Analog Inputs Setup Screen. Murphy Centurion C5 Series, Centurion C5
Reklama
Reklama
Analog Inputs Setup Screen
For all configured analog input devices, the user may edit: a) Scaled Minimum Minimum engineering scale for the input when the raw counts are at the raw count offset reading.
Example: 0 PSI for a 0-100 PSI transmitter. b) Scaled Maximum - Maximum engineering scale for the input when the raw counts are at the raw count offset + raw count max (total raw counts).
Example: 100 PSI for a 0-100 PSI transmitter.
NOTE: To calibrate an analog input, change the raw offset and max settings. The scaled minimum and maximum settings should match the engineering unit range for the device. c) Moving Average Samples.
(1, 2, 4). Apply averaging filter to the input. d) Raw Count Offset.
Set the lowest raw analog input counts seen from the device. e) Raw Count Span.
Set the highest raw analog input counts span seen from the device. This number is added to the raw count offset to equal the actual raw count reading.
The user can view the raw counts of the analog inputs to calibrate the input by adjusting the offset and max raw count readings.
NOTE: Typical approximate raw readings for 4-
20mA input:
4mA = 5243 counts
20mA = 26214 counts (5243 + 20971)
Section 50
2021-06-21 - 30 -
00-02-1031