Identification

TECHNICAL DATA

The 460 is a power thyristor unit designed to control an industral single-phase load with a high current requirement at start-up using thyristors.

!

Attention !

It is the user's responsibility to ensure that the nominal values of the thyristor unit are compatible with the conditions of installation and operation before commissioning the thyristor unit.

Power

Nominal current

Nominal line to line voltage

Supply frequency

Dissipated power

Cooling

Fan

Load

Residual current

15 A to 150 A

120 Vac to 500 Vac (+10%,-15%)

Inhibition below 70% of the nominal voltage; response time <10 ms; automatic reset 2 s after return to 85 % of the value

50 or 60 Hz (

±

2 Hz)

1.3 W (approximately) per ampere

Permanent fan cooling above 100 A nominal

Consumption 23 VA

Powered by the electronics supply voltage

Resistive with high temperature coefficient or inductive

(transformer primary circuit or inductor)

In the OFF state, typically below 30 mA

Environment

Operating temperature

Altitude

Storage temperature

Protection

Thyristor protection

External cabling

Atmosphere

Humidity

Pollution

0

°

C to +50

°

C in vertical position

2000 m maximum

-10

°

C to +70

°

C

IP00 (can be opened without tools according to IEC 592)

Internal high speed fuse fuse blown indicator light.

(external fuse for 150 A model 464)

Varistor and RC snubber

To be performed according to the standards IEC 364

Non-explosive, non-corrosive and non-conducting

RH of 5% to 95% without condensation

Degree 2 admissible, defined by IEC 664

1-6

Identification

TECHNICAL DATA

The 460 is a power thyristor unit designed to control an industral single-phase load with a high current requirement at start-up using thyristors.

!

Attention !

It is the user's responsibility to ensure that the nominal values of the thyristor unit are compatible with the conditions of installation and operation before commissioning the thyristor unit.

Power

Nominal current

Nominal line to line voltage

Supply frequency

Dissipated power

Cooling

Fan

Load

Residual current

15 A to 150 A

120 Vac to 500 Vac (+10%,-15%)

Inhibition below 70% of the nominal voltage; response time <10 ms; automatic reset 2 s after return to 85 % of the value

50 or 60 Hz (

±

2 Hz)

1.3 W (approximately) per ampere

Permanent fan cooling above 100 A nominal

Consumption 23 VA

Powered by the electronics supply voltage

Resistive with high temperature coefficient or inductive

(transformer primary circuit or inductor)

In the OFF state, typically below 30 mA

Environment

Operating temperature

Altitude

Storage temperature

Protection

Thyristor protection

External cabling

Atmosphere

Humidity

Pollution

0

°

C to +50

°

C in vertical position

2000 m maximum

-10

°

C to +70

°

C

IP00 (can be opened without tools according to IEC 592)

Internal high speed fuse fuse blown indicator light.

(external fuse for 150 A model 464)

Varistor and RC snubber

To be performed according to the standards IEC 364

Non-explosive, non-corrosive and non-conducting

RH of 5% to 95% without condensation

Degree 2 admissible, defined by IEC 664

460 User Manual 1-6 460 User Manual

Identification

Control

Power supply

Signal type

Setpoint

Input impedance

Manual control

Thyristor firing modes

Delayed thyristor firing

Enable / Inhibition

Diagnostics

Feedback type

Configuration

Connection

Connection of the electronics power supply to the user terminal block

Consumption: 7 VA (non-fan-cooled unit) 30 VA (fan-cooled unit)

Analogue

Voltage: 0-5 V; 1-5 V or 0-10 V

Current: 0-5 mA ; 0-10 mA ; 0-20 mA or 4-20 mA

Voltage:

100 k

Current:

250

or 1000

External potentiometer 10 k

The following can be reconfigured by the user:

• Phase angle

• Single firing (burst firing with a firing or non-firing cycle)

Fast cycle

(typical modulation time at 50 % power : 0.8 s)

Slow cycle

(typical modulation time at 50 % power : 8 s)

Fast cycle with adjustable soft start between

0 and 250 ms (with or without soft end)

Slow cycle with adjustable soft start between

0 and 250 ms (with or without soft end)

For inductive loads the delayed firing of the first alternation of the burst mode firing (without soft operation)

eliminates transient currents

Using external switch or external voltage on the control terminal block.

Response time: enable 2 s; inhibition < 25 ms

Connector for diagnostic unit used to adjust and control the thyristor unit using 20 test signals

Squared load current or squared voltage control.

Supply variation compensation.

Shielded cable connected to ground at both extremities.

0.5 mm

2 to 2.5 mm 2 wires

Tightening 0.7 N.m

The control terminals are insulated from the power and the load circuit.

460 User Manual 1-7 460 User Manual

Identification

Control

Power supply

Signal type

Setpoint

Input impedance

Manual control

Thyristor firing modes

Delayed thyristor firing

Enable / Inhibition

Diagnostics

Feedback type

Configuration

Connection

Connection of the electronics power supply to the user terminal block

Consumption: 7 VA (non-fan-cooled unit) 30 VA (fan-cooled unit)

Analogue

Voltage: 0-5 V; 1-5 V or 0-10 V

Current: 0-5 mA ; 0-10 mA ; 0-20 mA or 4-20 mA

Voltage:

100 k

Current:

250

or 1000

External potentiometer 10 k

The following can be reconfigured by the user:

• Phase angle

• Single firing (burst firing with a firing or non-firing cycle)

Fast cycle

(typical modulation time at 50 % power : 0.8 s)

Slow cycle

(typical modulation time at 50 % power : 8 s)

Fast cycle with adjustable soft start between

0 and 250 ms (with or without soft end)

Slow cycle with adjustable soft start between

0 and 250 ms (with or without soft end)

For inductive loads the delayed firing of the first alternation of the burst mode firing (without soft operation)

eliminates transient currents

Using external switch or external voltage on the control terminal block.

Response time: enable 2 s; inhibition < 25 ms

Connector for diagnostic unit used to adjust and control the thyristor unit using 20 test signals

Squared load current or squared voltage control.

Supply variation compensation.

Shielded cable connected to ground at both extremities.

0.5 mm

2 to 2.5 mm 2 wires

Tightening 0.7 N.m

The control terminals are insulated from the power and the load circuit.

1-7

Identification

Retransmissions

Signal outputs Retransmission output on the control terminal block.

• Instantaneous load current.

The full wave rectified signal (0 to 5 V) proportional to the real load current image.

• Instantaneous load voltage.

The full wave rectified signal (4.3 V in full firing).

Current limit

Linear limit

Threshold limit

Proportional load current limit

(0 % to 110 % of the nominal current).

Adjustment using potentiometer on front fascia.

Maximum load current limit.

(0 % to 110 % of the nominal current).

Adjustment possible using an external potentiometer or an external voltage.

Partial load failure detection

Alarm

Test

Signalling

"Slave firing" output

20% current decrease detection.

Adjustment on front fascia using "Adjust/Seuil" potentiometer.

Using front fascia "Test" push button.

"Load Fail" indicator light on the front fascia.

Alarm relay switch open in alarm status (in standard version)

Switch closed in alarm status (option 83)

• Logic signal (10 Vdc; 10 mA max)

available on the control terminal block.

!

Attention !

Due to the continual improvement of products, Eurotherm may be required to modify specifications without prior notice. For any further information and in the event of doubt, contact your Eurotherm Office.

Identification

Retransmissions

Signal outputs Retransmission output on the control terminal block.

• Instantaneous load current.

The full wave rectified signal (0 to 5 V) proportional to the real load current image.

• Instantaneous load voltage.

Current limit

Linear limit

Threshold limit

Proportional load current limit

(0 % to 110 % of the nominal current).

Adjustment using potentiometer on front fascia.

Maximum load current limit.

(0 % to 110 % of the nominal current).

Adjustment possible using an external potentiometer or an external voltage.

Partial load failure detection

Alarm

Test

Signalling

"Slave firing" output

20% current decrease detection.

Adjustment on front fascia using "Adjust/Seuil" potentiometer.

Using front fascia "Test" push button.

"Load Fail" indicator light on the front fascia.

Alarm relay switch open in alarm status (in standard version)

Switch closed in alarm status (option 83)

• Logic signal (10 Vdc; 10 mA max)

available on the control terminal block.

!

Attention !