Overview
The EtherNet/IP communication module stores data and offers services in a CIP object hierarchy, consisting of the following nested levels:
When the module’s local slave service is activated, remote devices can send explicit messages to the module’s object hierarchy and perform services that:
access module data, or execute module commands
The local slave function is activated by selecting Active Configuration in the General Configuration page of the Local Slave window
see page 62
.
This chapter describes the CIP objects the EtherNet/IP communication module can expose to remote devices.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Adapter Diagnostic Object
Assembly Object
Connection Manager Object
Ethernet Link Object
Identity Object
Module Diagnostic Object
Scanner Diagnostic Object
TCP/IP Interface Object
Page
31008211 09/2020
169
CIP objects
Adapter Diagnostic Object
Overview
The Adapter Diagnostic CIP object consists of the attributes and services described below.
Attributes
The Adapter Diagnostic CIP object consists of the following attributes:
1. Class attributes:
ID (hex)
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
2. Instance attributes:
ID (hex) Description
01 Control Bits
Type
WORD
GET SET
X X
SET
—
—
Value
0: Deactivate checking time for production and consumption (default)
1: Activate
02 ST_DIAG_CNT wErrFrameCnt
STRUCT X
UINT
X wErrTimeOutCnt wErrRefusedCnt dwErrProdCnt dwErrConsCnt dwErrProdByteCnt dwErrConsByteCnt
03
04
Input Status
Output Status
X = supported
— = not supported
UINT
UINT
UDINT
UDINT
UDINT
UDINT
WORD
WORD
X
X
—
—
Incremented each time a frame isn’t sent by missing resources or is impossible to send.
Incremented when a connection is timed out.
Incremented when a connection is refused by the remote station.
Incremented at each production.
Incremented at each consumption.
Total bytes produced.
Total bytes consumed.
See Status descriptions, below.
See Status descriptions, below.
170
31008211 09/2020
ID (hex) Description
05 ST_LINK
CIP Status
Extended Status
Production
Connection ID
06
Consumed
Connection ID
OtoT API
TtoO API
OtoT RPI
TtoO RPI
ST_SOCK_PARAM
IpSockId
IpForeign wPortForeign
IpLocal wPortLocal
X = supported
— = not supported
CIP objects
Type
STRUCT X
UINT
GET SET
—
UINT
DWORD
DWORD
UDINT
UDINT
UDINT
UDINT
STRUCT X
DWORD
DWORD
UINT
DWORD
UINT
—
Value
See Status descriptions, below.
See Status descriptions, below.
Connection ID
Connection ID
API of the Connection
API of the Connection
RPI of the Connection
RPI of the Connection
Internal identifier
IP of the remote station
Port number of the remote station
IP of the local station
Port number of the local station
31008211 09/2020
171
CIP objects
ID (hex) Description
07 ST_PRODUCTION bValid dwCurrentTime dwProductionTime
SequenceNumber stCheckTime dwLastTime dwMaxTime dwMinTime dwRPI wOverRun wUnderRun dwCurrentTime
X = supported
— = not supported
UDINT
UDINT
UDINT
STRUCT
UDINT
UDINT
UDINT
UDINT
UINT
UINT
UDINT
Type
STRUCT X
WORD
GET SET
—
Value
0: data of the struct production is not valid
1: data of the struct production is valid
(Internal Use—number of ticks before next production)
(Internal Use—number of ticks between production)
Number of the dwquence in the production
(Internal Use)
Maximum time between 2 productions
Minimum time between 2 productions
API of the connection
Number of times the production was too long
Number of times the production was too short
(Internal Use)
172
31008211 09/2020
CIP objects
ID (hex) Description
08
09
ST_CONSUMPTION bValid dwCurrentTime UDINT dwConsumptionTime UDINT
SequenceNumber stCheckTime dwLastTime dwMaxTime dwMinTime dwRPI wOverRun
UDINT
STRUCT
UDINT
UDINT wUnderRun dwCurrentTime
Connection Entry List byGeneralStatus byReserved
Extended Status
X = supported
— = not supported
Type
STRUCT X
WORD
GET SET
—
Value
0: data of the struct consumption is not valid
1: data of the struct consumption is valid
(Internal Use—number of ticks before the timeout)
(Internal Use—number of ticks in the timeout)
Number of the sequence in the consumption
UDINT
UDINT
UINT
UINT
UDINT
STRUCT X
BYTE
BYTE
WORD
—
(Internal Use)
Maximum time between 2 consumptions
Minimum time between 2 consumptions
API of the connection
Number of times the consumption was too long
Number of times the consumption was too short
(Internal Use)
Status of the CCO object. See Status descriptions, below.
31008211 09/2020
173
CIP objects
Adapter Status
Adapter status values include the followng:
Status Description Extended Explanation
0
33
53
54
OK
No connection
IDLE
Connection in progress
0xFB
0xFD
0xFE
0x02
0x20
0
0
0
0
CIP
Status
0xFB
0xFB
0xFB
0xFB
0
0
0
0
0
0
0xFB01
0xFB07
0xFB0B
0xFB0C
0xFB0E
The I/O data are correctly exchanged.
No connection.
Connection in timeout.
Optimization error / unknown MAC Address.
Timeout on consumption.
Connection closed by a Fw_Close.
Module in STOP.
Error from encapsulation layer.
Error on TCP connection.
No more resources to handle the connection.
Connections refused by bad format or parameters.
An IDLE notification is received.
The connection is established, but I/O data is not yet consumed.
174
31008211 09/2020
CIP objects
Services
The CIP Adapter Diagnostic object performs the following services upon the listed object types:
ID (hex)
01
61
62
63
Description Class Instance Notes
Get_Attributes_All X X
Get_Output — X Returns the status and values of the output:
Offset Type Description
Get_Intput — X
0
2
UINT Status
USINT[0...409] Output Data
Returns the status and values of the input:
Offset Type Description
Set_DiagCounters — X
0
2
UINT Status
USINT[0...409] Input Data
Sets the values of the structure:
ST_DIAG_CNT to 0, and
ST_CHECK_TIME (production and consumption) to 0 (but not fields dwLastTime and dwCurrentTime)
the structure ST_DIAG_CNT to 0.
X = supported
— = not supported
31008211 09/2020
175
CIP objects
Assembly Object
Overview
The Assembly CIP object consists of the attributes and services described below.
Attributes
The Assembly CIP object consists of the following attributes:
1. Class attributes:
ID (hex)
01
Description
Revision
02 Max Instance
X = supported
— = not supported
2. Instance attributes:
ID (hex)
03
Description
Data
X = supported
— = not supported
Type
Array of
BYTE
GET
X
X
SET
—
—
GET
X
SET
X
Services
The CIP Assembly object performs the following services upon the listed object types:
ID (hex)
01
0E
10
Description
Get_Attributes_All
Get_Attributes_Single
Set_Attributes_Single
Class Instance
X X
X
—
X
X
Notes
—
—
Returns these values:
0E=attribute not settable: assembly is not o->T type
0F=permission denied: assembly is being used by an active connection
13=config too small: the
Set_Attributes_Single command contains partial data
15=too big data: the Set_Attributes_Single command contains too much data
X = supported
— = not supported
176
31008211 09/2020
CIP objects
Connection Manager Object
Overview
The Connection Manager CIP object consists of the attributes and services described below.
Attributes
The Connection Manager CIP object consists of the following attributes:
1. Class attributes:
ID (hex)
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
2. Instance attributes:
ID (hex) Description
01 Open Requests
02 Open Format Rejects
03
04
05
06
07
Open Other Rejects
Close Requests UINT
Close Format Requests UINT
Close Other Requests
Type
UINT
UINT
Open Resource Rejects UINT
UINT
UINT
SET
—
—
GET SET Value
X X Number of Forward Open service requests received
X X
X
X
X
X
Number of Forward Open service requests that were rejected due to bad format
Number of Forward Open service requests that were rejected due to lack of resources
Number of Forward Open service requests that were rejected for reasons other than bad format or lack of resources
X X
X
X
X
X
Number of Forward Close service requests received
Number of Forward Close service requests that were rejected due to bad format
Number of Forward Close service requests that were rejected for reasons other than bad format
X = supported
— = not supported
31008211 09/2020
177
CIP objects
ID (hex) Description
08 Connection Timeouts
09
11
12
13
Connection Entry List
CPU_Utilization
MaxBuffSize
BufSize Remaining
X = supported
— = not supported
Type
UINT
STRUCT X
UINT X
GET SET Value
X X Total number of connection timeouts that occurred in connections controlled by this connections manager
—
—
List of connections—always 0
CPU Utilization in tenths of a percent— always 0
UDINT
UDINT
X
X
—
—
Amount of buffer space originally available—always 0
Amount of buffer space now available— always 0
Services
The CIP Connection Manager object performs the following services upon the listed object types:
ID (hex)
01
0E
4E
Description
Get_Attributes_All
Get_Attributes_Single
Forward Close
52
54
Unconnected Send
Forward Open
X = supported
— = not supported
Class Instance
X X
X
—
X
X
—
—
X
X
Notes
—
—
Managed internally by the
EtherNet/IP stack—no link to
CPU exists
178
31008211 09/2020
CIP objects
Ethernet Link Object
Overview
The Ethernet Link CIP object consists of the attributes and services described below.
Attributes
The Ethernet Link CIP object consists of the following attributes:
1. Class attributes:
ID (hex)
01
Description
Revision
02 Max Instance
X = supported
— = not supported
2. Instance attributes:
ID (hex) Description
01 Interface Speed
02 Interface Flags
Type
UDINT
DWORD
—
GET
X
X
SET
—
—
Value
Valid values include:
0, 10000000, 100000000
Bit 0: Link Status
0 = Inactive
1 = Active
Bit 1: Duplex Mode
0 = half duplex
1 = full duplex
Bits 2-4: Negotiation Status
3 = successfully negotiated speed and duplex
4 = forced speed and link
Bit 5: Manual Setting Requires Reset
0 = automatic
1 = device need reset
Bit 6: Local Hardware Fault
0 = no fault
1 = fault detected
Module MAC Address 03 Physical Address ARRAY of
6 USINT
X = supported
— = not supported
X
GET SET
X —
X —
31008211 09/2020
179
CIP objects
ID (hex) Description
04 Interface Counters STRUCT
In octets
Type
UDINT
GET
X
SET
—
UDINT In Ucast
Packets
In NUcast
Packets
In Discards
UDINT
UDINT
In Errors UDINT
UDINT In Unknown
Protos
Out Octets
Out Ucast
Packets
Out NUcast
Packets
Out Discards
Out Errors
X = supported
— = not supported
UDINT
UDINT
UDINT
UDINT
UDINT
Value
Octets received on the interface
Unicast packets received on the interface
Non-unicast packets received on the interface
Inbound packets received on the interface, but discarded
Inbound packets that contain errors
(does not include In Discards)
Inbound packets with unknown protocol
Octets sent on the interface
Unicast packets sent on the interface
Non-unicast packets sent on the interface
Outbound packets discarded
Outbound packets that contain errors
180
31008211 09/2020
CIP objects
ID (hex) Description
05 Media Counters
Alignment
Errors
FCS Errors
Single
Collisions
Multiple
Collisions
SQE Test
Errors
Deferred
Transmissions
Type
STRUCT X
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
Late Collisions UDINT
GET SET
—
Excessive
Collisions
MAC Transmit
Errors
Carrier Sense
Errors
Frame Too
Long
MAC Receive
Errors
X = supported
— = not supported
UDINT
UDINT
UDINT
UDINT
UDINT
Value
Frames that are not an integral number of octets in length
Frames received that do not pass the
FCS check
Successfully transmitted frames that experienced exactly one collision
Successfully transmitted frames that experienced more than one collision
Number of times the SQE test error is generated
Frames for which first transmission attempt is delayed because the medium is busy
Number of times a collision is detected later than 512 bittimes into the transmission of a packet
Frames for which transmission fails due to excessive collisions
Frames for which transmission fails due to internal MAC sublayer transmit error
Times that the carrier sense condition was lost or never asserted when attempting to transmit a frame
Frames received that exceed the maximum permitted frame size
Frames for which reception on an interface fails due to an internal MAC sublayer receive error
31008211 09/2020
181
CIP objects
ID (hex) Description
06 Interface Control
Control Bits
Type
STRUCT
WORD
GET
X
SET
X
Forced
Interface Speed
UINT
Value
API of the connection
Bit 0: Auto-negotiation
0 = Disabled
1 = Enabled
Note: When auto-negotiation is enabled, the error 0x0C (Object State
Conflict) is returned when attempting to set either:
Forced Interface Speed, or
Forced Duplex Mode
Bit 1: Forced Duplex Mode (if autonegotiation bit = 0)
0 = half duplex
1 = full duplex
Valid values include:
10000000, 100000000
Note: Attempting to set any other value returns the error 0x09
(Invalid Attribute Value)
X = supported
— = not supported
Services
The CIP Ethernet Link object performs the following services upon the listed object types:
ID (hex)
01
05
0E
X = supported
— = not supported
Description
Get_Attributes_All
Set_Attribute_Single
Get_Attribute_Single
Class
X
—
X
X
X
Instance
X
182
31008211 09/2020
Identity Object
Overview
The Identity CIP object consists of the attributes and services described below.
Attributes
The Identity CIP object consists of the following attributes:
1. Class attributes:
ID (hex)
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
2. Instance attributes:
ID (hex)
01
02
03
04
Description
Vendor ID
Device Type
Product Code
Revision
Major
Minor
05 Status bit 2:
0x01=the module is configured bits 4-7:
0x03=no I/O connections established
0x06=at least 1 I/O connection in run mode
0x07=at least 1 I/O connection established, all in IDLE mode
06
07
Serial Number
Product Name
X = supported
— = not supported
Type
UINT
UINT
UINT X
STRUCT X
USINT
USINT
Word
GET
X
X
X
UDINT
STRING
X
X
SET
—
—
—
—
—
SET
—
—
—
—
CIP objects
31008211 09/2020
183
CIP objects
Services
The CIP Identity object performs the following services upon the listed object types:
ID (hex)
01
0E
05
Description
Get_Attributes_All
Get_Attributes_Single
Reset
Class Instance
X X
X
—
X
X
Notes
Applies to all class and all instance attributes
Applies to all class and all instance attributes
Two types:
00=power cycle
01=return to factory defaults and power cycle
X = supported
— = not supported
184
31008211 09/2020
CIP objects
Module Diagnostic Object
Overview
The Module Diagnostic CIP object consists of the attributes and services described below.
Attributes
The Module Diagnostic CIP object consists of the following attributes:
1. Class attributes:
ID (hex)
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
2. Instance attributes:
ID (hex) Description
01 Module Status
02
03
04
05
CNF Version
CRC
I/O Connection Status
Size Table
Table
Cco Mode
SET
—
—
Type
WORD
WORD
UDINT X
STRUCT X
WORD
WORD[]
WORD
GET SET Value
X — 01=started
02=stopped
03=running
X — 0x0100
X
—
—
X
—
— size (16 bytes) table of I/O status (8 WORDS)
1=INPUT and OUTPUT status of I/O connection are OK
0=at least 1 INPUT or OUTPUT status of I/O connection is not OK
01=activate status to CCO in the module
02=block access to CCO
X = supported
— = not supported
31008211 09/2020
185
CIP objects
Services
The CIP Module Diagnostic object performs the following services upon the listed object types:
ID (hex)
01
Description
Get_Attributes_All
0E Set_Attributes_Single
X = supported
— = not supported
Class Instance
X X
— X
Notes
—
—
186
31008211 09/2020
CIP objects
Scanner Diagnostic Object
Overview
The Scanner Diagnostic CIP object consists of the attributes and services described below.
Attributes
The Scanner Diagnostic CIP object consists of the following attributes:
1. Class attributes:
ID (hex)
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
2. Instance attributes:
ID (hex) Description
01 Control Bits
Type
WORD
GET SET
X X
SET
—
—
Value
0: Deactivate checking time for production and consumption (default)
1: Activate
02 ST_DIAG_CNT wErrFrameCnt
STRUCT X
UINT
X wErrTimeOutCnt wErrRefusedCnt dwErrProdCnt dwErrConsCnt dwErrProdByteCnt dwErrConsByteCnt
03
04
Input Status
Output Status
X = supported
— = not supported
UINT
UINT
UDINT
UDINT
UDINT
UDINT
WORD
WORD
X
X
—
—
Incremented each time a frame isn’t sent by missing resources or is impossible to send.
Incremented when a connection is timed out.
Incremented when a connection is refused by the remote station.
Incremented at each production.
Incremented at each consumption.
Total bytes produced.
Total bytes consumed.
See Status descriptions, below.
See Status descriptions, below.
31008211 09/2020
187
CIP objects
ID (hex) Description
05 ST_LINK
CIP Status
Extended Status
Production
Connection ID
06
Consumed
Connection ID
OtoT API
TtoO API
OtoT RPI
TtoO RPI
ST_SOCK_PARAM
IpSockId
IpForeign wPortForeign
IpLocal wPortLocal
X = supported
— = not supported
Type
STRUCT X
UINT
GET SET
—
UINT
DWORD
DWORD
UDINT
UDINT
UDINT
UDINT
STRUCT X
DWORD
DWORD
UINT
DWORD
UINT
—
Value
See Status descriptions, below.
See Status descriptions, below.
Connection ID
Connection ID
API of the Connection
API of the Connection
RPI of the Connection
RPI of the Connection
Internal identifier
IP of the remote station
Port number of the remote station
IP of the local station
Port number of the local station
188
31008211 09/2020
CIP objects
ID (hex)
07
Description
ST_PRODUCTION bValid dwCurrentTime dwProductionTime
SequenceNumber stCheckTime dwLastTime dwMaxTime dwMinTime dwRPI wOverRun wUnderRun dwCurrentTime
X = supported
— = not supported
UDINT
UDINT
UDINT
STRUCT
UDINT
UDINT
UDINT
UDINT
UINT
UINT
UDINT
Type
STRUCT X
WORD
GET SET
—
Value
0: data of the struct production is not valid
1: data of the struct production is valid
(Internal Use—number of ticks before next production)
(Internal Use—number of ticks between production)
Number of the dwquence in the production
(Internal Use)
Maximum time between 2 productions
Minimum time between 2 productions
API of the connection
Number of times the production was too long
Number of times the production was too short
(Internal Use)
31008211 09/2020
189
CIP objects
ID (hex)
08
09
Description
ST_CONSUMPTION bValid dwCurrentTime UDINT dwConsumptionTime UDINT
SequenceNumber stCheckTime dwLastTime dwMaxTime dwMinTime dwRPI wOverRun
UDINT
STRUCT
UDINT
UDINT wUnderRun dwCurrentTime
Connection Entry List byGeneralStatus byReserved
Extended Status
X = supported
— = not supported
Type
STRUCT X
WORD
GET SET
—
Value
0: data of the struct consumption is not valid
1: data of the struct consumption is valid
(Internal Use—number of ticks before timeout)
(Internal Use—number of ticks of the timeout)
Number of the sequence in the consumption
UDINT
UDINT
UINT
UINT
UDINT
STRUCT X
BYTE
BYTE
WORD
—
(Internal Use)
Maximum time between 2 consumptions
Minimum time between 2 consumptions
API of the connection
Number of times the consumption was too long
Number of times the consumption was too short
(Internal Use)
Status of the CCO object. See Status descriptions, below.
190
31008211 09/2020
CIP objects
Scanner Status
Scanner status values include the followng:
Extended Explanation
0
33
53
54
Status
58
65
Description
OK
Timeout
IDLE
Connection established
0xFB
0xFB
0xFB
Not connected (TCP) 0xFE
Not connected (CIP) 0xFB
0xFB
0xFB
0
0
CIP
Status
0
0xFB
0
0
0
0xFB0B
0xFB08
0xFB09
0xFB0A
0xFB01
0xFB02
0xFB03
68
70
77
0xFB
0xFB
Connection establishing
0xFB
0xFB
0xD0
0xD0
Not connected (EPIC) 0xFD
0xFD
Scanner stopped
0xFD
0
0xFB04
0xFB05
0xFB06
0xFB07
0x0001
0x0002
0
The I/O data are correctly exchanged.
Timeout detected on consumption.
An IDLE notification is received.
The connection is established, but I/O is not yet consumed.
Impossible to start the production.
Impossible to start the consumption.
Not enough resources to manage the connection.
Error on TCP connection.
Timeout for Fw_Open response.
Bad format of the Fw_Open response (so addr).
Bad parameters in the Fw_Open response (OT
Net Par).
Bad parameters in the Fw_Open response (TO
Net Par).
Fw_Open respons asks for port number other than
2222.
Error joining the UDP multicast group.
Optimization error / unknown MAC Address.
Connection is closed.
Connection is pending.
Error code in register session response.
Error code in the frame.
Encapsulation session un-registered.
Connection is stopped.
31008211 09/2020
191
CIP objects
Services
The CIP Scanner Diagnostic object performs the following services upon the listed object types:
Notes ID (hex) Description
01 Get_Attributes_All
Class
X
Instance
X
61 Get_Output — X
62 Get_Input —
63 Set_DiagCounters —
X = supported
— = not supported
X
X
0
2
Returns the status and values of the output:
Offset Type Description
UINT
USINT[0...409]
Status
Output Data
0
2
Returns the status and values of the input:
Offset Type Description
UINT
USINT[0...409]
Status
Input Data
Sets the value of the structure ST_DIAG_CNT to 0.
192
31008211 09/2020
TCP/IP Interface Object
Overview
The Identity CIP object consists of the attributes and services described below.
Attributes
The TCP/IP Interface CIP object consists of the following attributes:
1. Class attributes:
ID (hex)
01
Description
Revision
02 Max Instance
X = supported
— = not supported
GET
X
X
2. Instance attributes:
ID (hex) Description
01
02
Status
Configuration Capability
03
04
Configuration Control
Physical Link Object
Path Size
Path
Interface Configuration 05
IP Address
Network Mask
Gateway Address
Name Server
Name Server 2
Domain Name
06 Host Name
X = supported
— = not supported
Type GET SET Value
DWORD X
DWORD X
—
— always = 0x01
0x01 = from BootP
0x11 = from flash
0x00 = other
DWORD X X 0x01 = out-of-box default
STRUCT X
UINT
Padded
EPATH
STRUCT X
—
X 0x00 = out-of-box default
UDINT
UDINT
UDINT
UDINT
UDINT
STRING
STRING X —
SET
—
—
31008211 09/2020
CIP objects
193
CIP objects
Services
The CIP TCP/IP Interface object performs the following services upon the listed object types:
ID (hex)
01
0E
05
Description
Get_Attributes_All
Get_Attributes_Single
Get_Attributes_Single
X = supported
— = not supported
Class Instance
X X
X
—
X
X
Notes
—
—
—