Gas Piping. Lennox ML196DFE Series Units

Add to My manuals
51 Pages

advertisement

Gas Piping. Lennox ML196DFE Series Units | Manualzz

Gas Piping

Gas supply piping should not allow more than 0.5”W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.

CAUTION

If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line.

WARNING

Do not over torque (800 in-lbs) or under torque (350 inlbs) when attaching the gas piping to the gas valve.

1 - Gas piping may be routed into the unit through either the left- or right-hand side. Supply piping enters into the gas valve from the side of the valve as shown

in Figure 51. Connect the gas supply piping into the

gas valve. The maximum torque is 800 in lbs and minimum torque is 350 in lbs when when attaching the gas piping to the gas valve.

2 - When connecting gas supply, factors such as length of run, number of fittings and furnace rating must be considered to avoid excessive pressure drop.

TABLE 11 lists recommended pipe sizes for typical

applications.

NOTE - Use two wrenches when connecting gas piping to avoid transferring torque to the manifold.

3 - Gas piping must not run in or through air ducts, clothes chutes, chimneys or gas vents, dumb waiters or elevator shafts. Center gas line through piping hole. Gas line should not touch side of unit. See

Figure 51.

4 - Piping should be sloped 1/4 inch per 15 feet (6mm per 5.6m) upward toward the gas meter from the furnace. The piping must be supported at proper intervals, every 8 to 10 feet (2.44 to 3.05m), using suitable hangers or straps. Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate.

5 - A 1/8” N.P.T. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection.

See Figure 55.

6 - In some localities, codes may require installation of a manual main shut-off valve and union (furnished by installer) external to the unit. Union must be of the ground joint type.

IMPORTANT

Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petroleum gases.

Leak Check

After gas piping is completed, carefully check all field-in stalled piping connections for gas leaks. Use a commercially available leak detecting solution specifically manu factured for leak detection. Never use an open flame to test for gas leaks.

The furnace must be isolated from the gas supply sys tem by closing the individual manual shut-off valve during any gas supply system at pressures greater than or equal to ½ psig. (3.48 kPa, 14 inches w.c.). This furnace and its components are designed, manufactured and inde pendently certified to comply with all applicable ANSI/CSA standards. A leak check of the furnace and its components is not required.

1/8” N.P.T. PLUGGED TAP

CAP

Figure 50

FURNACE

IMPORTANT

When testing pressure of gas lines, gas valve must be

disconnected and isolated. See Figure 50. Gas valves

can be damaged if subjected to pressures greater than

1/2 psig (3.48 kPa).

WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection. Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed.

Page 33

MANUAL

MAIN SHUT-OFF

VALVE

(1/8 in. NPT plugged tap shown)

Left Side Piping

(Standard)

AUTOMATIC

GAS VALVE

(with manual shut-off valve)

AUTOMATIC

GAS VALVE

(with manual shut-off valve)

MANUAL

MAIN SHUT-OFF

VALVE

(1/8 in. NPT plugged tap shown)

GROUND

JOINT

UNION

GROUND

JOINT

UNION

DRIP LEG

FIELD

PROVIDED

AND INSTALLED

NOTE - BLACK IRON PIPE

ONLY

TO BE ROUTED INSIDE OF CABINET

DRIP LEG

Right Side Piping

(Alternate)

Figure 51

Nominal

Iron Pipe

Size Inches

(mm)

1/2

(12.7)

3/4

(19.05)

1

(25.4)

1-1/4

(31.75)

1-1/2

(38.1)

2

(50.8)

2-1/2

(63.5)

3

(76.2)

Internal

Diameter inches

(mm)

.622

(17.799)

.824

(20.930)

1.049

(26.645)

1.380

(35.052)

1.610

(40.894)

2.067

(52.502)

2.469

(67.713)

3.068

(77.927)

10

(3.048)

172

(4.87)

360

(10.19)

678

(19.19)

1350

(38.22)

2090

(59.18)

4020

(113.83)

6400

(181.22)

11300

(319.98)

20

(6.096)

118

(3.34)

247

(7.000)

466

(13.19)

957

(27.09)

1430

(40.49)

2760

(78.15)

4400

(124.59)

7780

(220.30)

TABLE 11

Gas Pipe Capacity - ft3/hr (m3/hr)

Length of Pipe - feet (m)

30

(9,144)

95

(2.69)

199

(5.63)

374

(10.59)

768

(22.25)

1150

(32.56)

2220

(62.86)

3530

(99.95)

6250

(176.98)

40

(12,192)

81

(2.29)

170

(4.81)

320

(9.06)

657

(18.60)

985

(27.89)

1900

(53.80)

3020

(85.51)

5350

(151.49)

50

(15.240)

72

(2.03)

151

(4.23)

284

(8.04)

583

(16.50)

873

(24.72)

1680

(47.57)

2680

(75.88)

4740

(134.22)

60

(18.288)

65

(1.84)

137

(3.87)

257

(7.27)

528

(14.95)

791

(22.39)

1520

(43.04)

2480

(70.22)

4290

(121.47)

70

(21.336)

60

(1.69)

126

(3.56)

237

(6.71)

486

(13.76)

728

(20.61)

1400

(39.64)

2230

(63.14)

3950

(111.85)

80

(24.384)

NOTE Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.

56

(1.58)

117

(3.31)

220

(6.23)

452

(12.79)

677

(19.17)

1300

(36.81)

2080

(58.89)

3670

(103.92)

90

(27.432)

635

(17.98)

1220

(34.55)

1950

(55.22)

3450

(97.69)

52

(1.47)

110

(3.11)

207

(5.86)

424

(12.00)

100

(30,480)

50

(1.42)

104

(2.94)

195

(5.52)

400

(11.33)

600

(17.00)

1160

(32.844)

1840

(52.10)

3260

(92.31)

Page 34

advertisement

Related manuals