Control Head Type 8681
ASInterface-Design
11.8. Programming data
The control heads have been configured as AS interface version with an extended address range (A/B slaves) for
62 slaves or optionally as an AS interface version for 31 slaves.
A change between the two configurations in the control head is only possibly by exchanging the electronic PCB!
If one control head is replaced with another control head having a different configuration in the AS interface field bus system (e.g. AS interface version 62 slaves (A/B-Slave) to replace a device with AS interface version
31 slaves), a configuration error will be generated at the master due to the different ID codes!
In this case (intentional replacement!), the current configuration must be re-programmed in the AS interface master. Please read the operating instructions of the used AS interface master!
AS-i address factory setting:
AS-i address = 0
Programming data table:
I/O configuration
ID code
Extended ID code 1
Extended ID code 2
Profile
Programming data for 62 slaves
AS interface - Device for A/B slave addressing (default device)
7 hex (4 inputs / 4 outputs) see below: Bit configuration table
A hex
7 hex
E hex
S-7. A.E
Programming data for 31 slaves
AS interface (optional)
7 hex (4 inputs / 4 outputs) see below: Bit configuration table
F hex
(F hex)
(F hex)
S-7. F.F
Bit configuration table:
Data bit D3 D2 D1 D0
Input
Output
Parameter bit
Output
External initiator S4 Position 3
Not used
P3
Not used
Solenoid valve 3
P2
Not used
Position 2
Solenoid valve 2
P1
Not used
Position 1
Solenoid valve 1
P0
Not used
51