Defrost levels cont'd
Defrost level
4
Level of humidity
High
5 Extremely high
Relative humidity indoors 1
61% - 80%
>80%
Description
Apartments or houses with high humidity
Buildings with very high humidity level.
Approximate values of relative humidity in the extract air at cold outdoor temperatures.
In newly constructed houses it might be necessary with a higher defrost level during the first winter period.
5.6.1
Setting the defrost level
1. Go to the service menu by using the SELECTION knob.
Service
2. Enter the service level by typing the password, default
1111. Use the SELECTION knob for each digit and confirm with the ENTER button after each set digit and choose
"
NO
" for the system not be locked.
3. Go to: Functions
Choose: Defrosting
Password
Password XXXX
Locked YES/NO
Functions
4. Set the mode
Defrosting
Defrosting
Mode 0–5
Allow unbalance YES/NO
Note:
This setting is only valid for units equipped with counter flow heat exchangers.
5. Select if unbalanced airflows are allowed in the building during the defrost cycle. Choose between YES and NO. Default is YES.
5.7
Programming the Week schedule
Set the week schedule according to below procedure:
1. Go to the service menu by using the SELECTION knob.
Service
2. Enter the service level by typing the password, default
1111. Use the SELECTION knob for each digit and confirm with the ENTER button after each set digit and choose
" NO " for the system not be locked.
3. Go to:
Week program
Password
Password XXXX
Locked YES/NO
4. Choose Week program again.
Service
Week program
Week program
5. Set week day and time you want the unit to be in ON level. Two periods per day can be programmed. The rest of the time the unit will be in OFF level.
Airflow
Week program
Day: MON
Per 1: 07:00 16:00
Per 2: 00:00 00:00
212962 | v02
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 Overview
- 5 General Description
- 5 Warranty
- 5 Type label
- 5 Important Safety Information
- 5 Intended Use
- 6 Admonitions
- 7 Declaration of Conformity
- 8 Technical Data
- 8 Electrical data
- 8 Dimensions and Weight
- 9 Duct connections
- 10 Delivery, Transport, Storage
- 10 Transport and storage
- 10 Delivery/Unloading
- 10 Installation
- 10 Unpacking
- 13 bracket
- 14 installation
- 15 hood wiring
- 17 bracket
- 18 installation
- 20 hood wiring
- 22 panel
- 22 panel directly on the unit
- 23 cabinets
- 25 panel as a door
- 25 Commissioning
- 25 Control panel
- 26 Display symbols
- 26 Start up wizard
- 27 Procedure
- 27 Perform Factory reset
- 28 System curves
- 28 Coarse 50% type filter
- 29 Airflow settings
- 29 Setting the airflow
- 30 Moisture transfer control
- 30 Defrost level settings
- 31 Setting the defrost level
- 31 Programming the Week schedule
- 32 Ext/Force run
- 32 Extra functions
- 33 Electrical connections
- 33 Print card layout
- 35 Before Starting the System
- 36 Operation
- 36 Setting the temperature
- 36 Manual setting of airflow
- 37 Cool recovery
- 37 Service menu overview
- 46 Service
- 46 Warnings
- 47 Internal components
- 47 Component descriptions
- 48 Filters
- 48 Heat exchanger
- 48 Print card
- 48 Temperature sensors
- 48 Humidity sensor
- 48 Trouble shooting
- 50 Alarm list
- 51 Replacing rotor drive belt