low) to
Input 2_setting limiter
(high)
000E 000F 14 15 RO Input 1_setting limiter
(low) to
Input 1_setting limiter
(high)
P.
P.
Continued on the next page.
70
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Low- order
High- order bute
0010 0011 16 17
Data range
Unused
Input 1_burnout state 0012 0013 18 19 RO 0: OFF
1: ON
Input 2_burnout state 0014 0015 20 21 RO
Unused 0016 0017 22 23
0018 0019 24 25 RO 0: OFF
1: ON
001A 001B 26 27 RO
Event 1 state
Event 2 state
Event 3 state
Event 4 state
Unused
Unused
Input 1_ manipulated output value (MV1) monitor
001C 001D 28 29 RO
0020 0021 32 33
0022 0023 34 35
0024 0025 36 37 RO −
001E 001F 30 31 RO
5.0 to +
105.0 %
0026 0027 38 39 RO Input 2_ manipulated output value (MV2) monitor
Factory set value
Refer- ence page
P.
P.
P.
P.
P.
P.
P.
P.
Continued on the next page.
IMR01N13-E2
71
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Error code
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Low- order
High- order bute
Data range data b0: Adjustment data error b1: EEPROM error b2: A/D conversion error b3: RAM check error b4: Hardware
configuration b5: Software
configuration b6: Unused b7: Watchdog timer error b8 to b10:
Unused b11: Program busy b12 to b31:
Unused
Data 0: OFF 1: ON
[Decimal number:
0 to 4095]
Event input (DI) state 002A 002B 42 43 RO Bit data b0: DI 1 state b1: DI 2 state b2: DI 3 state b3: DI 4 state b4: DI 5 state b5 to b31:
Unused
Data 0: Contact open
1: Contact closed
[Decimal number: 0 to 31]
Operation mode state 002C 002D 44 45 RO Bit data b0: Control STOP b1: Control RUN b2: Input 1_Manual mode
(Including Input 1_
Factory set value
Refer- ence page
P.
P.
P. b3: Input 2_Manual mode
(Including Input 2_ b4: Remote mode b5 to b31:
Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 31]
Continued on the next page.
72
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Memory area soak time monitor
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Low- order
High- order bute
Data range
002E 002F 46 47 RO 0 minute 00.00 second to
9 minutes 59.99 seconds or
0 hour 00 minute 00
second to 9 hours 59
minutes 59 seconds
Input 1_PID/AT transfer
Input 2_PID/AT transfer
Input 1_
Auto/Manual transfer
Input 2_
Auto/Manual transfer
0030 0031 48 49 R/W 0: PID control
1: Autotuning (AT)
No PID/AT transfer is valid prior to factory shipment. The transfer
0032 0033 50 51 R/W becomes valid only when
“1: AT function (PI)” or
“0: AT function (PID)” is selected in AT action selection.
0034 0035 52 53 R/W 0: Auto mode
1: Manual mode
0036 0037 54 55 R/W
Remote/Local transfer
RUN/STOP transfer
Memory area selection
Event 1 set value
Event 2 set value
Event 3 set value
0038 0039 56 57 R/W 0: Local mode
003C 003D 60
1: Remote mode
003A 003B 58 59 R/W 0: Control RUN
1: Control STOP
61 R/W 1 to 16
003E 003F 62 63 R/W
0040 0041 64 65 R/W
0042 0043 66 67 R/W
Deviation:
− Input span to
+ Input span
Process/SV:
Input scale low to
Input scale high
Factory set value
Refer- ence page
P.
Continued on the next page.
IMR01N13-E2
73
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Control loop break alarm 1 (LBA1) time
LBA1 deadband
Event 4 set value
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Low- order
High- order bute
Data range
0044 0045 68 69 R/W 0 to 7200 seconds
0: OFF (Unused)
0046 0047 70 71 R/W 0.0 to Input span
Factory set value
Refer- ence page
Control loop break alarm 2 (LBA2) time
0048 0049 72 73 R/W Deviation:
− Input span to
+ Input span
Process/SV:
Input scale low to
Input scale high
004A 004B 74 75 R/W 0 to 7200 seconds
0: OFF (Unused)
LBA2 deadband 004C 004D 76 77 R/W 0.0 to Input span
Input 1_set value (SV1) 004E 004F 78 79 R/W Input 1_setting limiter
(low) to Input 1_ setting limiter (high)
Input 1_ proportional band
Input 1_integral time 0052 0053 82 83 R/W 0 to 3600 seconds,
0.0 to 3600.0 seconds or
0.00 to 360.00 seconds *
0, 0.0 or 0.00: PD action
* Varies with the setting
of the integral/derivative
time decimal point
position selection.
Input 1_derivative time 0054 0055 84 85 R/W 0 to 3600 seconds,
0.0 to 3600.0 seconds or
0.00 to 360.00 seconds *
0, 0.0 or 0.00: PI action
Input 1_control response parameter
* Varies with the setting
of the integral/derivative
time decimal point
position selection.
0056 0057 86 87 R/W 0: Slow
1: Medium
2: Fast
0.00
(PI action)
P. 116
0050 0051 80 81 R/W 0.0 to 1000.0 % of input span
0 or 0.0: ON/OFF action
Continued on the next page.
74
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Low- order
High- order bute
0058 0059 88 89
Data range
Unused
Input 2_set value (SV2) 005A 005B 90 91 R/W Input 2_setting limiter
(low) to Input 2_ setting limiter (high)
Input 2_ proportional band
005C 005D 92 93 R/W TC/RTD inputs:
0 to Input span
Voltage/current inputs:
0.0 to 1000.0 % of Input
span
0 or 0.0: ON/OFF action
Input 2_integral time 005E 005F 94 95 R/W 0 to 3600 seconds,
0.0 to 3600.0 seconds or
0.00 to 360.00 seconds *
0, 0.0 or 0.00: PD action
* Varies with the setting
of the integral/derivative
time decimal point
position selection.
Factory set value
Refer- ence page
Input 2_derivative time 0060 0061 96 97 R/W 0 to 3600 seconds,
0.0 to 3600.0 seconds or
0.00 to 360.00 seconds *
0, 0.0 or 0.00: PI action
* Varies with the setting
of the integral/derivative
time decimal point
position selection.
Input 2_control response parameter
0062 0063 98 99 R/W 0: Slow
1: Medium
2: Fast
0064 0065 100 101 Unused
Input 1_setting change rate limiter (up)
Input 1_setting change rate limiter (down)
0066 0067 102 103 R/W 0.0 to Input span/unit time *
0068 0069 104 105 R/W
0.0: OFF (Unused)
* Unit time: seconds
(factory set value)
Continued on the next page.
IMR01N13-E2
75
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Input 2_setting change rate limiter (down)
Input 2_setting change rate limiter (down)
Area soak time
Link area number
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Low- order
High- order bute
Data range
006A 006B 106 107 R/W 0.0 to Input span/unit time *
0.0: OFF (Unused)
006C 006D 108 109 R/W * Unit time:
60
(factory set value)
006E 006F 110 111 R/W 0 minute 00.00 second to
9 minutes 59.99 seconds or
0 hour 00 minute 00
second to 9 hours 59
minutes 59 seconds
0070 0071 112 1113 R/W 0 to 16
0: OFF (No link)
Unused 0072 0073 114 115
Unused 0074 0075 116 117
Input 1_PV bias 0076 0077 118 119 R/W − Input span to
+ Input span
Input 1_PV digital filter 0078 0079 120 121 R/W 0.00 to 10.00 seconds
0.00: OFF (Unused)
Input 1_PV ratio 007A 007B 122 123 R/W 0.500 to 1.500
Input 1_
PV low input cut-off
Input 1_ proportional cycle time
007C 007D 124 125 R/W 0.00 to 25.00 % of input span
007E 007F 126 127 R/W 0.1 to 100.0 seconds
Factory set value
0.0
Relay contact output:
20.0 seconds
Refer- ence page
P. 118
P. 125
Voltage pulse output and triac output:
2.0 seconds
Input 1_ manual output value
0080 0081 128 129 R/W MV scaling low to
MV scaling high
Continued on the next page.
76
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Input 2_PV bias
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
0082 0083 130 131 R/W − Input span to
+
Data range
Input span
Input 2_PV digital filter 0084 0085 132 133 R/W 0.00 to 10.00 seconds
0.00: OFF (Unused)
Input 2_PV ratio
Input 2_
PV low input cut-off
Input 2_ proportional cycle time
0086 0087 134 135 R/W 0.500 to 1.500
0088 0089 136 137 R/W 0.00 to 25.00 % of input span
008A 008B 138 139 R/W 0.1 to 100.0 seconds
Factory set value
Reference page
Relay contact output:
20.0 seconds
P. 125
Voltage pulse output and triac output:
2.0 seconds
Input 2_ manual output value
Set lock level
008C 008D 140 141 R/W Input 2_output limiter
(low) to Input 2_output limiter (high)
008E 008F 142 143 R/W Bit data b0: Lock only setting items other than SV and events (EV1 to
EV4). b1: Lock only events
(EV1 to EV4). b2: Lock only set b3 to b31:
Unused
Data 0: Unlock 1: Lock
[Decimal number: 0 to 7]
Continued on the next page.
IMR01N13-E2
77
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
EEPROM storage state 0090 0091 144 145 RO 0: The content of the
EEPROM does not
coincide with that of
Factory set value
Reference page
P.
1: The content of the
with that of the RAM.
EEPROM storage mode 0092 0093 146 147 R/W 0: Set values are store to
the EEPROM when set
values are changed.
1: Not set values are store
to the EEPROM when
set values are changed.
0094 0095 148 149 Unused
Unused 0096 0097 150 151
0098 0099 152 153 Unused
Unused
PV1_ peak hold value monitor
009A 009B 154
009C 009D 156
155
157
RO Input 1_input scale low to
Input 1_input scale high
PV1_bottom hold value monitor
PV1_hold reset
Displays the maximum
PV of Input 1.
009E 009F 158 159 RO Input 1_input scale low to
Input 1_input scale high
Displays the minimum
PV of Input 1.
00A0 00A1 160 161 R/W 0, 1
0: Hold reset execution
If 0 is written, the hold value is reset to return to 1.
The polling of “1” is always made.
P.
P.
Continued on the next page.
78
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
PV2_ peak hold value monitor
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
00A2 00A3 162 163 RO Input 2_input scale low to
Input 2_input scale high
PV2_bottom hold value monitor
Displays the maximum
PV of Input 2.
00A4 00A5 164 165 RO Input 2_input scale low to
Input 2_input scale high
Displays the minimum
PV of Input 2.
PV2_hold reset
Interlock release
Auto-zero
(Input 1)
00A6 00A7 166 167 R/W 0, 1
0: Hold reset execution
If 0 is written, the hold value is reset to return to 1.
The polling of “1” is always made.
00A8 00A9 168 169 R/W 0, 1
0: Interlock release
execution
If 0 is written, the interlock is released.
00AA 00AB 170 171 R/W 0, 1, 3
1: Zero point adjustment
execution
Writing “1” starts
zero point adjustment,
and then “1” returns to
“0” after the
adjustment is finished.
3: Adjustment error
Writing “0” returns to
a normal state.
Relevant pressure sensors:
CZ-100P, CZ-200P,
CZ-GP100 (without
amplifier), the other strain
gauge type sensors
Factory set value
Reference page
P.
P.
Continued on the next page.
IMR01N13-E2
79
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Auto calibration
(Input 1)
Name
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
00AC 00AD 172 173 R/W 0 to 3
1: Auto calibration
execution
Writing “1” starts auto
calibration, and it
changes to “2” during
the adjustment and
returns to “0” after the
adjustment is finished.
3: Adjustment error
Writing “0” returns to
a normal state.
Relevant pressure sensors:
CZ-GP100 (without
amplifier), the other strain
gauge type sensors
Unused 00AE
⋅
⋅
⋅
01FE
00AF
⋅
⋅
01FF
174
⋅
⋅
510
175
⋅
⋅
⋅
511
STOP display selection 0200 0201 512 513 R/W 0: Displays on the
Factory set value
Reference page
Bar graph display selection
Bar graph resolution setting
Unused
1: Displays on
the set value (SV) unit
0202 0203 514 515 R/W 0: No display
1: Input 1_manipulated
output value (MV)
2: Input 1_measured
3: Input 1_set value (SV)
4: Input 1_deviation value
5: Unused (Not available)
6: Input 2_manipulated
output value (MV)
7: Input 2_measured
8: Input 2_set value (SV)
9: Input 2_deviation value
0204 0205 516 517 R/W 1 to 100 digit/dot
0206 0207 518 519
Continued on the next page.
80
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Auto/Manual transfer key operation selection
(A/M)
Name
Remote/Local transfer key operation selection
(R/L)
RUN/STOP transfer key operation selection
(R/S)
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
0208 0209 520 521 R/W 0: Unused
1: Auto/Manual transfer
for input 1
2: Auto/Manual transfer
for input 2
3: Auto/Manual transfer
for input 1 and input 2
020A 020B 522 523 R/W 0: Unused
1: Remote/Local transfer
020C 020D 524 525 R/W 0: Unused
1: RUN/STOP transfer
Input 1_ input type selection
Factory set value
Reference page
020E 020F 526 527 R/W Voltage (V)/current (I) inputs
− 19999 to + 99999
14: 0 to 20 mA DC
15: 4 to 20 mA DC
16: 0 to 10 V DC
17: 0 to 5 V DC
18: 1 to 5 V DC
19: 0 to 1 V DC
20: 0 to 100 mV DC
21: 0 to 10 mV DC
24: ± 100 mV DC
25: ± 10 mV DC
26: ± 10 V DC
27: ± 5 V DC
28: ± 1 V DC
Relevant pressure sensors:
CZ-GP100,
the other voltage/current
type sensors
Pressure sensor input
0.0 to 250.0 MPa
29: Resin pressure sensor
Relevant pressure sensors:
CZ-100P, CZ-200P,
CZ-GP100 (without
amplifier), the other strain
gauge type sensors
22, 23: Unused available)
Depends on model code.
When not specifying:
Pressure sensor input
P. 137
Continued on the next page.
IMR01N13-E2
81
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Input 1_
Name display unit selection
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
0210 0211 528 529 R/W 2: MPa
3: bar
4: kgf/cm 2
5: psi
Input 1_ decimal point position
0212 0213 530 531 R/W 0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
* Less than 1 MPa:
Decimal point position 0 to 4
Less than 10 MPa:
Decimal point position 0 to 3
Less than 100 MPa:
Decimal point position 0 to 2
100 MPa or more:
Decimal point position 0 or 1
Voltage (V)/current (I) inputs:
Decimal point position 0 to 4
Input 1_input scale high 0214 0215 532 533 R/W Input scale low to
Maximum value of the selected input range
Voltage (V)/current (I) inputs: − 19999 to + 99999
* Varies with the setting of the decimal point position
Factory set value
Pressure sensor input:
2
V/I: 0
Pressure sensor input:
50.0
V/I: 100.0
Input 1_input scale low 0216 0217 534 535 R/W Minimum value of the selected input range to Input scale high
Input 1_input error determination point
(high)
Pressure sensor input:
0.0
Voltage (V)/current (I) inputs: − 19999 to + 99999
* Varies with the setting of the decimal point position
V/I: 0.0
0218 0219 536 537 R/W Input scale low − (5 % of input span) to Input scale high + (5 % of input span)
Pressure sensor input:
Input scale high + (5 % of input span)
V/I: 105.0
Reference page
P. 138
P. 140
P. 141
P. 142
Input 1_input error determination point
(low)
Input 1_ burnout direction
Input 1_square root extraction selection
Power supply frequency selection
021A 021B 538 539 R/W Pressure sensor input:
Input scale low − (5 % of input span)
P. 143
V/I: − 5.0
021C 021D 540 541 R/W 0: Upscale
1: Downscale
021E 021F 542 543 R/W 0: Unused
1: Used
0220 0221 544 545 R/W 0: 50
1: 60 Hz
Continued on the next page.
82
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Input 2_ input type selection
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
0222 0223 546 547 R/W TC input
0: K 200 to + 1372 ° C
− 328.0 to + 2501.6 ° F
1: J − 200 to + 1200 ° C
− 328.0 to + 2192.0 ° F
2: R 50 to + 1768 ° C
− 58.0 to + 3214.4 ° F
3: S 50 to + 1768 ° C
− 58.0 to + 3214.4 ° F
4: B 0 to 1800 ° C
32.0 to 3272.0 ° F
5: E 200 to + 1000 ° C
− 328.0 to + 1832.0 ° F
6: N 0 to 1300 ° C
32.0 to 2372.0 ° F
7: T 200 to + 400 ° C
− 328.0 to + 752.0 ° F
8: W5Re/W26Re
0 to 2300 ° C
32.0 to 4172.0 ° F
9: PLII
0 to 1390 ° C
32.0 to 2534.0 ° F
RTD input (3-wire system)
12: Pt100
− 200 to + 850 ° C
− 328.0 to + 1562.0 ° F
13: JPt100
− 200 to + 600 ° C
− 328.0 to + 1112.0 ° F
Voltage (V)/ current (I) inputs:
− 19999 to + 99999
14: 0 to 20 mA DC
15: 4 to 20 mA DC
16: 0 to 10 V DC
17: 0 to 5 V DC
18: 1 to 5 V DC
19: 0 to 1 V DC
20: 0 to 100 mV DC
21: 0 to 10 mV DC
24: ± 100 mV DC
25: ± 10 mV DC
26: ± 10 V DC
27: ± 5 V DC
28: ± 1 V DC
22, 23: Unused available)
Factory set value
Depend on the model code.
When not specifying:
Type K
Reference page
P. 137
Continued on the next page.
IMR01N13-E2
83
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Input 2_ display unit selection
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
0224 0225 548 549 R/W 0: ° C
1: ° F
Data range
Input 2_ decimal point position
0226 0227 550 551 R/W 0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Input 2_input scale high 0228 0229 552 553 R/W TC/RTD inputs:
Input scale low to
Maximum value of
the selected input range
Factory set value
TC/RTD:
Maximum value of the selected input range
Voltage (V)/current (I) inputs:
− 19999 to + 99999
* Varies with the setting
of the decimal point
position
V/I: 100.0
Input 2_input scale low 022A 022B 554 555 R/W TC/RTD inputs:
Minimum value of
the selected input range
to Input scale high
Input 2_input error determination point
(high)
TC/RTD:
Minimum value of the selected input range
Voltage (V)/current (I) inputs:
− 19999 to + 99999
* Varies with the setting
of the decimal point
position
V/I: 0.0
022C 022D 556 557 R/W Input scale low − (5 % of input span) to Input scale high + (5 % of input span)
TC/RTD:
Input scale high + (5 % of input span)
Reference page
P. 140
P. 141
P. 142
Input 2_input error determination point
(low)
022E 022F 558 559 R/W
V/I: 105.0
TC/RTD:
Input scale low − (5 % of input span)
V/I: − 5.0
P. 143
Continued on the next page.
84
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Input 2_ burnout direction
Input 2_square root extraction selection
Event input logic selection
Output logic selection
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
0230 0231 560 561 R/W 0: Upscale
1: Downscale
0232 0233 562 563 R/W 0: Unused
1: Used
0234 0235 564 565 R/W 0 to 15
0236 0237 566 567 R/W 3 to 8, 11
1, 2, 9, and 10:
Unused (Not available)
Factory set value
Reference page
1-input controller: 3
2-input controller: 5
P. 149
0238 0239 568 569 R/W 0.0 to 600.0 seconds Output 1 timer setting
Output 2 timer setting
Output 3 timer setting
Output 4 timer setting
Output 5 timer setting
Transmission output 1_ type selection
023A 023B 570 571 R/W
023C 023D 572 573 R/W
023E 023F 574 575 R/W
0240 0241 576 577 R/W
0242 0243 578 579 R/W 0: None
1: Input 1_measured
0.0 P. 151
0.0 P. 151
0.0 P.
2: Input 1_set value (SV)
3: Input 1_deviation value
4: Input 1_manipulated
output value (MV)
5: Input 2_measured
6: Input 2_set value (SV)
7: Input 2_deviation value
8: Input 2_manipulated
output value (MV)
9: Unused (Not available)
Continued on the next page.
IMR01N13-E2
85
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Transmission output 1_ scale high
Transmission output 1_ scale low
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
0244 0245 580 581 R/W
0246 0247 582 583 R/W
Data range
Measured value (PV) and set value (SV):
Input scale low to
Input scale high
Manipulated output value (MV):
− 5.0 to + 105.0 %
Deviation:
− Input span to
+ Input span
Factory set value
Reference page
PV/SV:
Input scale high
MV: 100.0
Deviation:
+ Input span
PV/SV:
Input scale low
MV: 0.0
Deviation:
− Input span
P. 154
P. 155
Transmission output 2_ type selection
0248 0249 584 585 R/W 0: None
1: Input 1_measured
2: Input 1_set value (SV)
3: Input 1_deviation value
4: Input 1_manipulated
output value (MV)
5: Input 2_measured
Transmission output 2_ scale high
Transmission output 2_ scale low
024A 024B 586 587 R/W
024C 024D 588 589 R/W
6: Input 2_set value (SV)
7: Input 2_deviation value
8: Input 2_manipulated
output value (MV)
9: Unused (Not available)
Measured value (PV) and set value (SV):
Input scale low to
Input scale high
Manipulated output value (MV):
− 5.0 to + 105.0 %
Deviation:
− Input span to
+ Input span
PV/SV:
Input scale high
MV: 100.0
Deviation:
+ Input span
PV/SV:
Input scale low
MV: 0.0
Deviation:
− Input span
P. 154
P. 155
Continued on the next page.
86
Continued from the previous page.
6. MODBUS COMMUNICATION PROTOCOL
Name
Transmission output 3_ type selection
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
024E 024F 590 591 R/W 0: None
1: Input 1_measured
Factory set value
Reference page
2: Input 1_set value (SV)
3: Input 1_deviation value
4: Input 1_manipulated
output value (MV)
5: Input 2_measured
6: Input 2_set value (SV)
7: Input 2_deviation value
8: Input 2_manipulated
output value (MV)
9: Unused (Not available)
Transmission output 3_ scale high
Transmission output 3_ scale low
0250 0251 592
0252 0253 594
593
595
R/W
R/W
Measured value (PV) and set value (SV):
Input scale low to
Input scale high
Manipulated output value (MV):
− 5.0 to + 105.0 %
Deviation:
− Input span to
+ Input span
PV/SV:
Input scale high
MV: 100.0
Deviation:
+Input span
PV/SV:
Input scale low
MV: 0.0
P. 154
P. 155
Deviation:
− Input span
Event 1 type selection 0254 0255 596 597 R/W 0: None
1: Deviation high
2: Deviation low
3: Deviation high/low
4: Band
5: Process high
6: Process low
7: SV high
8: SV low
Event 1 hold action 0256 0257 598 599 R/W 0: OFF
1: ON
2: Re-hold action ON
Continued on the next page.
IMR01N13-E2
87
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Event 1 differential gap
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
0258 0259 600 601 R/W 0 to Input span
Factory set value
Reference page
Pressure sensor input:
2.0 MPa
P. 161
Event 2 assignment
TC/RTD:
2.0 ° C [ ° F]
V/I: 0.2 % of input span
Event 1 action at input error
Event 1 assignment
025A 025B 602 603 R/W 0: Normal processing
1: Turn the event output
ON
025C 025D 604 605 R/W 1: For input 1
2: For input 2
Event 2 type selection 025E 025F 606 607 R/W 0: None
1: Deviation high
2: Deviation low
3: Deviation high/low
4: Band
5: Process high
6: Process low
7: SV high
8: SV low
Event 2 hold action 0260 0261 608 609 R/W 0: OFF
1: ON
2: Re-hold action ON
Event 2 differential gap 0262 0263 610 611 R/W 0 to Input span Pressure sensor input:
2.0 MPa
P. 161
TC/RTD:
2.0 ° C [ ° F]
V/I: 0.2 % of input span
Event 2 action at input error
0264 0265 612 613 R/W 0: Normal processing
1: Turn the event output
ON
0266 0267 614 615 R/W 1: For input 1
2: For input 2
Continued on the next page.
88
IMR01N13-E2
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
Event 3 type selection 0268 0269 616 617 R/W 0: None
1: Deviation high
2: Deviation low
3: Deviation high/low
4: Band
5: Process high
6: Process low
7: SV high
8: SV low
9: Control loop break
Factory set value
0
Reference page
P. 156
Event 3 hold action 026A 026B 618 619 R/W 0: OFF
1: ON
2: Re-hold action ON
Event 3 differential gap 026C 026D 620 621 R/W 0 to Input span
0 P. 159
Pressure sensor input:
2.0 MPa
P. 161
TC/RTD:
2.0 ° C [ ° F]
Event 3 action at input error
Event 3 assignment
026E 026F 622 623 R/W 0: Normal processing
1: Turn the event output
ON
0270 0271 624 625 R/W 1: For input 1
2: For input 2
Event 4 type selection 0272 0273 626 627 R/W 0: None
1: Deviation high
2: Deviation low
3: Deviation high/low
4: Band
5: Process high
6: Process low
7: SV high
8: SV low
9: Control loop break
V/I: 0.2 % of input span
0
1
0
P. 163
P. 165
P. 156
Continued on the next page.
IMR01N13-E2
89
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Event 4 hold action
Event 4 differential gap
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
0274 0275 628 629 R/W 0: OFF
1: ON
2: Re-hold action ON
0276 0277 630 631 R/W 0 to Input span
Factory set value
0
Reference page
P. 159
Pressure sensor input:
2.0 MPa
P. 161
TC/RTD:
2.0 ° C [ ° F]
V/I: 0.2 % of input span
Event 4 action at input error
0278 0279 632 633 R/W 0: Normal processing
1: Turn the event output
ON
Event 4 assignment 027A 027B 634 635 R/W 1: For input 1
2: For input 2
Unused 027C 027D 636 637
Unused 027E 027F 638 639
Unused 0280 0281 640 641
Unused 0282 0283 642 643
Hot/Cold start selection 0284 0285 644 645 R/W Power failure less than 3 seconds:
0: Hot 1
1: Hot 1
2: Hot 1
3: Hot 2
4: Hot 2
5: Cold
6: Hot 1
7: Hot 2
8: Stop
Power failure 3 seconds or more:
0: Hot 1
1: Hot 2
2: Cold
3: Hot 2
4: Cold
5: Cold
6: Stop
7: Stop
8: Stop
Continued on the next page.
90
IMR01N13-E2
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Input 2_use selection
Unused
Unused
SV tracking
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
0288 0289 648 649
Data range
0286 0287 646 647 R/W 0: Single loop control
1: Remote input
028A 028B 650 651
Input 1_control action type selection
Input 1_ integral/derivative time decimal point position selection
Input 1_derivative gain
Input 1_ON/OFF action differential gap (upper)
028C 028D 652 653 R/W 0: Unused
1: Used
028E 028F 654 655 R/W 0: Direct action
1: Reverse action
0290 0291 656 657 R/W 0: No decimal place
1: One decimal place
2: Two decimal places
0292 0293 658
0294 0295 660
659
661
R/W 0.1 to 10.0
R/W 0 to Input span
Factory set value
Reference page
Input 1_ON/OFF action differential gap (lower)
0296 0297 662 663 R/W
Pressure sensor input:
1.0 MPa
V/I: 0.1 % of input span
Pressure sensor input:
1.0 MPa
V/I: 0.1 % of input span
P. 170
P. 171
0298 0299 664 665 R/W 0: Normal control
1: Manipulated Output
029A 029B 666 667 R/W Value at Input Error
Input 1_action at input error (high)
Input 1_action at input error (low)
Input 1_manipulated output value at input error
Input 1_output change rate limiter (up)
Input 1_output change rate limiter (down)
Input 1_output limiter
(high)
Input 1_output limiter
(low)
Unused
029C 029D 668
029E 029F 670
02A0 02A1 672
669
671
673
R/W −
R/W
5.0 to +
0.0: OFF
105.0
R/W 0.0 to 1000.0 %
%
/second
02A2 02A3 674 675 R/W Input 1_output limiter
02A6 02A7 678 679
(low) to 105.0 %
02A4 02A5 676 677 R/W − 5.0 % to Input 1_ output limiter (high)
−
−
5.0 P.
0.0 P. 174
5.0 P.
Continued on the next page.
IMR01N13-E2
91
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Input 2_control action type selection
Input 2_ integral/derivative time decimal point position selection
Input 2_derivative gain
Input 2_ON/OFF action differential gap (upper)
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
02A8 02A9 680 681 R/W 0: Direct action
1: Reverse action
02AA 02AB 682 683 R/W 0: No decimal place
1: One decimal place
2: Two decimal places
02AC 02AD 684
02AE 02AF 686
685
687
R/W 0.1 to 10.0
R/W 0 to Input span
Factory set value
Reference page
TC/RTD:
1.0 ° C [ ° F]
V/I: 0.1 % of input span
P. 170
Input 2_ON/OFF action differential gap (lower)
02B0 02B1 688 689 R/W TC/RTD:
1.0 ° C [ ° F]
V/I: 0.1 % of input span
P. 171
Input 2_action at input error (high)
Input 2_action at input error (low)
Input 2_manipulated output value at input error
Input 2_output change rate limiter (up)
Input 2_output change rate limiter (down)
Input 2_output limiter
(high)
Input 2_output limiter
(low)
Unused
Input 1_AT bias
02B2 02B3 690
02B4 02B5 692
02B6 02B7 694
691
693
695
R/W 0: Normal control
1: Manipulated Output
R/W Value at Input Error
R/W − 5.0 to + 105.0 %
02B8 02B9 696 697 R/W 0.0 to 1000.0 % /second
0.0: OFF
02BA 02BB 698 699 R/W
02BC 02BD 700 701 R/W Input 2_output limiter
(low) to 105.0 %
02BE 02BF 702 703 R/W − 5.0 % to Input 2_ output limiter (high)
02C0 02C1 704 705
Input 1_AT cycle
02C2 02C3 706 707 R/W − Input span to
+ Input span
02C4 02C5 708 709 R/W 0: 1.5 cycles
1: 2.0 cycles
2: 2.5 cycles
3: 3.0 cycles
−
−
5.0 P.
0.0
5.0 P.
P. 174
Continued on the next page.
92
IMR01N13-E2
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Input 1_
AT differential gap time
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
02C6 02C7 710 711 R/W 0.00 to 50.00 seconds
Input 2_AT bias 02C8 02C9 712 713 R/W − Input span to
+ Input span
Input 2_AT cycle 02CA 02CB 714 715 R/W 0: 1.5 cycles
1: 2.0 cycles
2: 2.5 cycles
3: 3.0 cycles
02CC 02CD 716 717 R/W 0.00 to 50.00 seconds Input 2_
AT differential gap time
Unused
Unused
Unused
Unused
Setting change rate limiter unit time
02CE 02CF 718
02D0 02D1 720
02D2 02D3 722
02D4 02D5 724
02D6 02D7 726
719
721
723
725
727
R/W 1 to 3600 seconds
Soak time unit selection 02D8 02D9 728 729 R/W 0: 0 hour 00 minutes 00
second to 9 hours 59
minutes 59 seconds
2: 0 minutes 00.00
seconds to 9 minutes
Factory set value
60
Reference page
P. 181
Input 1_setting limiter
(high)
Input 1_setting limiter
(low)
Input 2_setting limiter
(high)
02DA 02DB 730 731 R/W Input 1_setting limiter
(low) to Input 1_input
scale high
02DC 02DD 732 733 R/W Input 1_input scale low to
Input 1_setting limiter
(high)
02DE 02DF 734 735 R/W Input 2_setting limiter
(low) to Input 2_input
scale high
Input 1_ input scale high
Input 1_ input scale low
Input 2_ input scale high
P. 182
P. 183
P. 182
Continued on the next page.
IMR01N13-E2
93
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Input 2_setting limiter
(low)
Name
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
02E0 02E1 736 737 R/W Input 2_input scale low to
Input 2_setting limiter
(high)
ROM version display 02E2 02E3 738 739 RO Display the version of loading software.
Integrated operating time display
02E4 02E5 740 741 RO 0 to 99999 hours
Holding peak value ambient temperature display
02E6 02E7 742 743 RO − 10.0 to + 100.0 ° C
02E8 02E9 744 745 Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Alarm lamp lighting condition setting
02EA 02EB 746
02EC 02ED 748
02EE 02EF 750
02F0 02F1 752
02F2 02F3 754
02F4 02F5 756
02F6 02F7 758
02F8 02F9 760
747
749
751
753
755
757
759
761
R/W Bit
Factory set value
Reference page
Input 2_ input scale low
P. 183
P.
P.
P.
02FA 02FB 762 763 b4 to b31: Unused
Data
0: ALM lamp is not lit
1: ALM lamp is lit
[Decimal number: 0 to 15]
Unused
94
Continued on the next page.
IMR01N13-E2
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Input 1_
Name
PV1 hold function
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
02FC 02FD 764 765 R/W 0: Unused
1: Used
Factory set value
Reference page
Input 2_
PV2 hold function
02FE 02FF 766 767 R/W
Gain setting
(Input 1)
0300 0301 768 769 R/W 0.500 to 4.000 mV/V
Relevant pressure sensors:
CZ-100P, CZ-200P,
CZ-GP100 (without
amplifier), the other strain
gauge type sensors
CZ-100P/
CZ-200P:
1.500
CZ-GP100
(without amplifier), the other strain gauge type sensors:
3.330
P. 186
Linearize type selection
(Input 1)
0302 0303 770 771 R/W 0: Unused
1 to 20: Used
Relevant pressure sensors:
CZ-100P, CZ-200P
0304 0305 772 773 R/W 40.0 to 100.0 % Shunt resistance output value (Input 1)
Relevant pressure sensors:
CZ-GP100 (without
amplifier), the other strain
gauge type sensors
Input 1_
PV transfer function
0306 0307 774 775 R/W 0: Unused
1: Used
0308 0309 776 777 R/W Input 2_
PV transfer function
Input 1_MV scaling high
(Input 1)
030A 030B 778 779 R/W − 1999.9 to + 9999.9
Input 1_MV scaling low
(Input 1)
030C 030D 780 781 R/W
Decimal point position of MV scaling (Input 1)
030E 030F 782 783 R/W 0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
0
0.0
P.
P. 190
Continued on the next page.
IMR01N13-E2
95
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Input 1_AT action
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
0310 0311 784 785 R/W 0: AT function (PID)
1: AT function (PI)
Input 2_AT action 0312 0313 786 787 R/W 2: No AT function
0314 0315 788 789 RO − 5.0 to + 105.0 % Input 1_manipulated output value when transferred to Auto from
Manual
0316 0317 790 791 RO Input 2_manipulated output value when transferred to Auto from
Manual
Interlock function
Input 1_
MV transfer function
Input 2_
MV transfer function
0318 0319 792 793 R/W Bit data b0: OUT1 b1: OUT2 b2: OUT3 b3: OUT4 b4: OUT5 b5 to b31:
Unused
Data
0: No Interlock function
1: Interlock function
[Decimal number: 0 to 31]
031A 031B 794 795 R/W 0: Unused
1: Used
031C 031D 796 797 R/W
Unused 031C
⋅
⋅
04FE
031F
⋅
⋅
04FF
794
⋅
⋅
1278
795
⋅
⋅
⋅
1279
Factory set value
2
Reference page
P.
P.
0
P. 191
P. 194
96
IMR01N13-E2
6. MODBUS COMMUNICATION PROTOCOL
Items relating to the memory area other than the control area
Name
Memory area selection
Register address
Hexadecimal Decimal
Attri-
Low- High- LowHighbute order order order order
Data range
0500 0501 1280 1281 R/W 1 to 16
Factory set value
Reference page
Event 1 set value 0502 0503 1282 1283 R/W
Event 2 set value
Event 3 set value
0504 0505 1284 1285 R/W
0506 0507 1286 1287 R/W
Deviation:
− Input span to
+ Input span
Process/SV:
Input scale low to
Input scale high
Control loop break alarm 1 (LBA1) time
LBA1 deadband
Event 4 set value
0508 0509 1288 1289 R/W 0 to 7200 seconds
0: OFF (Unused)
050A 050B 1290 1291 R/W 0.0 to Input span
050C 050D 1292 1293 R/W Deviation:
− Input span to
+ Input span
Process/SV:
Input scale low to
Input scale high
Control loop break alarm 2 (LBA2) time
050E 050F 1294 1295 R/W 0 to 7200 seconds
0: OFF (Unused)
0510 0511 1296 1297 R/W 0.0 to Input span LBA2 deadband
Input 1_set value (SV1) 0512 0513 1298 1299 R/W Input 1_setting limiter
(low) to Input 1_setting limiter (high)
Input 1_ proportional band
0514 0515 1300 1301 R/W 0.0 to 1000.0 % of input span
(0 or 0.0: ON/OFF action)
Input 1_integral time 0516 0517 1302 1303 R/W 0 to 3600 seconds,
0.0 to 3600.0 seconds or
0.00 to 360.00 seconds *
(0, 0.0 or 0.00: PD action)
* Varies with the setting
of the integral/derivative
time decimal point
position selection.
0.0
100.0
5.00
P. 197
P. 198
P. 198
Continued on the next page.
IMR01N13-E2
97
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
Input 1_derivative time 0518 0519 1304 1305 R/W 0 to 3600 seconds,
0.0 to 3600.0 seconds or
0.00 to 360.00 seconds *
(0, 0.0 or 0.00: PI action)
* Varies with the setting
of the integral/derivative
time decimal point
position selection.
Input 1_control response parameter
051A 051B 1306 1307 R/W 0: Slow
1: Medium
2: Fast
Unused 051C 051D 1308 1309
Input 2_set value (SV2) 051E 051F 1310 1311 R/W Input 2_setting limiter
(low) to Input 2_setting limiter (high)
Input 2_ proportional band
Input 2_integral time
0520 0521 1312 1313 R/W TC/RTD inputs:
0 to Input span
Voltage/current inputs:
0.0 to 1000.0 % of input
span
(0 or 0.0: ON/OFF action)
0522 0523 1314 1315 R/W 0 to 3600 seconds,
0.0 to 3600.0 seconds or
0.00 to 360.00 seconds *
(0, 0.0 or 0.00: PD action)
* Varies with the setting
of the integral/derivative
time decimal point
position selection.
Factory set value
Reference page
Input 2_derivative time 0524 0525 1316 1317 R/W 0 to 3600 seconds,
0.0 to 3600.0 seconds or
0.00 to 360.00 seconds *
(0, 0.0 or 0.00: PI action)
* Varies with the setting
of the integral/derivative
time decimal point
position selection.
Continued on the next page.
98
IMR01N13-E2
6. MODBUS COMMUNICATION PROTOCOL
Continued from the previous page.
Name
Input 2_control response parameter
Register address
Hexadecimal Decimal
Attri-
Low- order
High- order
Loworder
Highorder bute
Data range
0526 0527 1318 1319 R/W 0: Slow
1: Medium
2: Fast
0528 0529 1320 1321 Unused
Input 1_setting change rate limiter (up)
Input 1_setting change rate limiter (down)
Input 2_setting change rate limiter (up)
Input 2_setting change rate limiter (down)
Area soak time
052A 052B 1322 1323 R/W
052C 052D 1324 1325 R/W
052E 052F 1326 1327 R/W
0530 0531 1328 1329 R/W
0.0 to Input span/unit time *
0.0: OFF (Unused)
* Unit time: seconds
(factory set value)
0532 0533 1330 1331 R/W 0 minute 00.00 second to
9 minutes 59.99 seconds or
0 hour 00 minute 00
second to 9 hours 59
minutes 59 seconds
0534 0535 1332 1333 R/W 0 to 16
0: OFF (No link)
Link area number
Factory set value
0.0
0.0
0.0
0.00.00
Reference page
P.
P. 200
P. 200
P. 201
IMR01N13-E2
99
7. COMMUNICATION DATA DESCRIPTION
Reference to communication data contents
(1)
Input 1_ measured value (PV1) monitor
RKC communication identifier
Modbus register address
M1
Low-order: 0000H (0)
High-order:0001H (1)
(4)
(5)
(6)
(7)
Input 2_ measured value (PV2) monitor
RKC communication identifier
Modbus register address
M0
Low-order: 0002H (2)
High-order:0003H (3)
Measured value (PV) is the input value of the controller. There are thermocouple input, resistance temperature detector input, voltage input and current input.
(8)
(9)
(1) Name:
Attribute: RO (Read only)
Digits: 7
Data range: Input scale low to Input scale high
See Input range table (P. 137)
Factory set value:
Related parameters: Decimal point position (P. 139)
Communication data name is written.
(2)
(3)
(2) RKC communication identifier:
Communication identifier of RKC communication is written.
(3) Modbus register address:
Modbus communication data register addresses are written. These register addresses are written using both of hexadecimal and decimal (in parentheses) numbers.
If Modbus 1 is selected in the communication protocol selection of the engineering mode, the address of high-order words and that of low-order words are reversed.
(4) Description: A short description of the communication data item is written.
(5) Attribute: A method of how communication data items are read or written when viewed from the host computer is described.
RO: Only reading data is possible.
Data direction
Host computer The controller
R/W: Reading and writing data is possible.
Data direction
Host computer The controller
(6) Digits: The data number of digits in RKC communication is written.
(7) Data range: The reading range or the writing range of communication data is written.
(8) Factory set value: The factory set value of communication data is written.
(9) Related parameters: A name and a page of related parameters are written.
There is item including the functional description.
100
advertisement
Related manuals
advertisement
Table of contents
- 11 3.1 Connect the Communication
- 16 4.1 Transfer to Setup Setting Mode
- 17 4.2 Setting the Communication Parameters
- 21 4.3 Communication Requirements
- 23 5.1 Polling
- 24 5.1.1 Polling procedures
- 28 5.1.2 Polling procedure example
- 29 5.2 Selecting
- 29 5.2.1 Selecting procedures
- 33 5.2.2 Selecting procedure example
- 34 5.3 Examples of Polling and Selecting Check Programs
- 34 5.3.1 Example of temperature set values polling check program
- 36 5.3.2 Example of temperature set values selecting checking program
- 38 5.4 Communication Items List
- 61 6.1 Message Format
- 62 6.2 Function Code
- 62 6.3 Communication Mode
- 63 6.4 Slave Responses
- 64 6.5 Calculating CRC-16
- 67 6.6 Message Format
- 67 6.6.1 Read holding registers [03H]
- 68 6.6.2 Preset single register [06H]
- 69 6.6.3 Diagnostics (Loopback test) [08H]
- 70 6.6.4 Preset multiple registers [10H]
- 71 6.7 Data Configuration
- 71 6.7.1 Data scale
- 75 6.7.2 Caution for handling communication data
- 76 6.8 Data Map List
- 107 Model codes
- 107 Measured value (PV) monitor
- 107 Set value (SV) monitor
- 108 Remote input value monitor
- 108 Burnout state
- 109 Event state
- 109 Manipulated output value (MV) monitor
- 110 Error code
- 111 Event input (DI) state
- 112 Operation mode state
- 113 Memory area soak time monitor
- 113 PID/AT transfer
- 115 Auto/Manual transfer
- 115 Remote/Local transfer
- 116 RUN/STOP transfer
- 116 Memory area selection
- 117 Event set value
- 118 Control loop break alarm (LBA) time
- 118 LBA deadband
- 121 Set value (SV)
- 121 Proportional band
- 122 Integral time
- 122 Derivative time
- 123 Control response parameter
- 124 Setting change rate limiter (up)
- 124 Setting change rate limiter (down)
- 126 Area soak time
- 127 Link area number
- 128 PV bias
- 128 PV digital filter
- 129 PV ratio
- 130 PV low input cut-off
- 131 Proportional cycle time
- 131 Manual output value
- 132 Set lock level
- 133 EEPROM storage state
- 133 EEPROM storage mode
- 134 PV peak hold value monitor
- 135 PV bottom hold value monitor
- 136 PV hold reset
- 137 Interlock release
- 137 Auto-zero
- 138 Auto calibration
- 139 STOP display selection
- 140 Bar graph display selection
- 141 Bar graph resolution setting
- 141 Auto/Manual transfer key operation selection (A/M)
- 142 Remote/Local transfer key operation selection (R/L)
- 142 RUN/STOP transfer key operation selection (R/S)
- 143 Input type selection
- 144 Display unit selection
- 145 Decimal point position
- 146 Input scale high
- 147 Input scale low
- 148 Input error determination point (high)
- 149 Input error determination point (low)
- 150 Burnout direction
- 151 Square root extraction selection
- 151 Power supply frequency selection
- 152 Event input logic selection
- 155 Output logic selection
- 157 Output timer setting
- 159 Transmission output_type selection
- 160 Transmission output_scale high
- 161 Transmission output_scale low
- 162 Event type selection
- 165 Event hold action
- 167 Event differential gap
- 169 Event action at input error
- 171 Event assignment
- 172 Hot/Cold start selection
- 173 Input 2_use selection
- 173 SV tracking
- 174 Control action type selection
- 175 Integral/Derivative time decimal point position selection
- 175 Derivative gain
- 176 ON/OFF action differential gap (upper)
- 177 ON/OFF action differential gap (lower)
- 178 Action at input error (high)
- 179 Action at input error (low)
- 179 Manipulated output value at input error
- 180 Output change rate limiter (up)
- 180 Output change rate limiter (down)
- 182 Output limiter (high)
- 182 Output limiter (low)
- 183 AT bias
- 184 AT cycle
- 185 AT differential gap time
- 187 Setting change rate limiter unit time
- 187 Soak time unit selection
- 188 Setting limiter (high)
- 189 Setting limiter (low)
- 190 ROM version display
- 190 Integrated operating time display
- 190 Holding peak value ambient temperature display
- 191 Alarm lamp lighting condition setting
- 192 PV hold function
- 192 Gain setting
- 193 Linearize type selection
- 194 Shunt resistance output value
- 194 PV transfer function
- 195 MV scaling high
- 196 MV scaling low
- 196 Decimal point position of MV scaling
- 197 AT action
- 197 Manipulated output value when transferred to Auto from Manual
- 198 Interlock function
- 200 MV transfer function
- 201 Items relating to the memory area other than the control area:
- 201 Memory area selection
- 201 Event set value
- 202 Control loop break alarm (LBA) time
- 203 LBA deadband
- 203 Set value (SV)
- 204 Proportional band
- 204 Integral time
- 205 Derivative time
- 205 Control response parameter
- 206 Setting change rate limiter (up)
- 206 Setting change rate limiter (down)
- 207 Area soak time
- 207 Link area number