Changing (loading) jobs. Mitsubishi Electric Vision Sensor Basic Course
Reklaam
Reklaam
Changing (loading) jobs
This section describes how to load the job file "3School_Vision.job".
The number "3" prefixed to the file name is the ID number. By setting this ID number to "Command" (D2000) of the input word block, the job ("3School_Vision") can be loaded.
Operating procedure
1.
Enter "D2000" for the device name of the device/buffer memory batch monitor of GX
Works3.
2.
Click the [Start Monitoring] button.
Input!
Click!
5
3.
Enter "3" as the current value of D2000.
Input!
On!
Input!
4.
Enter "D1000" for the device name.
5.
Turn on "Set Offline" (D1000.7) of the control bit block to set the vision sensor to offline.
5 TRAINING 2 COMMUNICATIONS BETWEEN A PROGRAMMABLE CONTROLLER AND VISION SENSOR
5.5 Checking Operations
125
Check!
6.
Check that the online/offline status of In-Sight
Explorer is as shown on the left.
If "Comms Online?" is displayed, the
In-Sight vision system has been set to online mode by the EasyBuilder user interface, but the vision system remains offline due to the communication protocol (such as
ProfiNET, EtherNet/IP, native mode).
7.
Turn on "Execute Command" (D1000.4) of the control bit block to load a job.
On!
8.
When loading of the job is completed,
"Command Completed" (D1002.D) of the status bit block is turned on.
9.
When "Command Completed" (D1002.D) turns on, turn off "Execute Command" (D1000.4) and
"Set Offline" (D1000.7).
On!
To load a job, the file name of the job must begin with an ID number.
When loading a job, set the vision sensor to offline.
126 5 TRAINING 2 COMMUNICATIONS BETWEEN A PROGRAMMABLE CONTROLLER AND VISION SENSOR
5.5 Checking Operations