Configuration

UPS Settings

Start up Settings

Use the display interface to configure these settings at initial start up. The UPS will prompt for a response to each setting, if no response is given, the default setting will be used.

NOTE: The UPS will not turn on until all of these settings have been configured.

Function

Language

Output

Voltage

Input

Power

Quality

Menu

Type

Date

Factory Default

English

120 Vac

Good

Standard

UPS manufacture date

+ 90 days

Options

•English

•French

•German

•Spanish

•Italian

•Portuguese

•Japanese

•100

•110

•120

•127

•Good

•Fair

•Poor

Description

The language for the display interface.

Language options will vary by model and firmware version.

Set the output voltage while the UPS is in Standby mode.

Select the desired utility power input quality.

•Good: The UPS will go on battery power more often to provide the cleanest power supply to the connected equipment.

•Fair: The UPS will tolerate some voltage fluctuations.

•Poor: The UPS will tolerate more voltage fluctuations and will go on battery power less often.

If unsure of the local power quality, or the connected equipment is sensitive to voltage fluctuations set the sensitivity level to Good, using the Advanced menu.

Standard or

Advanced

The advanced menus include all parameters. The Standard menus display a limited set of menus and options.

mm-yyyy Enter the current date.

General settings

Configure these settings at any time, using the display interface, PowerChute ™ software, or a network management card.

Function

High Transfer

Point

Low Transfer

Point

Green Mode

Factory

Default

Options

100 V: 108 Vac 108-114 Vac

110 V: 116 Vac 116-125 Vac

120 V: 127 Vac 127-136 Vac

127 V: 134 Vac 134-143 Vac

100 V: 92 Vac 86-92 Vac

110 V: 98 Vac 89-98 Vac

120 V: 106 Vac 97-106 Vac

127 V: 112 Vac 103-112 Vac

Description

To avoid unnecessary battery usage, set the transfer point higher if the utility voltage is chronically high and the connected equipment is known to work under this condition. The power quality setting will automatically change this setting.

Note: Use the Advanced Menus to configure this setting.

Set the transfer point lower if the utility voltage is chronically low and the connected equipment can tolerate this condition.The

P OWER Q UALITY

Note:

setting will automatically change this setting.

Use the Advanced Menus to configure this setting.

If the UPS input voltage is between the high transfer point and the lower transfer point, the UPS will operate in Green Mode . Configure this setting using the Advanced menus.

Smart-UPS SMT750X93/SMT1500X93/SMT1500RMX93/SMX3000RMX93 19