15.4. Error Codes Table
Diagnosis display
Abnormality / Protection control
Abnormality
Judgement
Emergency operation
Primary location to verify
H00
H11
H12
H14
H15
H16
H19
H23
H25
No abnormality detected
Indoor / outdoor abnormal communication
Connection capability rank abnormal
Indoor intake air temperature sensor abnormality
Outdoor compressor temperature sensor abnormality
Outdoor Current Transformer open circuit
Indoor fan motor merchanism lock
Indoor heat exchanger temperature sensor abnormality
E-Ion breakdown
— Normal operation
> 1 min after starting operation
Indoor fan operation only
—
Continue for 5 sec.
—
—
Continue for 5 sec.
—
—
Continue for 5 sec.
—
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
—
—
—
O
(Cooling only)
—
O
O
—
—
• Internal / external cable connections
• Indoor / Outdoor PCB
—
• Intake air temperature sensor
(defective or disconnected)
• Compressor temperature sensor
(defective or disconnected)
• Outdoor PCB
• IPM (Power transistor) module
• Indoor PCB
• Fan motor
• Heat exchanger temperature sensor
(defective or disconnected)
• Indoor PCB
• E-Ion PCB
• Outdoor temperature sensor (defective or disconnected)
• Outdoor heat exchanger temperature sensor (defective or disconnected)
• Discharge temperature sensor
H27
H28
H30
H33
H38
H58
H97
H98
H99
F11
F90
F91
F93
F95
F96
F97
F98
F99
Outdoor air temperature sensor abnormality
Outdoor heat exchanger temperature sensor abnormality
Discharge temperature sensor abnormality
Indoor/Outdoor wrong connection
Indoor/Outdoor mismatch (brand code)
Abnormal gas sensor
Outdoor Fan Motor lock abnormality
Indoor high pressure protection
Outdoor compressor overheating protection
Total running current protection
Outdoor Direct Current (DC) peak detection
—
—
Continue for 6 hours
—
—
Indoor heat exchanger anti-freezing protection
Cooling / Heating cycle changeover abnormality
PFC control
—
Refrigeration cycle abnormality 7 times occurance continuously
Outdoor compressor abnormal revolution 4 times occurance within 20 minutes
Cool high pressure protection
4 times occurance within 30 minutes
4 times occurance within 10 minutes
IPM (power transistor) overheating protection
4 times occurance within 20 minutes
—
4 times occurance within 20 minutes
3 times occurance within 20 minutes
7 times occurance continuously
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
• Indoor/Outdoor supply voltage
—
• Gas sensor
(defective or disconnected)
• Outdoor PCB
• Outdoor Fan Motor
• Air filter dirty
• Air circulation short circuit
• Insufficient refrigerant
• Air filter dirty
• 4-way valve
• V-coil
• Voltage at PFC
• No refrigerant
(3-way valve is closed)
• Outdoor compressor
• Outdoor refrigerant circuit
• Excess refrigerant
• Improper heat radiation
• IPM (Power transistor)
• Insufficient refrigerant
• Compressor
• Excess refrigerant
• Improper heat radiation
• Outdoor PCB
• IPM (Power transistor)
• Compressor
Note:
“O” - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the “CHECK” button at Remote Control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is changed from one “beep” to four “beep” sounds.
45
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Order No. MAC
- 4 2.1. CS-E18GKEW CU-E18GKE
- 6 2.2. CS-E21GKES CU-E21GKE
- 9 4.1. Indoor Unit
- 9 4.2. Outdoor Unit
- 9 4.3. Remote Control
- 10 5.1. Indoor Unit & Remote Control
- 11 5.2. Outdoor Unit
- 15 9.1. Indoor Unit
- 16 9.2. Outdoor Unit
- 17 10.1. Indoor Unit
- 18 10.2. Indicator
- 19 10.3. Outdoor Unit
- 20 11.1. Select The Best Location
- 20 11.2. Indoor/Outdoor Unit Installation Diagram
- 21 11.3. Indoor Unit
- 24 11.4. Outdoor Unit
- 27 12.1. Basic Function
- 27 12.2. Airflow Direction
- 28 of Soft Dry Mode)
- 30 12.4. Powerful Mode Operation
- 30 12.5. ON Timer Control
- 31 12.6. OFF Timer Control
- 31 12.7. Auto Restart Control
- 31 12.8. Indication Panel
- 31 12.9. Patrol Operation
- 33 12.10. e-ion Operation
- 36 13.1. Protection Control For All Operations
- 37 Operation
- 38 13.3. Protection Control For Heating Operation
- 40 14.1. Auto OFF/ON Button
- 40 14.2. Select Remote Control Transmission Code
- 41 14.3. Remote Control Button
- 42 15.1. Refrigeration Cycle System
- 43 Current
- 44 15.3. Breakdown Self Diagnosis Function
- 45 15.4. Error Codes Table
- 46 And Indoor Fan Motor Removal Procedures
- 50 Procedure
- 51 17.1. Operation Characteristics
- 59 17.2. Sensible Capacity Chart
- 60 18.1. CS-E18GKEW CS-E21GKES
- 62 18.2. CU-E18GKE CU-E21GKE