2 Wiring. YASKAWA CIMR-F7A
Reklāma
Reklāma
Wiring
This chapter describes wiring terminals, main circuit terminal connections, main circuit terminal wiring specifications, control circuit terminals, and control circuit wiring specifications.
Connections to Peripheral Devices..............................2-2
Connection Diagram ....................................................2-3
Terminal Block Configuration .......................................2-5
Wiring Main Circuit Terminals ......................................2-6
Wiring Control Circuit Terminals ................................2-23
Wiring Check .............................................................2-31
Installing and Wiring Option Boards ..........................2-32
2
-2
Connections to Peripheral Devices
Examples of connections between the Inverter and typical peripheral devices are shown in Fig 2.1
.
Power supply
Molded-case circuit breaker or ground fault interrupter
Magnetic contactor (MC)
AC reactor for power factor improvement
Zero phase reactor
Input noise filter
Braking resistor
Inverter
Varispeed F7 DC reactor for power factor improvement
Ground
Output noise filter
Zero phase reactor
Motor
Ground
Fig 2.1 Example Connections to Peripheral Devices
Connection Diagram
Connection Diagram
The connection diagram of the Inverter is shown in Fig 2.2
.
When using the Digital Operator, the motor can be operated by wiring only the main circuits.
2MCCB
3-phase power
200 to 240 V
50/60 Hz
R
S
T
1MCCB
MC
Forward Run/Stop
2MCCB THRX OFF
ON
Thermal relay trip contact for Braking Resistor Unit
MC
1 2
Thermal relay trip contact for motor cooling fan
1 2
MC
MC
SA
THRX
SA
TRX
SA
TRX
MC C MA
Fault contact
Multi-function contact inputs
Factory settings
Reverse Run/Stop
Thermal switch contact for Braking Unit
External fault 3 4
Fault reset
Multi-step speed reference 1
Multi-step speed reference 2
Jog frequency selection
External baseblock command
FU
FV
FW
External frequency references
+ 1
S1
S2
R/L1
S/L2
T/L3
S3
S4
S5
S6
S7
S8
Braking Unit
(optional)
+ 3
Thermal switch contact
Thermal relay trip contact
+
3
Level detector
-
-
4
+
0
-
0
P
1 2
B
Braking Resistor Unit
(optional)
FU
FV
FW
Inverter
CIMR-F7A2022
U/T1
V/T2
W/T3
U
V
W
Motor
Cooling fan
IM
IM
CN5 (NPN setting)
SC
+24V 8mA
Pulse train input
2 k
Ω
Frequency setting adjustment
Frequency setter
3
2 k
Ω
1
2
0 to 10 V
4 to 20 mA P
0 to 10 V
MEMOBUS communications
RS-485/422
P
((
P
R+
R-
S+
S-
IG
E (G)
RP
+24V
Shield wire connection terminal
Master speed pulse train
0 to 32 kHz (3 k Ω )
High level: 3.5 to 13.2 V input
+V
A1
A2
A3
AC
Frequency setting power
+15 V, 20 mA
Master speed reference
0 to 10 V (20 k
Ω
)
Master speed reference
4 to 20 mA (250
Ω
)
[0 to 10 V (20 k
Ω
) input]
0V
Multi-function anlog input
0 to 10 V (20 k
Ω
)
Factory setting:
Not used
-V (15V 20mA)
Terminating resistance
(Ground to 100 max.)
PG-B2
(optional)
TA1
3
4
5
1
2
6
TA3
TA2
2
3
4
Shieded twisted-pair wires
Pulse monitor output
Pulse A
30 mA max.
D
Pulse B
30 m max.
C
H
B
G
A
F
PG
MP
AC
Pulse train output
0 to 32 kHz (2.2 k
Ω
)
Default: Output frequency
AM
FM
AC
AM
Ammeter adjustment
20 k
Ω
Multi-function analog output 2
-10 to 10 V 2 mA
Default: Output current
0 to +10 V
FM
Ammeter adjustment
20 k Ω
Multi-function analog output 1
-10 to 10 V 2 mA
Default: Output frequency
0 to +10 V
E(G)
MA
MB
MC
M1
M2
P1
P2
PC
MA A
Error contact output
250 VAC, 10 mA min.
1 A max.
30 VDC, 10 mA min.
1 A max.
Min. load
5 VDC, 10 mA
Multi-function contact oputput
250 VAC, 10 mA min. 1 A max.
30 VDC, 10 mA min. 1 A max.
Default: Running signal
Min. load
5 VDC, 10 mA
Open collector 1
Default: Zerospeed
Open collector 2
Default: Frequency agree signal
Multi-function open-collector outputs
48 VDC 50 mA max.
Fig 2.2 Connection Diagram (Model CIMR-F7A2022 Shown Above)
2-
3
2
-4
IMPORTANT
1. Control circuit terminals are arranged as shown below.
Inverters with SPEC: C or earlier
Inverters with SPEC: E or later
2. The output current capacity of the +V and − V terminals are 20 mA. Do not short-circuit between the +V, − V, and AC terminals. Doing so may result in a malfunction or a breakdown of the Inverter.
3. Disable the stall prevention during deceleration (set constant L3-04 to 0) when using a Braking Resistor
Unit. If this user constant is not changed to disable stall prevention, the system may not stop during deceleration.
4. Main circuit terminals are indicated with double circles and control circuit terminals are indicated with single circles.
5. The wiring for a motor with a cooling fan is not required for self-cooling motors.
6. PG circuit wiring (i.e., wiring to the PG-B2 Board) is not required for control without a PG.
7. Sequence input signals S1 to S8 are labeled for sequence connections (0 V common and sinking mode) for no-voltage contacts or NPN transistors. These are the default settings.
For PNP transistor sequence connections (+24V common and sourcing mode) or to provide a 24-V external power supply, refer to Table 2.13
.
8. The master speed frequency reference can set to input either a voltage (terminal A1) or current (terminal
A2) by changing the setting of parameter H3-13. The default setting is for a voltage reference input.
9. The multi-function analog output is a dedicated meter output for an analog frequency meter, ammeter, voltmeter, wattmeter, etc. Do not use this output for feedback control or for any other control purpose.
10.DC reactors to improve the input power factor are built into 200 V Class Inverters for 22 to 110 kW and 400
V Class Inverters for 22 to 300 kW. A DC reactor is thus an option only for Inverters for 18.5 kW or less.
11.Set parameter L8-01 to 1 when using a breaking resistor (ERF). When using a Braking Resistor Unit, a shutoff sequence for the power supply must be made using a thermal relay trip.
12.The permissible load of a multi-function contact output and an error contact output is 10 mA. Use a multifunction open-collector output for a load less than 10 mA.
13.Do not ground nor connect the AC terminal on the control circuit to the unit. Doing so may result in a malfunction or a breakdown of the Inverter.
14.If turning off the power only for the main circuit but leaving the power ON for the control circuit, use a separate power supply for the control circuit and a specially designed Inverter, which are sold as options.
15.
indicates shield wire and
P
indicates twisted-pair shield wire.
Terminal Block Configuration
Terminal Block Configuration
The terminal arrangement for 200 V Class Inverters are shown in Fig 2.3
and Fig 2.4
.
E (G) FM AC AM
SC A1 A2 A3
S1 S2 S3 S4
P1 P2 PC
+V AC -V
S5 S6 S7
SC
S8
MP
RP R+ R- S+ S-
IG
MA
M1
MB MC
M2 E (G)
Control circuit terminals
Main circuit terminals
Charge indicator
Ground terminal
Fig 2.3 Terminal Arrangement (200 V Class Inverter with SPEC: E or later for 0.4 kW Shown Above)
Control circuit terminals
Charge indicator
Main circuit terminals
Ground terminal
Fig 2.4 Terminal Arrangement (200 V Class Inverter with SPEC: E or later for 22 kW Shown Above)
2-
5
2
-6
Wiring Main Circuit Terminals
Applicable Wire Sizes and Closed-loop Connectors
Select the appropriate wires and crimp terminals from Table 2.1
to Table 2.3
. Refer to instruction manual
TOBPC72060000 for wire sizes for Braking Resistor Units and Braking Units.
Inverter
Model
CIMR
F7A20P4
Table 2.1 200 V Class Wire Sizes
Terminal Symbol
U/T1, V/T2, W/T3
Terminal
Screws
M4
Tightening
Torque
(N•m)
1.2 to 1.5
Possible
Wire Sizes mm
2
(AWG)
2 to 5.5
(14 to 10)
Recommended
Wire Size
2 mm
(AWG)
2
(14)
Wire Type
F7A20P7 U/T1, V/T2, W/T3 M4 1.2 to 1.5
2 to 5.5
(14 to 10)
2
(14)
F7A21P5 U/T1, V/T2, W/T3
F7A22P2 U/T1, V/T2, W/T3
F7A23P7 U/T1, V/T2, W/T3
F7A25P5 U/T1, V/T2, W/T3
F7A27P5 U/T1, V/T2, W/T3
M4
M4
M4
M4
M5
F7A2011 U/T1, V/T2, W/T3 M5
F7A2015
F7A2018
F7A2022
F7A2030
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/T2,
W/T3
B1, B2
M6
M5
M6
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/T2,
W/T3
B1, B2
M8
M5
M6
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
3
M8
M6
M8
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
3
M8
M6
M8
1.2 to 1.5
1.2 to 1.5
1.2 to 1.5
1.2 to 1.5
2.5
2.5
4.0 to 5.0
2.5
4.0 to 5.0
9.0 to 10.0
2.5
4.0 to 5.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
2 to 5.5
(14 to 10)
2 to 5.5
(14 to 10)
3.5 to 5.5
(12 to 10)
5.5
(10)
8 to 14
(8 to 6)
14 to 22
(6 to 4)
8 to 22
(8 to 4)
22 to 38
(4 to 2)
50 to 60
(1 to 1/0)
8 to 22
(8 to 4)
22 to 38
(4 to 2)
30 to 38
(4 to 2)
8 to 14
(8 to 6)
22
(4)
30 to 38
(3 to 2)
8 to 14
(8 to 6)
22
(4)
30 to 60
(3 to 1)
3.5
(12)
5.5
(10)
2
(14)
2
(14)
8
(8)
14
(6)
-
22
(4)
50
(1)
-
22
(4)
-
22
(4)
30
(3)
30
(4)
-
22
(4)
30
(3)
Power cables, e.g., 600 V vinyl power cables
Wiring Main Circuit Terminals
Inverter
Model
CIMR
F7A2037
F7A2045
F7A2055
F7A2075
F7A2090
F7A2110
3 r/ 1, / 2
Table 2.1 200 V Class Wire Sizes (Continued)
Terminal Symbol
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/ 1, / 2
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/ 1, / 2
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
, 1
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, R1/L11,
S1/L21, T1/L31
3 r/ 1, / 2
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/ 1, / 2
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/ 1, / 2
Terminal
Screws
M10
M8
M10
M4
M10
M8
M10
M4
M10
M10
M8
M10
M4
M12
M10
M8
M12
M4
M12
M12
M8
M12
M4
M12
M12
M8
M12
M4
Tightening
Torque
(N•m)
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
17.6 to 22.5
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
31.4 to 39.2
17.6 to 22.5
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
31.4 to 39.2
31.4 to 39.2
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
31.4 to 39.2
31.4 to 39.2
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
Possible
Wire Sizes mm
2
(AWG)
60 to 100
(2/0 to 4/0)
5.5 to 22
(10 to 4)
30 to 60
(2 to 2/0)
0.5 to 5.5
(20 to 10)
80 to 100
(3/0 to 4/0)
80 to 125
(3/0 to 250)
80 to 100
(3/0 to 4/0)
5.5 to 60
(10 to 2/0)
100 to 200
(3/0 to 400)
0.5 to 5.5
(20 to 10)
150 to 200
(250 to 400)
100 to 150
(4/0 to 300)
5.5 to 60
(10 to 2/0)
60 to 150
(2/0 to 300)
0.5 to 5.5
(20 to 10)
5.5 to 22
(10 to 4)
38 to 60
(1 to 2/0)
0.5 to 5.5
(20 to 10)
50 to 100
(1/0 to 4/0)
100
(4/0)
5.5 to 60
(10 to 2/0)
30 to 60
(3 to 4/0)
0.5 to 5.5
(20 to 10)
200 to 325
(350 to 600)
150 to 325
(300 to 600)
5.5 to 60
(10 to 2/0)
150
(300)
0.5 to 5.5
(20 to 10)
Recommended
Wire Size mm
2
(AWG)
60
(2/0)
Wire Type
-
30
(2)
1.25
(16)
80
(3/0)
-
38
(1)
1.25
(16)
50 × 2P
(1/0 × 2P)
100
(4/0)
-
60 × 2P
(2/0 × 2P)
1.25
(16)
200 × 2P, or 50 × 4P
(350 × 2P, or 1/0 ×
2P)
150 × 2P, or 50 × 4P
(300 × 2P, or 1/0 ×
4P)
50
(1/0)
1.25
(16)
80 × 2P
(3/0 × 2P)
80 × 2P
(3/0 × 2P)
-
100
(3/0)
1.25
(16)
150 × 2P
(250 × 2P)
100 × 2P
(4/0 × 2P)
-
Power cables, e.g., 600 V vinyl power cables
-
150 × 2P
(300 × 2P)
1.25
(16)
* The wire thickness is set for copper wires at 75 ° C
2-
7
2
-8
Inverter
Model
CIMR
F7A40P4
Table 2.2 400 V Class Wire Sizes
Terminal Symbol
U/T1, V/T2, W/T3
Terminal
Screws
M4
Tightening
Torque
(N•m)
1.2 to 1.5
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size
2 mm
(AWG)
2 to 5.5
(14 to 10)
2
(14)
Wire Type
F7A40P7 U/T1, V/T2, W/T3
F7A41P5 U/T1, V/T2, W/T3
F7A42P2 U/T1, V/T2, W/T3
M4
M4
M4
1.2 to 1.5
1.2 to 1.5
1.2 to 1.5
2 to 5.5
(14 to 10)
2 to 5.5
(14 to 10)
2 to 5.5
(14 to 10)
F7A43P7
F7A45P5
F7A47P5
F7A4011
U/T1, V/T2, W/T3
U/T1, V/T2, W/T3
U/T1, V/T2, W/T3
U/T1, V/T2, W/T3
M4
M4
M4
M5
1.2 to 1.5
1.2 to 1.5
1.8
2.5
F7A4015
F7A4018
F7A4022
F7A4030
F7A4037
F7A4045
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/T2,
W/T3
B1, B2
M5
M5
(M6)
M6
M5
M6
R/L1, S/L2, T/L3, , 1, 3, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
M6
M8
R/L1, S/L2, T/L3, , 1, 3, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
M6
M8
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, W/
T3, R1/L11, S1/L21, T1/L31
3
M8
M6
M8
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, W/
T3, R1/L11, S1/L21, T1/L31
3
M8
M6
M8
2.5
2.5
(4.0 to 5.0)
4.0 to 5.0
2.5
4.0 to 5.0
4.0 to 5.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
2 to 5.5
(14 to 10)
3.5 to 5.5
(12 to 10)
2 to 5.5
(14 to 10)
5.5(10)
3.5 to 5.5
(12 to 10)
5.5 to 14
(10 to 6)
8 to 14
(8 to 6)
5.5 to 14
(10 to 6)
8 to 38
(8 to 2)
8
(8)
8 to 22
(8 to 4)
14 to 22
(6 to 4)
14 to 38
(6 to 2)
22
(4)
22 to 38
(4 to 2)
22 to 60
(4 to 1/0)
8 to 22
(8 to 4)
22 to 38
(4 to 2)
38 to 60
(2 to 1/0)
8 to 22
(8 to 4)
22 to 38
(4 to 2)
2
(14)
2
(14)
2
(14)
-
22
(4)
38
(2)
5.5
(10)
8
(8)
5.5
(10)
8
(8)
2
(14)
5.5
(10)
3.5
(12)
8
(8)
3.5
(12)
2
(14)
3.5
(12)
22
(4)
22
(4)
38
(2)
14
(6)
14
(6)
8
(8)
8
(8)
-
22
(4)
Power cables, e.g., 600 V vinyl power cables
Wiring Main Circuit Terminals
Inverter
Model
CIMR
F7A4055
F7A4075
F7A4090
F7A4110
F7A4132
F7A4160
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
3
3
3
3
3
Table 2.2 400 V Class Wire Sizes (Continued)
Terminal Symbol
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 r/ 1, 200/
2
200, 400/
2
400
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 r/ 1, 200/
2
200, 400/
2
400
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 r/ 1, 200/
2
200, 400/
2
400
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/ 1, 200/
2
200, 400/
2
400
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 r/ 1, 200/
2
200, 400/
2
400
Terminal
Screws
M8
M6
M8
M10
M10
M8
M10
M4
M10
M10
M8
M10
M4
M10
M10
M8
M12
M4
M10
M10
M8
M12
M4
M12
M12
M8
M12
M4
Tightening
Torque
(N•m)
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
17.6 to 22.5
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
17.6 to 22.5
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
17.6 to 22.5
17.6 to 22.5
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
17.6 to 22.5
17.6 to 22.5
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
31.4 to 39.2
31.4 to 39.2
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size mm 2
(AWG)
50
(1)
Wire Type
-
22
(4)
60
(2/0)
50
(1/0)
-
60
(2/0)
1.25
(16)
80 × 2P
(3/0 × 2P)
60 × 2P
(2/0 × 2P)
-
100
(4/0)
1.25
(16)
100 × 2P
(4/0 × 2P)
80 × 2P
(3/0 × 2P)
-
50 × 2P
(1/0 × 2P)
1.25
(16)
38
(2)
1.25
(16)
100
(4/0)
100
(4/0)
-
50
(1)
1.25
(16)
50 × 2P
(1/0 × 2P)
50 × 2P
(1/0 × 2P)
-
Power cables, e.g., 600 V vinyl power cables
50 to 60
(1 to 1/0)
0.5 to 5.5
(20 to 10)
80 to 100
(3/0 to 4/0)
60 to 100
(2/0 to 4/0)
8 to 60
(8 to 2/0)
100 to 150
(4/0 to 300)
0.5 to 5.5
(20 to 10)
100 to 200
(4/0 to 400)
80 to 200
(3/0 to 400)
8 to 60
(8 to 2/0)
50 to 150
(1/0 to 300)
0.5 to 5.5
(20 to 10)
80 to 100
(3/0 to 4/0)
8 to 22
(8 to 4)
50 to 100
(1 to 4/0)
0.5 to 5.5
(20 to 10)
50 to 100
(1/0 to 4/0)
50 to 100
(1/0 to 4/0)
8 to 60
(8 to 2/0)
60 to 150
(2/0 to 300)
8 to 22
(8 to 4)
22 to 38
(4 to 2)
60 to 100
(2/0 to 4/0)
50 to 100
(1/0 to 4/0)
5.5 to 22
(10 to 4)
38 to 60
(2 to 2/0)
0.5 to 5.5
(20 to 10)
80 to 100
(3/0 to 4/0)
2-
9
2
-10
Inverter
Model
CIMR
F7A4185
F7A4220
F7A4300
, 1
3
, 1
3
, 1
3
Terminal Symbol
R/L1, S/L2, T/L3
Table 2.2 400 V Class Wire Sizes (Continued)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 r/ 1, 200/
2
200, 400/
2
400
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 r/ 1, 200/
2
200, 400/
2
400
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3 r/ 1, 200/
2
200, 400/
2
400
Terminal
Screws
M16
M16
M16
M16
M16
M4
M16
M16
M16
M16
M16
M4
M16
M16
M16
M16
M16
M16
M4
Tightening
Torque
(N•m)
78.4 to 98
78.4 to 98
78.4 to 98
78.4 to 98
78.4 to 98
1.3 to 1.4
78.4 to 98
78.4 to 98
78.4 to 98
78.4 to 98
78.4to 98
1.3 to 1.4
78.4 to 98
78.4 to 98
78.4 to 98
78.4 to 98
78.4 to 98
78.4 to 98
1.3 to 1.4
Possible
Wire Sizes mm
2
(AWG)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
0.5 to 5.5
(20 to 10)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
0.5 to 5.5
(20 to 10)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
100 to 325
(4/0 to 600)
0.5 to 5.5
(20 to 10)
Recommended
Wire Size mm 2
(AWG)
150 × 2P
(300 × 2P)
125 × 2P
(250 × 2P)
325 × 2P
(600 × 2P)
-
125 × 2P
(250 × 2P)
1.25
(16)
100 × 2P
(3/0 × 2P)
1.25
(16)
250 × 2P
(500 × 2P)
200 × 2P
(400 × 2P)
125 × 4P
(250 × 4P)
-
125 × 2P
(250 × 2P)
1.25
(16)
125 × 4P
(250 × 4P)
125 × 2P
(250 × 2P)
125 × 4P
(4/0 × 4P)
200 × 4P
(400 × 4P)
-
Wire Type
Power cables, e.g., 600 V vinyl power cables
* The wire thickness is set for copper wires at 75 ° C.
Wiring Main Circuit Terminals
Table 2.3 Closed-loop Connector Sizes (JIS C2805) (200 V Class and 400 V Class)
Wire Thickness (mm 2 ) Terminal Screws
M3.5
0.5
Size
1.25 to 3.5
M4
M3.5
1.25 to 4
1.25 to 3.5
0.75
M4 1.25 to 4
1.25
M3.5
M4
M3.5
1.25 to 3.5
1.25 to 4
2 to 3.5
2
M4
M5
M6
2 to 4
2 to 5
2 to 6
3.5/5.5
8
14
22
30/38
50/60
M5
M6
M8
M6
M8
M6
M8
M8
M8
M10
M8
M4
M5
M6
M8
80
100
100
150
200
325
M10
M12
M12 x 2
M16
2 to 8
5.5 to 4
5.5 to 5
5.5 to 6
5.5 to 8
8 to 5
8 to 6
8 to 8
14 to 6
14 to 8
22 to 6
22 to 8
38 to 8
60 to 8
60 to 10
80 to 10
100 to 10
100 to 12
150 to 12
200 to 12
325 to 12
325 to 16
IMPORTANT
1. Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line voltage drop is calculated as follows:
Line voltage drop (V) = 3 x wire resistance (W/km) x wire length (m) x current (A) x 10 -3
2. Use a closed-loop connector (made by J.S.T. Mfg. Co., Ltd. or an equivalent) for the main circuit input and output terminals of Inverters of 200V 11 kW or more and those of 400V 22 kW or more.
2-
11
2
-12
Main Circuit Terminal Functions
Main circuit terminal functions are summarized according to terminal symbols in Table 2.4
. Wire the terminals correctly for the desired purposes.
Table 2.4 Main Circuit Terminal Functions (200 V Class and 400 V Class)
Purpose
Main circuit power input
Terminal Symbol
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
Model: CIMR-F7A □
200 V Class 400 V Class
20P4 to 2110 40P4 to 4300
2022 to 2110 4022 to 4300
Inverter outputs U/T1, V/T2, W/T3 20P4 to 2110 40P4 to 4300
20P4 to 2110 40P4 to 4300 DC power input 1,
Braking Resistor Unit connection
B1, B2
DC reactor connection 1, 2
20P4 to 2018
20P4 to 2018
40P4 to 4018
40P4 to 4018
Braking Unit connection 3, 2022 to 2110 4022 to 4300
Ground 20P4 to 2110 40P4 to 4300
Note The 1 and input terminals for the DC power do not conform to UL/cUL standards.
Wiring Main Circuit Terminals
Main Circuit Configurations
The main circuit configurations of the Inverter are shown in Fig 2.5
.
Table 2.5 Inverter Main Circuit Configurations
200 V Class 400 V Class
CIMR-F7A20P4 to 2018 CIMR-F7A40P4 to 4018
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
Power supply
Control circuits
Cooling fan is provided for
Inverters of 3.7 kW or more.
CIMR-F7A2022, 2030
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
Power supply
Control circuits
Cooling fan is provided for
Inverters of 2.2 kW or more.
CIMR-F7A4022 to 4055
Power supply
Control circuits
CIMR-F7A2037 to 2110 a b
Power supply
Control circuits
CIMR-F7A4075 to 4300 a b a b
Power supply
Control circuits a b
Power supply
Control circuits
Note Consult your Yaskawa representative before using 12-phase rectification.
* These terminals are wired before shipment. When using DC power for the main circuit power supply, remove the wires between R-r/ for 200 V Class Inverters, input 200 VAC to r/
1
- /
2
, or, for 400 V Class Inverters, input either 200 VAC to r/
1
- 200/
1
and S- /
2
200 or 400 VAC to r/
2
, then,
1
-
400/
2
400.
2-
13
2
-14
Standard Connection Diagrams
Standard Inverter connection diagrams are shown in Fig 2.5.
The connections depend on the Inverter capacity.
CIMR-F7A20P4 to 2018 and 40P4 to 4018
DC reactor
(optional)
Braking Resistor
Unit (optional)
CIMR-F7A2022, 2030, and 4022 to 4055
Braking Resistor
Unit (optional)
Braking Unit
(optional)
3-phase 200
VAC (400 VAC)
3-phase 200
VAC (200 VAC)
Be sure to remove the short-circuit bar before connecting the DC reactor.
The DC reactor is built in.
IMPORTANT
When connecting a separately-installed type Braking Unit (model CDBR), connect the B1 terminal of the
Inverter to the + terminal of the Braking Unit and connect the − terminal of the Inverter to the − terminal of the
Braking Unit. The B2 terminal is not used in this case.
CIMR-FA2037 to 2110
Braking Resistor
Unit (optional)
Braking Unit
(optional)
CIMR-F7A4075 to 4300
Braking Resistor
Unit (optional)
Braking Unit
(optional)
3-phase
200 VAC
3-phase
400 VAC l l
Control power is supplied internally from the main circuit DC power supply for all Inverter models.
IMPORTANT
If a Braking Unit or a Braking Resistor Unit is connected to a wrong terminal, the Inverter, Braking Unit, or
Braking Resistor Unit can be damaged.
Refer to FOR VARISPEED-600 SERIES INVERTER BRAKING UNIT BRAKING RESISTOR UNIT
INSTRUCTIONS (TOBPC720600000) for connecting the Inverter with a Braking Unit or a Braking Resistor
Unit.
Fig 2.5 Main Circuit Terminal Connections
Wiring Main Circuit Terminals
Wiring the Main Circuits
This section describes wiring connections for the main circuit inputs and outputs.
Wiring Main Circuit Inputs
Observe the following precautions for wiring the main circuit power supply inputs.
Installing a Molded-case Circuit Breaker
Always connect the power input terminals (R, S, and T) and power supply via a molded-case circuit breaker
(MCCB) suitable for the Inverter.
• Choose an MCCB with a capacity of 1.5 to 2 times the Inverter's rated current.
•
•
For the MCCB's time characteristics, be sure to consider the Inverter's overload protection (one minute at
150% of the rated output current).
If the same MCCB is to be used for more than one Inverter, or other devices, set up a sequence so that the power supply will be turned OFF by a fault output, as shown in Fig 2.6
.
Inverter
20P4 to 2030: 3-phase,
200 to 240 VAC, 50/60 Hz
2037 to 2110: 3-phase,
200 to 230 VAC, 50/60 Hz
40P4 to 4300: 3-phase,
380 to 460 VAC, 50/60 Hz
Power supply
Fault output
(NC)
* For 400 V Class Inverters, connect a 400/200 V transformer.
Fig 2.6 MCCB Installation
Installing a Ground Fault Interrupter
Inverter outputs use high-speed switching, so high-frequency leakage current is generated. At the Inverter primary side, use a ground fault interrupter for Inverters with a countermeasure against high frequency to detect only the leakage current in the frequency range that is hazardous to humans and to ignore high-frequency leakage current. Use one or several ground fault interrupters with a total cumulative sensitivity amperage of at least 30 mA per Inverter.
Using a ground fault interrupter without a countermeasure against high frequency may result in a malfunction caused by high-frequency leakage current. If a ground fault interrupter without a countermeasure malfunctions, replace it with a ground fault interrupter with a countermeasure against high frequency or reduce the carrier frequency of the Inverter. Alternatively, use one or several ground fault interrupters with a total cumulative sensitivity amperage of at least 200 mA per Inverter.
2-
15
2
-16
Installing a Magnetic Contactor
If the power supply for the main circuit is to be shut off during a sequence, a magnetic contactor can be used.
When a magnetic contactor is installed on the primary side of the main circuit to forcibly stop the Inverter, however, the regenerative braking does not work and the Inverter will coast to a stop.
• The Inverter can be started and stopped by opening and closing the magnetic contactor on the primary side.
Frequently opening and closing the magnetic contactor, however, may cause the Inverter to break down.
Start and stop the Inverter at most once every 30 minutes.
•
•
When the Inverter is operated with the Digital Operator, automatic operation cannot be performed after recovery from a power interruption.
If the Braking Resistor Unit is used, program the sequence so that the magnetic contactor is turned OFF by the contact of the Unit's thermal overload relay.
Connecting Input Power Supply to the Terminal Block
Input power supply can be connected to any terminal R, S or T on the terminal block; the phase sequence of input power supply is irrelevant to the phase sequence.
Installing an AC Reactor or DC Reactor
If the Inverter is connected to a large-capacity power transformer (600 kW or more) or the phase advancing capacitor is switched, an excessive peak current may flow through the input power circuit, causing the converter unit to break down.
To prevent this, install an optional AC Reactor on the input side of the Inverter or a DC reactor to the DC reactor connection terminals.
This also improves the power factor on the power supply side.
Installing a Surge Absorber
Always use a surge absorber or diode for inductive loads near the Inverter. These inductive loads include magnetic contactors, electromagnetic relays, solenoid valves, solenoids, and magnetic brakes.
Installing a Noise Filter on Power Supply Side
Install a noise filter to eliminate noise transmitted between the power line and the Inverter.
• Correct Noise Filter Installation
Power supply
MCCB
Noise filter
Inverter IM
MCCB
Other controllers
Use a special-purpose noise filter for Inverters.
Fig 2.7 Correct Power supply Noise Filter Installation
Wiring Main Circuit Terminals
• Incorrect Noise Filter Installation
Power supply MCCB
Inverter
MCCB
Generalpurpose noise filter
Other controllers
IM
Power supply
MCCB
Generalpurpose noise filter
Inverter IM
MCCB
Other controllers
Do not use general-purpose noise filters. No generalpurpose noise filter can effectively suppress noise generated from the Inverter.
Fig 2.8 Incorrect Power supply Noise Filter Installation
Wiring the Output Side of Main Circuit
Observe the following precautions when wiring the main output circuits.
Connecting the Inverter and Motor
Connect output terminals U, V, and W to motor lead wires U, V, and W, respectively.
Check that the motor rotates forward with the Forward Run Command. Switch over any two of the output terminals to each other and reconnect if the motor rotates in reverse with the Forward Run Command.
Never Connect a Power Supply to Output Terminals
Never connect a power supply to output terminals U, V, and W. If voltage is applied to the output terminals, the internal circuits of the Inverter will be damaged.
Never Short or Ground Output Terminals
If the output terminals are touched with bare hands or the output wires come into contact with the Inverter casing, an electric shock or grounding will occur. This is extremely hazardous. Do not short the output wires.
Do Not Use a Phase Advancing Capacitor or Noise Filter
Never connect a phase advancing capacitor or LC/RC noise filter to an output circuit. The high-frequency components of the Inverter output may result in overheating or damage to these part or may result in damage to the Inverter or cause other parts to burn.
Precautions When Using an Magnetic Contactor
Never connect an magnetic contactor between the Inverter and motor and turn it ON or OFF during operation.
If the magnetic contactor is turned ON while the Inverter is operating, a large inrush current will be created and the overcurrent protection in the Inverter will operate.
2-
17
2
-18
When using an magnetic contactor to switch to a commercial power supply, stop the Inverter and motor before operating the magnetic contactor. Use the speed search function if the magnetic contactor is operated during operation. If measures for momentary power interrupts are required, use a delayed release magnetic contactor.
Installing a Thermal Overload Relay
This Inverter has an electronic thermal protection function to protect the motor from overheating. If, however, more than one motor is operated with one Inverter or a multi-polar motor is used, always install a thermal relay (THR) between the Inverter and the motor and set L1-01 to 0 (no motor protection). The sequence should be designed so that the contacts of the thermal overload relay turn OFF the magnetic contactor on the main circuit inputs.
Installing a Noise Filter on Output Side
Connect a noise filter to the output side of the Inverter to reduce radio noise and inductive noise.
Power supply
MCCB
Inverter
Noise filter
IM
Radio noise
Inductive noise
AM radio
Signal line
Controller
Inductive Noise:
Radio Noise:
Electromagnetic induction generates noise on the signal line, causing the controller to malfunction.
Electromagnetic waves from the Inverter and cables cause the broadcasting radio receiver to make noise.
Fig 2.9 Installing a Noise Filter on the Output Side
Countermeasures Against Inductive Noise
As described previously, a noise filter can be used to prevent inductive noise from being generated on the output side. Alternatively, cables can be routed through a grounded metal pipe to prevent inductive noise. Keeping the metal pipe at least 30 cm away from the signal line considerably reduces inductive noise.
Power supply
MCCB Metal pipe
Inverter IM
30 cm min.
Signal line
Controller
Fig 2.10 Countermeasures Against Inductive Noise
Wiring Main Circuit Terminals
Countermeasures Against Radio Interference
Radio noise is generated from the Inverter as well as from the input and output lines. To reduce radio noise, install noise filters on both input and output sides, and also install the Inverter in a totally enclosed steel box.
The cable between the Inverter and the motor should be as short as possible.
Power supply
MCCB
Steel box
Noise filter
Inverter
Noise filter
Metal pipe
IM
Fig 2.11 Countermeasures Against Radio Interference
Cable Length between Inverter and Motor
If the cable between the Inverter and the motor is long, the high-frequency leakage current will increase, causing the Inverter output current to increase as well. This may affect peripheral devices. To prevent this, adjust the carrier frequency (set in C6-01, C6-02) as shown in Table 2.6
. (For details, refer to Chapter 5 User Constants .)
Cable length
Carrier frequency
Table 2.6 Cable Length between Inverter and Motor
50 m max.
15 kHz max.
100 m max.
10 kHz max.
More than 100 m
5 kHz max.
Ground Wiring
Observe the following precautions when wiring the ground line.
•
•
Always use the ground terminal of the 200 V Inverter with a ground resistance of less than 100 Ω and that of the 400 V Inverter with a ground resistance of less than 10 Ω .
Do not share the ground wire with other devices, such as welding machines or power tools.
•
•
Always minimize the length of the ground wire.
Leakage current flows through the Inverter. Therefore, if the distance between the ground electrode and the ground terminal is too long, potential on the ground terminal of the Inverter will become unstable.
When using more than one Inverter, be careful not to loop the ground wire.
OK
Fig 2.12 Ground Wiring
NO
2-
19
2
-20
Connecting the Braking Resistor (ERF)
A Braking Resistor that mounts to the Inverter can be used with 200 V and 400 V Class Inverters with outputs from 0.4 to 3.7 kW.
Connect the braking resistor as shown in Fig 2.13
.
L8-01 (Protect selection for internal DB resistor)
L3-04 (Stall prevention selection during deceleration)
(Select either one of them.)
Table 2.7
1 (Enables overheat protection)
0 (Disables stall prevention function)
3 (Enables stall prevention function with braking resistor)
Inverter
Braking resistor
Fig 2.13 Connecting the Braking Resistor
IMPORTANT
The braking resistor connection terminals are B1 and B2. Do not connect to any other terminals. Connecting to any terminals other than B1 or B2 can cause the resistor to overheat, resulting in damage to the equipment.
Connecting the Braking Resistor Unit (LKEB) and Braking Unit (CDBR)
Use the following settings if using a Braking Resistor Unit and Braking Unit.
A Braking Resistor that mounts to the Inverter can also be used with Inverters with outputs from 0.4 to 3.7
kW.
Table 2.8
L8-01 (Protect selection for internal DB resistor) 0 (Disables overheat protection)
L3-04 (Stall prevention selection during deceleration)
(Select either one of them.)
0 (Disables stall prevention function)
3 (Enables stall prevention function with braking resistor)
L8-01 is used when a braking resistor without thermal overload relay trip contacts (ERF type mounted to
Inverter) is connected.
The Braking Resistor Unit cannot be used and the deceleration time cannot be shortened by the Inverter if L3-
04 is set to 1 (i.e., if stall prevention is enabled for deceleration).
Wiring Main Circuit Terminals
To prevent the Unit from overheating, design the sequence to turn OFF the power supply for the thermal overload relay trip contacts of the Unit as shown in Fig 2.14
.
200 V and 400 V Class Inverters with 0.4 to 18.5 kW Output
LKEB Braking
Resistor Unit
Inverter
Thermal overload relay trip contact
IMPORTANT
When connecting a separately-installed type Braking Unit (model CDBR), connect the B1 terminal of the
Inverter to the + terminal of the Braking Unit and connect the − terminal of the Inverter to the − terminal of the
Braking Unit. The B2 terminal is not used in this case.
200 V and 400 V Class Inverters with 22 kW or higher Output
CDBR Braking
Unit
LKEB Braking
Resistor Unit
Inverter
Thermal protector trip contact
Thermal overload relay trip contact
Fig 2.14 Connecting the Braking Resistor Unit and Braking Unit
Connecting Braking Units in Parallel
When connecting two or more Braking Units in parallel, use the wiring and connectors shown in Fig 2.15
.
There are connectors for selecting whether each Braking Unit is to be a Master or Slave. Select “Master” for the first Braking Unit only, and select “Slave” for all other Braking Units (i.e., from the second Unit onwards).
2-
21
2
-22
Braking resistor overheating contacts (Thermal protector contacts)
Braking
Resistor
Unit
Braking resistor overheating contacts (Thermal protector contacts)
Braking
Resistor
Unit
Braking resistor overheating contacts (Thermal protector contacts)
Braking
Resistor
Unit
Inverter
Braking Unit #2 Braking Unit #3
Braking Unit #1
Cooling fin overheating contacts (thermostat contacts)
Cooling fin overheating contacts (thermostatic contacts)
Cooling fin overheating contacts (thermostatic contacts)
Fig 2.15 Connecting Braking Units in Parallel
Breaking Unit Application Precautions
When using a Braking Resistor Unit, create a sequence to detect overheating of the braking resistor and turn
OFF the power supply to the Inverter.
MCCB
Three-phase power:
200 to 240 V, 50/60 Hz or
380 to 480 V, 50/60 Hz
R/L1
S/L2
T/L3
Overload relay trip contact of Braking Resistor Unit
Inverter
MC MA
Fault contacts
* Use a transformer with 200 and 400 V outputs for the power 400 V Inverter.
Fig 2.16 Power Shutoff Sequence
Wiring Control Circuit Terminals
Wiring Control Circuit Terminals
Wire Sizes and Closed-loop Connectors
For remote operation using analog signals, keep the control line length between the Digital Operator or operation signals and the Inverter to 50 m or less, and separate the lines from high-power lines (main circuits or relay sequence circuits) to reduce induction from peripheral devices.
When setting frequencies from an external frequency setter (and not from a Digital Operator), use shielded twisted-pair wires and ground the shield to terminal E (G), as shown in the following diagram.
Shield terminal
E(G)
2k Ω
2k Ω
V Speed setting power supply +15 V 20 mA
A1 Master speed reference 0 to 10 V (-10 to 10 V)
A2 Master speed reference 4 to 20 A
(0 to 10 V, -10 to 10 V)
2k Ω
2k Ω
P P
P P
A3 Auxiliary reference 0 to 10 V (-10 to 10 V)
RP Pulse train input 32 kHz max.
AC Analog common
-V Speed setting power supply -15 V 20 mA
Fig 2.17
Terminal numbers and wire sizes are shown in Table 2.9
.
Terminals
FM, AC, AM, P1, P2, PC,
SC, A1, A2,
S8
A3
M2
, +V, -V ,
S1, S2, S3, S4, S5, S6, S7,
, MA, MB, MC, M1,
Table 2.9 Terminal Numbers and Wire Sizes (Same for all Models)
Terminal
Screws
Tightening
Torque
(N•m)
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size mm
2
(AWG)
Wire Type
M3.5
0.8 to 1.0
0.5 to 2
*2
(20 to 14)
0.75
(18)
MP, RP, R+, R-, S+, S-,
IG
E (G)
Phoenix type
M3.5
0.5 to 0.6
0.8 to 1.0
Single wire
(26 to 14)
0.5 to 2
*2
(20 to 14)
*3
0.14 to 2.5
Stranded wire:
0.14 to 1.5
:
0.75
(18)
1.25
(12)
• Shielded, twisted-pair wire
*1
• Shielded, polyethylene-covered, vinyl sheath cable
(KPEV-S by Hitachi Electrical
Wire or equivalent)
* 1. Use shielded twisted-pair cables to input an external frequency reference.
* 2. Refer to Table 2.3 Close-loop Connector Sizes for suitable closed-loop crimp terminal sizes for the wires.
* 3. We recommend using straight solderless terminal on signal lines to simplify wiring and improve reliability.
2-
23
2
-24
Straight Solderless Terminals for Signal Lines
Models and sizes of straight solderless terminal are shown in the following table.
Wire Size mm
2
(AWG)
0.25 (24)
0.5 (20)
0.75 (18)
1.25 (16)
2 (14)
Table 2.10 Straight Solderless Terminal Sizes
Model
AI 0.25 - 8YE
AI 0.5 - 8WH
AI 0.75 - 8GY
AI 1.5 - 8BK
AI 2.5 - 8BU d1
0.8
1.1
1.3
1.8
2.3
d2
2
2.5
2.8
3.4
4.2
14
14
14
L
12.5
14
Manufacturer
Phoenix Contact d1 d2
Fig 2.18 Straight Solderless Terminal Sizes
Wiring Method
Use the following procedure to connect wires to the terminal block.
1. Loosen the terminal screws with a thin-slot screwdriver.
2. Insert the wires from underneath the terminal block.
3. Tighten the terminal screws firmly.
Thin-slot screwdriver Blade of screwdriver
Control circuit terminal block
Strip the end for
7 mm if no solderless terminal is used.
Wires
Solderless terminal or wire without soldering
3.5 mm max.
Blade thickness: 0.6 mm max.
Fig 2.19 Connecting Wires to Terminal Block
Wiring Control Circuit Terminals
Control Circuit Terminal Functions
The functions of the control circuit terminals are shown in Table 2.11
. Use the appropriate terminals for the correct purposes.
Type
Sequence input signals
Analog input signals
Photocoupler outputs
Table 2.11 Control Circuit Terminals
No.
Signal Name Function
S1 Forward Run/Stop Command Forward run when ON; stopped when OFF.
S2 Reverse Run/Stop Command Reverse run when ON; stopped when OFF.
S3 Multi-function input 1
*1
S4 Multi-function input 2
*1
Factory setting: External fault when ON.
Factory setting: Fault reset when ON.
S5
S6
S7
S8
SC
+V
-V
Multi-function input 3
Multi-function input 4
Multi-function input 5
Multi-function input 6
*1
*1
*1
*1
Sequence input common
+15 V power output
-15 V power output
Signal Level
Factory setting: Multi-speed reference 1 effective when ON.
Factory setting: Multi-speed reference 2 effective when ON.
Factory setting: Jog frequency selected when
ON.
Factory setting: External baseblock when
ON.
-
24 VDC, 8 mA
Photocoupler isolation
+15 V power supply for analog references
-15 V power supply for analog references
+15 V
(Max. current: 20 mA)
-15 V
(Max. current: 20 mA)
A1
A2
Master speed frequency reference
Multi-function analog input
-10 to +10 V/-100 to 100%
0 to +10 V/100%
4 to 20 mA/100%,
+100%
-10 to +10 V/-100 to
, 0 to +10 V/100%
Factory setting: Added to terminal A1
(H3-09 = 0)
-10 to +10 V , 0 to +10
V (Input impedance:
20 k Ω )
4 to 20 mA (Input impedance: 250 Ω )
-10 to +10 V , 0 to +10
V (Input impedance:
20 k Ω )
A3 Multi-function analog input
AC Analog reference common
E(G)
Shield wire, optional ground line connection point
-10 to +10 V/-100 to +100%, 0 to +10 V/
100%
Factory setting: Not used
(H3-05 = 1F)
0 V
-
P1
P2
Multi-function PHC output 1
Multi-function PHC output 2
-10 to +10 V, 0 to +10 V
(Input impedance:
20 k Ω )
-
-
Factory setting: Zero-speed
Zero-speed level (b2-01) or below when ON.
Factory setting: Frequency agreement detection
Frequency within 2 Hz of set frequency when ON.
50 mA max. at 48 VDC
*2
PC
Photocoupler output common for P1 and P2
-
2-
25
2
-26
Type
Relay outputs
No.
MA
MB
MC
M1
Fault output signal (NC contact)
Table 2.11 Control Circuit Terminals (Continued)
Signal Name
Fault output signal (NO contact)
Function
Fault when CLOSED across MA and MC
Fault when OPEN across MB and MC
Relay contact output common
-
Multi-function contact output
(NO contact)
Factory setting: Operating
Operating when CLOSED across M1 and
M2.
Signal Level
Dry contacts
Contact capacity:
10 mA min., 1 A max. at
250 VAC
10 mA min., 1 A max. at
30 VDC
Minimum permissible load: 5 VDC, 10 mA
*4
M2
Analog monitor outputs
Pulse
I/O
FM
AM
Multi-function analog monitor 1
Multi-function analog monitor 2
AC Analog common
RP
MP
Multi-function pulse input
*3
Multi-function pulse monitor
Factory setting: Output frequency
0 to 10 V/100% frequency
Factory setting: Current monitor
5 V/Inverter's rated current
-
Factory setting: Frequency reference input
(H6-01 = 0)
Factory setting: Output frequency
(H6-06 = 2)
-10 to +10 VDC ±5%
2 mA max.
0 to 32 kHz (3 k Ω
0 to 32 kHz (2.2 k
)
Ω )
RS-
485/
422
R+
R-
S+
S-
MEMOBUS communications input
MEMOBUS communications output
For 2-wire RS-485, short R+ and S+ as well as R- and S-.
Differential input, photocoupler isolation
Differential output, photocoupler isolation
IG Communications shield wire -
* 1. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-step speed setting 1 for S6, multi-step speed setting 2 for S7, and jog frequency command for S8.
* 2. When driving a reactive load, such as a relay coil, always insert a flywheel diode as shown in Fig 2.20
.
* 3. Pulse input specifications are given in the following table.
* 4. Use the photocoupler outputs when the minimum permissible load is 5 VDC or less and 10 mA or less.
Low level voltage
High level voltage
H duty
Pulse frequency
0.0 to 0.8 V
3.5 to 13.2 V
30% to 70%
0 to 32 kHz
Flywheel diode
External power:
48 V max.
Coil
50 mA max.
The rating of the flywheel diode must be at least as high as the circuit voltage.
Fig 2.20 Flywheel Diode Connection
Wiring Control Circuit Terminals
Shunt Connector CN5 and DIP Switch S1
The shunt connector CN 5 and DIP switch S1 are described in this section.
CN5
O
F
S1
1
2
OFF
V
ON
I
Terminating resistance
Analog input switch
: Factory settings
Note: Refer to Table 2.12
for S1 functions and to Table
2.13
for CN5 functions.
Fig 2.21 Shunt Connector CN5 and DIP Switch S1
The functions of DIP switch S1 are shown in the following table.
Name
S1-1
S1-2
RS-485 and RS-422 terminating resistance
Function
Table 2.12 DIP Switch S1
Setting
OFF: No terminating resistance
ON: Terminating resistance of 110 Ω
Input method for analog input A2
OFF: 0 to 10 V, − 10 to 10 V (internal resistance: 20 k Ω )
ON: 4 to 20 mA (internal resistance: 250 Ω )
2-
27
2
-28
Sinking/Sourcing Mode
The input terminal logic can be switched between sinking mode (0-V common) and sourcing mode (+24-V common) if shunt connector CN5 is used. An external 24-V power supply is also supported, providing more freedom in signal input methods.
Table 2.13 Sinking/Sourcing Mode and Input Signals
Internal Power Supply External Power Supply
CN5 CN5
CN5 (NPN set) Factory setting CN5 (EXT set)
Shunt position
SC
IP24V (24 V) External +24 V
SC
IP24V (24 V)
Sinking
Mode S1 S1
S2 S2
Sourcing
Mode
CN5
SC
CN5 (PNP set)
IP24V (24 V)
S1
S2
CN5
External + 24 V
SC
CN5 (EXT set)
IP24V (24 V)
S1
S2
Wiring Control Circuit Terminals
Control Circuit Terminal Connections
Connections to Inverter control circuit terminals are shown in Fig 2.22
.
Inverter
CIMR-F7A2022
External frequency references
Multi-function contact input
Defaults
Forward Run/Stop
Reverse Run/Stop
Thermal switch contact for Braking Unit
External fault
3 4
Fault reset
Multi-step command 1
(Main speed switching)
Multi-step speed setting 2
Jog frequency selection
External baseblock command
S1
S2
S3
S4
S5
S6
S7
S8
CN5 (NPN setting)
SC
+24V 8mA
Pulse train input
2 k
Ω
Frequency setting adjustment
Frequency setter
3
2 k
Ω
1
2
0 to 10 V
4 to 20 mA P
0 to 10 V
MEMOBUS communications
RS-485/422
P
P
R+
R-
S+
S-
E(G)
+24V
Shield wire connection terminal
RP
+V
A1
A2
A3
AC
Master speed pulse train
0 to 32 kHz (3 k
Ω
)
High level: 3.5 to 13.2 V input
Frequency setting power
+15 V 20 mA
0V
Master speed reference
0 to 10 V (20 k
Ω
)
Master speed reference
4 to 20 mA (250
Ω
)
[0 to 10 V (20 k
Ω
) input]
Multi-function anlog input
0 to 10 V (20 k
Ω
)
Factory setting:
Not used
-V (
−
15V 20mA)
Terminating resistance
IG
MP
AC
AM
FM
AC
Pulse train output
0 to 32 kHz (2.2 k Ω )
Default: Output frequency
−
Ammeter adjustment
20 k
Ω
Multi-function analog output 2
-10 to 10 V 2 mA
AM
+ Default: Output current
0 to +10 V
−
FM
Ammeter adjustment
20 k
Ω
+
Multi-function analog output 1
-10 to 10 V 2 mA
Default: Output current
0 to +10 V
E(G)
MA
MB
MC
M1
M2
P1
P2
PC
MA Error contact output
250 VAC, 10 mA min. 1 A max.
30 VDC, 10 mA min. 1 A max.
Min. load
5 VDC, 10 mA
MC
Multi-function contact output
250 VAC, 10 mA min. 1 A max.
30 VDC, 10 mA min. 1 A max.
Default: Running signal
Min. load
5 VDC, 10 mA
Open collector 1
Default: Zero- speed
Open collector 2
Default:
Frequency agree signal
Multi-function open-collector outputs
48 VDC, 50 mA
Fig 2.22 Control Circuit Terminal Connections
2-
29
2
-30
Control Circuit Wiring Precautions
Observe the following precautions when wiring control circuits.
• Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2,
•
•
•
•
•
Separate wiring for control circuit terminals MA, MB, MC, M1, and M2 (contact outputs) from wiring to other control circuit terminals.
Use shielded twisted-pair cables for control circuits to prevent operating faults. Process cable ends as shown in Fig 2.23
.
Connect the shield wire to terminal E (G).
Insulate the shield with tape to prevent contact with other signal lines and equipment.
Use a class 2 power supply (UL standard) when connecting to the control terminals.
Shield sheath Armor
Do not connect here.
Connect to shield sheath terminal at Inverter (terminal E
(G))
Insulate with tape
Fig 2.23 Processing the Ends of Shielded Twisted-pair Cables
Wiring Check
Wiring Check
Checks
Check all wiring after wiring has been completed. Do not perform a buzzer check on control circuits. Perform the following checks on the wiring.
•
•
Is all wiring correct?
Have any wire clippings, screws, or other foreign material been left?
•
•
Are all screws tight?
Are any wire ends contacting other terminals?
2-
31
2
-32
Installing and Wiring Option Boards
Option Board Models and Specifications
Up to three option boards can be mounted in the Inverter. You can mount up one board into each of the three places on the control board (A, C, and D) shown in Fig 2.24
.
Table 2.14
lists the type of option boards and their specifications.
Table 2.14 Option Board Specifications
Board Model Specifications
PG Speed Control Boards
PG-A2
PG-B2
PG-D2
PG-X2
Serial open-collector/complimentary inputs
Phase A/B complimentary inputs
Single line-driver inputs
Speed Reference Boards
AI-14U
AI-14B
DI-16H2 16-bit digital speed reference setting
DeviceNet Communication
Board
SI-N1
Profibus-DP Communication
Board
SI-P1
DeviceNet communications support
Profibus-DP communications support
InterBus-S Communication
Board *
CANopen Communication
Board *
CC-Link Communication
Board
SI-R
SI-S1
SI-C
InterBus-S communications support
CANopen communications support
CC-Link communications support
L ON W ORKS tion Board
Communica-
SI-J
SI-W1
L ON W ORKS communications support
MECHATROLINK Communication Board
SI-T MECHATROLINK communications support
AO-08 8-bit analog outputs, 2 channels
Analog Monitor Board
AO-12
DO-08
12-bit analog outputs, 2 channels
Six photocoupler outputs and 2 relay outputs
Digital Output Board
DO-02C 2 relay outputs
* Under development
DI-08
Phase A/B line-driver inputs
Input signal levels
0 to 10 V DC (20 k Ω ), 1 channel
4 to 20 mA (250 Ω ), 1 channel
Input resolution: 14-bit
Input signal levels
0 to 10 V DC (20 k Ω )
4 to 20 mA (250 Ω ), 3 channels
Input resolution: 13-bit with sign bit
8-bit digital speed reference setting
Mounting Location
A
A
A
A
C
C
C
C
D
D
D
D
C
C
C
C
C
C
C
Installing and Wiring Option Boards
Installation
Before mounting an option board, remove the terminal cover and be sure that the charge indicator inside the
Inverter is not lit. After confirming that the charge indicator is not lit, remove the Digital Operator and front cover and then mount the option board.
The side of the front cover of the Inverter for 200/400 V Class 0.4 to 5.5 kW can be cut out as described in Fig
2.25
to make wiring of the option board easy. If the side of the front cover is cut out, the protective structure will be open chassis (IEC IP00).
Refer to documentation provided with the option board for actual mounting instructions for option slots A, C, and D.
Preventing C and D option board Connectors from Rising
After installing an option board into slot C or D, insert an option clip to prevent the side with the connector from rising. The option clip can be easily removed by holding onto the protruding portion of the clip and pulling it out.
Remove the option clip before installing an option board into slot C or D. The option board cannot be installed completely and may not function property if it is installed with the option clip attached.
A option board mounting spacer hole
4CN
A option board connector
2CN
C option board connector
A option board mounting spacer
(Provided with A option board.)
Option clip
(To prevent raising of
C and D option boards)
3CN
D option board connector
C option board mounting spacer
C option board
D option board
D option board mounting spacer
A option board
A option board mounting spacer
Fig 2.24 Mounting option boards
Front Cover
Slit
Fig 2.25 Cutting the Front Cover
Cut out the slits on the front cover with nippers. Be careful to avoid injury.
2-
33
2
-34
PG Speed Control Board Terminals and Specifications
The terminal specifications for the PG Speed Control Boards are given in the following tables.
PG-A2
The terminal specifications for the PG-A2 are given in the following table.
Terminal No.
1
2
Table 2.15 PG-A2 Terminal Specifications
Contents
Power supply for pulse generator
Specifications
12 VDC (±5%), 200 mA max.
0 VDC (GND for power supply)
3
4
+12 V/open collector switching terminal
Terminal for switching between12 V voltage input and open collector input. For open collector input, short across 3 and 4.
TA1
TA2
5
8
(E)
6
7
Pulse input terminal
Pulse monitor output terminal
Shield connection terminal
H: +4 to 12 V; L: +1 V max. (Maximum response frequency: 30 kHz)
Pulse input common
12 VDC (±10%), 20 mA max.
Pulse monitor output common
-
PG-B2
The terminal specifications for the PG-B2 are given in the following table.
Terminal
TA1
TA2
TA3
6
1
2
3
4
(E)
No.
1
2
3
4
5
Table 2.16 PG-B2 Terminal Specifications
Contents Specifications
12 VDC (±5%), 200 mA max.
Power supply for pulse generator
0 VDC (GND for power supply)
A-phase pulse input terminal
H: +8 to 12 V
L: +1 V max.
(Maximum response frequency: 30 kHz)
B-phase pulse input terminal
Pulse input common
H: +8 to 12 V
L: +1 V max.
(Maximum response frequency: 30 kHz)
A-phase monitor output terminal
B-phase monitor output terminal
Shield connection terminal
Pulse input common
Open collector output, 24 VDC, 30 mA max.
A-phase monitor output common
Open collector output, 24 VDC, 30 mA max.
B-phase monitor output common
-
Installing and Wiring Option Boards
PG-D2
The terminal specifications for the PG-D2 are given in the following table.
Terminal
TA1
TA2
6
7
4
5
No.
1
2
3
8
(E)
Table 2.17 PG-D2 Terminal Specifications
Contents
Power supply for pulse generator
Pulse input + terminal
Pulse input - terminal
Common terminal
Pulse monitor output + terminal
Pulse monitor output - terminal
Shield connection terminal
* 5 VDC and 12 VDC cannot be used at the same time.
Specifications
12 VDC (±5%), 200 mA max.*
0 VDC (GND for power supply)
5 VDC (±5%), 200 mA max.*
Line driver input (RS-422 level input)
Maximum response frequency: 300 kHz
-
-
Line driver output (RS-422 level output)
PG-X2
The terminal specifications for the PG-X2 are given in the following table.
Terminal
TA1
TA2 4
5
2
3
10
1
8
9
6
7
4
5
No.
1
2
3
Table 2.18 PG-X2 Terminal Specifications
Contents
Power supply for pulse generator
A-phase + input terminal
A-phase - input terminal
B-phase + input terminal
B-phase - input terminal
Z-phase + input terminal
Z-phase - input terminal
Common terminal
A-phase + output terminal
A-phase - output terminal
B-phase + output terminal
B-phase - output terminal
Z-phase + output terminal
6
7
Z-phase - output terminal
Control circuit common
TA3 (E) Shield connection terminal
* 5 VDC and 12 VDC cannot be used at the same time.
12 VDC (±5%), 200 mA max.*
0 VDC (GND for power supply)
5 VDC (±5%), 200 mA max.*
Line driver input (RS-422 level input)
Maximum response frequency: 300 kHz
0 VDC (GND for power supply)
Line driver output (RS-422 level output)
Control circuit GND
Specifications
-
2-
35
2
-36
Wiring
Wiring examples are provided in the following illustrations for the option boards.
Wiring the PG-A2
Wiring examples are provided in the following illustrations for the PG-A2.
Three-phase,
200 VAC (400 VAC)
Inverter
R/L1 U/T1
V/T2 V/T2
W/T3 W/T3
4CN
E
PC-A2
E
4CN
TA1
4
5
TA2 (E)
6
7
8
1
2
3
+12 V power supply
0 V power supply
Pulse input (+)
Pulse input (-)
Pulse monitor output
• Shielded twisted-pair wires must be used for signal lines.
• Do not use the pulse generator's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.
• The length of the pulse generator's wiring must not be more than 100 meters.
• For open collector input, short across 3 and 4.
Fig 2.26 PG-A2 Wiring
PG power supply
+12 V
Short for open-collector input
Pulse input
Pulse input
Pulse monitor output
Fig 2.27 I/O Circuit Configuration of the PG-A2
Installing and Wiring Option Boards
Wiring the PG-B2
Wiring examples are provided in the following illustrations for the PG-B2.
Inverter
Three-phase 200
VAC (400 VAC)
Power supply +12 V
Power supply 0 V
A-phase pulse output (+)
A-phase pulse output (-)
B-phase pulse output (+)
B-phase pulse output (-)
A-phase pulse monitor output
B-phase pulse monitor output
• Shielded twisted-pair wires must be used for signal lines.
• Do not use the pulse generator's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.
• The length of the pulse generator's wiring must not be more than 100 meters.
• The direction of rotation of the PG can be set in user constant F1-05. The factory preset if for forward rotation, A-phase advancement.
Fig 2.28 PG-B2 Wiring
PG power supply +12 V
A-phase pulse input
B-phase pulse input
A-phase pulses
B-phase pulses
A-phase pulse monitor output
B-phase pulse monitor output
• When connecting to a voltage-output-type PG (encoder), select a PG that has an output impedance with a current of at least 12 mA to the input circuit photocoupler (diode).
• The pulse monitor dividing ratio can be changed using constant F1-06 (PG division rate).
A-phase pulses
B-phase pulses
• The pulse monitor emitter is connected to common inside the PG-B2. The emitter common must be used for external circuits.
Fig 2.29 I/O Circuit Configuration of the PG-B2
2-
37
Wiring the PG-D2
Wiring examples are provided in the following illustrations for the PG-D2.
Three-phase 200
VAC (400 VAC)
Inverter
2
-38
Power supply +12 V
Power supply 0 V
Power supply +5 V
Pulse input + (A/B phase)
Pulse input - (A/B phase)
Pulse monitor output
• Shielded twisted-pair wires must be used for signal lines.
• Do not use the pulse generator's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.
• The length of the pulse generator's wiring must not be more than 100 meters.
Fig 2.30 PG-D2 Wiring
Wiring the PG-X2
Wiring examples are provided in the following illustrations for the PG-X2.
Three-phase
200 VAC (400
VAC)
Inverter
R/L1 U/T1
S/L2
T/L3
V/T2
W/T3
Power supply +12 V
Power supply 0 V
Power supply +5 V
A-phase pulse input (+)
A-phase pulse input (-)
B-phase pulse input (+)
B-phase pulse input (-)
A-phase pulse monitor output
B-phase pulse monitor output
Z-phase pulse monitor output
• Shielded twisted-pair wires must be used for signal lines.
• Do not use the pulse generator's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.
• The length of the pulse generator's wiring must not be more than 100 meters.
• The direction of rotation of the PG can be set in user constant F1-05 (PG Rotation). The factory preset if for motor forward rotation, A-phase advancement.
Fig 2.31 PG-X2 Wiring
Installing and Wiring Option Boards
Wiring Terminal Blocks
Use no more than 100 meters of wiring for PG (encoder) signal lines, and keep them separate from power lines.
Use shielded, twisted-pair wires for pulse inputs and pulse output monitor wires, and connect the shield to the shield connection terminal.
Wire Sizes (Same for All Models)
Terminal wire sizes are shown in Table 2.19
.
Terminal
Pulse generator power supply
Pulse input terminal
Pulse monitor output terminal
Shield connection terminal
Table 2.19 Wire Sizes
Terminal
Screws
-
M3.5
Wire Thickness (mm
2
) Wire Type
Stranded wire: 0.5 to 1.25
Single wire: 0.5 to 1.25
0.5 to 2
• Shielded, twisted-pair wire
• Shielded, polyethylene-covered, vinyl sheath cable
(KPEV-S by Hitachi Electric Wire or equivalent)
Straight Solderless Terminals for Control Circuit Terminals
We recommend using straight solderless terminal on signal lines to simplify wiring and improve reliability.
Refer to Table 2.10 Straight Solderless Terminal Sizes for specifications.
Closed-loop Connector Sizes and Tightening Torque
The closed-loop connectors and tightening torques for various wire sizes are shown in Table 2.20
.
Wire Thickness [mm
2
]
Table 2.20 Closed-loop Connectors and Tightening Torques
Terminal
Screws
Crimp Terminal Size Tightening Torque (N • m)
0.5
1.25 - 3.5
0.75
1.25
2
M3.5
1.25 - 3.5
1.25 - 3.5
2 - 3.5
0.8
Wiring Method and Precautions
The wiring method is the same as the one used for straight solderless terminals. Refer to page 2-24. Observe the following precautions when wiring.
• Separate the control signal lines for the PG Speed Control Board from main circuit lines and power lines.
•
•
•
•
Connect the shield when connecting to a PG. The shield must be connected to prevent operational errors caused by noise. Also, do not use any lines that are more than 100 m long. Refer to Fig 2.23
for details on connecting the shield.
Connect the shield to the shield terminal (E).
Do not solder the ends of wires. Doing so may cause contact faults.
When not using straight solderless terminals, strip the wires to a length of approximately 5.5 mm.
2-
39
2
-40
Selecting the Number of PG (Encoder) Pulses
The setting for the number of PG pulses depends on the model of PG Speed Control Board being used. Set the correct number for your model.
PG-A2/PG-B2
The maximum response frequency is 32,767 Hz.
Use a PG that outputs a maximum frequency of approximately 20 kHz for the rotational speed of the motor.
60
= 20,000 Hz
Some examples of PG output frequency (number of pulses) for the maximum frequency output are shown in
Table 2.21
.
Motor's Maximum Speed (min
-1
1800
1500
Table 2.21 PG Pulse Selection Examples
)
PG Rating
(p/rev)
600
600
PG Output Frequency for Maximum Frequency Output (Hz)
18,000
15,000
1200
900
900
1200
18,000
18,000
Note 1. The motor speed at maximum frequency output is expressed as the sync rotation speed.
2. The PG power supply is 12 V.
3. A separate power supply is required if the PG power supply capacity is greater than 200 mA. (If momentary power loss must be handled, use a backup capacitor or other method.)
PG power supply
Capacitor for momentary power loss
Signals
Fig 2.32 PG-B2 Connection Example
Installing and Wiring Option Boards
PG-D2/PG-X2
There are 5 V and 12 V PG power supplies.
Check the PG power supply specifications before connecting.
The maximum response frequency is 300 kHz.
Use the following equation to computer the output frequency of the PG (f
PG
).
fPG(Hz) =
60
A separate power supply is required if the PG power supply capacity is greater than 200 mA. (If momentary power loss must be handled, use a backup capacitor or other method.)
PG-X2
TA1
IP12
IG
IP5
A (+)
A (-)
B (+)
B (-)
Z (+)
Z (-)
IG
8
9
10
5
6
3
4
7
1
2
PG power supply
AC
Capacitor for momentary power loss
0V +12V
+
0 V
+12 V
+
-
+
-
PG
TA3
Fig 2.33 PG-X2 Connection Example (for 12 V PG power supply)
2-
41