General information. Danfoss gas detection units - Types GD Basic and Basic+

Add to my manuals
10 Pages

advertisement

General information. Danfoss gas detection units - Types GD Basic and Basic+ | Manualzz

Data sheet | Danfoss gas detection units, types GD Basic and Basic+

General information • Cable gland not mounted but enclosed

• 4 mounting ears included

• Sensor head mounted bottom right

• Alarm device (Buzzer & Light) mounted bottom left (only Basic +)

Basic Basic +

Gas types and thresholds

Sensor

Ammonia EC 100

Ammonia EC 300

Sensor Type

Electrochemical

Electrochemical ppm range

0-100

0-300

Ammonia EC 1000

Ammonia SC 1000

HFC R404A, R507 SC2000

Electrochemical

Semiconductor

Semiconductor

0-1000

0-1000

0-2000

Hysteresis = 5% of Alarm1 (rounded up to the next higher integer)

Alarm 1

25 ppm

25 ppm

500 ppm

500 ppm

500 ppm

Alarm 2

35 ppm

150 ppm

900 ppm

900 ppm

900 ppm

Hysteresis

2 ppm

2 ppm

25 ppm

25 ppm

25 ppm

© Danfoss | DCS (MWA) | 2018.09

AI272545693488en-000102 | DKRCI.PD.S00.C2.02 | 7

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Frequently Answers and Questions

What is the purpose of the GD Basic and Basic+ gas detection units?
The GD Basic and Basic+ units are used for monitoring and warning of hazardous gas concentrations. They can be used for detecting commonly used refrigerants, and are intended to be connected to a central system like Gas Detection Controller Unit, or a PLC.
What types of sensors can be connected to the gas detection units?
Depending on the application, the units can be equipped with either an electrochemical or a semiconductor sensor.
How many alarm ranges can be configured on the gas detection units?
Each unit can be configured with two individual alarm ranges: Alarm 1 is a pre-alarm indicating the gas level has passed a predefined threshold 1, and Alarm 2 is the final alarm if the gas level passes a predefined threshold 2.
How are the gas detection units powered?
The units are powered by a 19 - 29 V AC/DC power supply, with reverse-polarity protection.
What is the maximum power consumption of the gas detection units?
The maximum power consumption is 250 mA (6 VA) at 24 V DC.
What types of communication interfaces do the units have?
The units have the following communication interfaces: Analog output (4-20 mA or 2-10V), RS485 open Modbus communication, Local bus for sensor, and Tool bus (2-wire / 19200 baud).
What is the maximum cable length for the local bus connecting the sensor board?
The maximum cable length for the local bus connecting the sensor board is 5 meters (16.4 ft.).
How are the gas detection units calibrated?
The units can be calibrated either by replacing the sensor heads or by calibration with gas using the Danfoss calibration adapter and calibration gas with the correct concentration.