advertisement
The Off Time specifies in ms the amount of time the digital point is to be turned off. The minimal value of the Off Time is
500 ms and the actual value may differ from the specified value by up to 50 ms.
The Status byte in the response will reflect the success or failure of the control operation:
- Request Accepted (0) will be return if the command was accepted;
- Request not Accepted due to Formatting Errors (3) will be returned if the Control Code byte was incorrectly formatted or an invalid Code was present in the command;
- Control Operation not Supported for this Point (4) will be returned if the Control Point was out of control.
To manually operate Relay #1, use the Direct-Operate (or SBO/Operate or Direct-Operate-No-Acknowledge) command to point 80 of the Control-Relay-Output-Block object with the Control Code value Latch On. To manually release Relay #1, use the Direct-Operate (or SBO/Operate or Direct-Operate-No-Acknowledge) command to point
80 of the Control-Relay-Output-Block object with the Control Code value Latch Off. To control Relay #2, use point
81. To revert Relay #1 or #2 to normal operation, use the Direct-Operate (or SBO/Operate or Direct-Operate-No-
Acknowledge) command to the correspondent point of the Control-Relay-Output-Block object with the Control
Code value Null Operation and Clear sub-field set to 1.
Pulse Counter Setup
Table 3-27 Pulse Counter Register
Counter Setup registers (see Table 3-28)
Counter #1 832-833
Counter #2 834-835
Counter #3 836-837
Counter #4 838-839
Table 3-28 Pulse Counter Setup Registers
Object : Var
40:2(read)
41:2(write)
Register contents
Associated digital input ID
40:2(read)
41:2(write)
Scale factor (number of units per input pulse)
… …
Associated digital input ID 40:2(read)
41:2(write)
40:2(read)
41:2(write)
Scale factor (number of units per input pulse)
Table 3-29 Pulsing Output Parameters
Input
Not allocated
Digital input #1
Digital input #2
0
1
2
ID
Object : Point
AO:832
Range
See Table 3-29
AO:833 1-9999
… …
AO:838 See Table 3-29
AO:839 1-9999
25
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 4 GENERAL
- 5 DNP PROTOCOL
- 5 Introduction
- 5 PM172EH Deviation from Standard
- 5 DNP Implementation
- 6 Scaling Analog Input Objects
- 8 PM172EH REGISTERS
- 8 Basic Data Registers
- 9 Basic Setup Registers
- 10 User Selectable Options Setup
- 11 Communications Setup
- 11 DNP Options Setup
- 13 DNP Event Setpoints Setup
- 14 Freeze Requests on Binary Counter Objects
- 15 Resetting Energy, Demands, Counters and Min/Max log
- 15 Status Registers
- 16 Alarm Status Registers
- 17 Extended Data Registers
- 21 Analog Output Setup
- 23 Analog Expander Channels Allocation Registers
- 23 Digital Inputs Allocation Registers
- 24 Pulsing Setpoints Registers
- 24 Relay Operation Control
- 25 Pulse Counter Setup
- 26 Class 0 Point Assignment
- 27 APPENDIX A DNP APPLICATION MESSAGES
- 29 APPENDIX B DNP DEVICE PROFILE