Blower Off Delay (Heat Mode). Bryant 345MAV, Series F

Add to My manuals
44 Pages

advertisement

Blower Off Delay (Heat Mode). Bryant 345MAV, Series F | Manualzz

TABLE 11—GAS RATE (CU FT/HR)

SECONDS

FOR 1

REVOLUTION

10

11

12

13

14

15

30

31

32

33

34

35

26

27

28

29

20

21

22

23

24

25

16

17

18

19

40

41

42

43

44

45

36

37

38

39

46

47

48

49

100

97

95

92

90

88

86

84

82

80

78

76

75

73

SIZE OF TEST DIAL SECONDS

1 2 5 FOR 1 cu ft

360 cu ft

720 cu ft

1800

REVOLUTION

50

327

300

277

257

240

655

600

555

514

480

1636

1500

1385

1286

1200

51

52

53

54

55

277

267

257

248

240

232

225

218

212

206

450

424

400

379

360

343

327

313

300

288

138

133

129

124

120

116

113

109

106

103

225

212

200

189

180

171

164

157

150

144

1125

1059

1000

947

900

857

818

783

750

720

692

667

643

621

600

581

563

545

529

514

80

82

84

86

88

90

72

74

76

78

60

62

64

66

68

70

56

57

58

59

200

195

189

185

180

176

172

167

164

160

157

153

150

147

500

486

474

462

450

439

429

419

409

400

391

383

375

367

92

94

96

98

100

102

104

106

108

110

112

116

120

124

36

35

35

34

33

33

39

38

38

37

32

31

30

29

45

44

43

42

41

40

50

48

47

46

60

58

56

54

53

51

64

63

62

61

SIZE OF TEST DIAL

1 2 5 cu ft

72 cu ft

144 cu ft

360

71

69

68

67

65

141

138

136

133

131

355

346

340

333

327

100

97

95

92

90

88

86

84

82

80

129

126

124

122

120

116

112

109

106

103

250

243

237

231

225

220

214

209

205

200

321

316

310

305

300

290

281

273

265

257

72

71

69

68

67

65

78

76

75

74

64

62

60

58

196

192

188

184

180

178

173

170

167

164

161

155

150

145

WARNING: Disconnect 115-v electrical power before changing speed tap. Failure to follow this warning could result in personal injury.

TABLE 13—BLOWER OFF DELAY SETUP POSITION

PINS

Time (in sec)

1 AND 2 2 AND 3 3 AND 4 4 AND 5

90 120 150 180

D.

Set Thermostat Heat Anticipator

When using a nonelectronic thermostat, the thermostat heat anticipator must be set to match amp draw of the electrical components in R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R and W. Fig. 49 illustrates an easy method of obtaining actual amp draw. The amp reading should be taken after blower motor has started and furnace is heating. Connect ammeter wires as shown in Fig. 49. The thermostat anticipator should NOT be in the circuit while measuring current. If thermostat has no subbase, the thermostat must be disconnected from R and W wires during current measurement.

See thermostat manufacturer’s instructions for adjusting heat anticipator and for varying heating cycle length.

For an electronic thermostat, set cycle rate for 3 cycles per hour.

VI.

CHECK SAFETY CONTROLS

This section covers the safety controls that must be checked before the installation is complete. The flame sensor, gas valve, and pressure switch were all checked in the Start-up prodecure section as part of normal operation.

A.

Check Primary Limit Control

This control shuts off combustion control system and energizes air-circulating blower motor if furnace overheats. Recommended method of checking this limit control is to gradually block off return air after furnace has been operating for a period of at least

5 minutes. As soon as limit control has shut off burners, return-air opening should be unblocked to permit normal air circulation. By using this method to check limit control, it can be established that limit is functioning properly and operates if there is a restricted return-air supply or motor failure. If limit control does not function during this test, cause must be determined and corrected.

B.

Check Pressure Switch

This control proves operation of draft inducer. Check switch operation as follows:

1. Turn off 115-v power to furnace.

2. Remove main furnace door and disconnect inducer motor lead wires from wire harness.

THERMOSTAT SUBBASE

TERMINALS WITH

THERMOSTAT REMOVED

HOOK-AROUND

VOLT/AMMETER

4. To change blower motor speed selections for heating mode, remove blower motor lead from control center HEAT terminal. (See Fig. 33.) Select desired blower motor speed lead from 1 of the other motor leads and relocate it to HEAT terminal. See Table 12 for lead color identification. Reconnect original lead on SPARE terminal.

Follow this same procedure for proper selection of COOL speed selection.

TABLE 12–SPEED SELECTOR

COLOR

Black

Yellow (When Present)

Blue

Red

White

SPEED

High

Medium High

Medium Low

Low

Common

FACTORY-

SHIPPED

CONNECTION

Cool

Spare

Heat

Fan

Com

R Y W G

10 TURNS

C.

Blower Off Delay (Heat Mode)

The blower off delay has 4 adjustable settings from 90 sec to 180 sec. (See Table 13.) The blower off delay jumpers are located on the furnace control board (See Fig. 33.) To change the blower off delay setting, move the jumper from one set of pins on the control board to the pins used for the desired blower off delay. Factory blower off delay setting is 120 sec.

—41—

FROM UNIT 24-VOLT

TERMINAL BLOCK

EXAMPLE:

5.0 AMPS ON AMMETER

10 TURNS AROUND JAWS

= 0.5 AMPS FOR THERMOSTAT SETTING

A80201

Fig. 49—Amp Draw Check with Ammeter

3. Turn on 115-v power to furnace.

4. Set thermostat to "call for heat" and wait 1 minute. When pressure switch is functioning properly, hot surface igniter should NOT glow, and status code LED flashes a 31 fault.

If hot surface igniter glows when inducer motor is disconnected, shut furnace down immediately. Determine reason pressure switch did not function properly and correct condition.

5. Turn off 115-v power to furnace.

6. Reconnect inducer motor leads, reinstall main furnace door, and turn on 115-v power supply.

CHECKLIST

1. Put away tools and instruments. Clean up debris.

2. Verify manual flame rollout reset switch has continuity.

3. Verify that blower and main access doors are properly installed.

4. Cycle test furnace with room thermostat.

5. Check operation of accessories per manufacturer’s instructions.

6. Review User’s Guide with owner.

7. Leave literature packet near furnace.

—42—

CHECKLIST—INSTALLATION

LOAD CALCULATION

____________ Heating Load (Btuh)

____________ Cooling Load (Btuh)

____________ Furnace Model Selection

VENT PIPING

Termination Location

________

________

________

________

________

________

________

Roof or Sidewall

Vent Pipe Length

Vent Pipe Elbow Quantity

Pipe Diameter Determined from Sizing Table

Pipe Sloped To Furnace

Pipe Insulation

Over Ceilings

Low-Ambient Exposed Pipes

________

________

________

________

________

Condensate Drain

Unit Level or Pitched Forward

Internal Tubing Connections Free of Kinks and Traps

External Drain Connection Leak Tight and

Sloped

Condensate Trap Primed before Start-Up

Heat Tape Installed if Required

________

________

CHECKLIST—START-UP

Gas Input Rate (Set Within 2 percent of

Rating Plate)

Temperature Rise Adjusted

________

________

Thermostat Anticipator

Anticipator Setting Adjusted or

Cycle Rate (3 Cycles per Hr) Selected

Safety Controls Check Operation

________

________

Primary Limit

Pressure Switch

—43—

© 2003 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —44— Printed in U.S.A.

345m408 Catalog No. 5334-520

advertisement

Related manuals

advertisement