- No category
advertisement
Model 7600 Controller Users Manual
Revision B
IMPORTANT! Figure 2.3 CAL MODE menus are only visible if the Input Data From: menu, described in section 2.2.7, is set for Sensor.
Figure 2.3 illustrates how the CAL MODE menus function to allow push button calibration of zero and span values. The correct zero and span set-point values must be entered in order for the to make the correct adjustments. This feature should be utilized only when there are no other zero/span controls within the monitoring system since it is inappropriate to calibrate the same signal at more than one point. Therefore, if calibration is to be performed at another transmitter or monitoring device, the CAL
MODE feature should not be used. Unintentional calibrations are reset by the UNITY
GAIN menu. Unity gain sets zero offset to 0 and span gain to 1.
A/D Cnts = 905
Edit = Cal Mode
Press Edit
0 PCTLEL
Edit = Cal Zero
Press Edit
Reading =Zero
Cal Set-Point
Press Dn
Press Up/Dn
Edit = Unity
Resets Cal Mode
Press Edit
51 PCTLEL
Edit = Cal Span
Press Edit
Offset = 0
Gain = 1
Reading =Span
Cal Set-Point
Press Dn Press Func.
0.000=Cal Zero
50.0=Cal Span
Returns to
Normal Mode*
Figure 2.3
The bottom line of the top left menu in Figure 2.3 allows access to the calibration menus by pressing EDIT. EDIT brings up the CAL ZERO display at the top right of Figure 2.3.
The top line displays the live channel value in engineering units and the bottom line states: EDIT = ZERO CAL. It is important to understand that pressing EDIT now will force this channel’s reading to match the zero set-point value previously entered.
Therefore, the sensor should have the appropriate stimulus to provide a response approximating the zero set-point. Pressing the Up or Down buttons from the CAL ZERO menu brings up the CAL SPAN menu. Pressing EDIT will cause a span adjustment forcing the reading to match the span set-point value previously entered. Again, the sensor should have the appropriate stimulus to provide a response approximating the span set-point. For example, if an LEL combustible sensor is to be spanned with 50% LEL
Scott Safety 6 087-0018 Rev B
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 6 SECTION
- 6 IMPORTANT SAFETY ISSUES
- 6 GENERAL DESCRIPTION
- 7 SPECIFICATIONS
- 7 DC POWER SUPPLY REQUIREMENTS
- 7 60 WATT AC – 24VDC POWER SUPPLY
- 8 AMBIENT TEMPERATURE RANGE
- 8 HUMIDITY RANGE
- 8 ALTITUDE
- 8 HOUSINGS
- 8 NON-INTRUSIVE MAGNETIC KEYPAD
- 8 APPROVALS
- 8 SECTION
- 8 BASIC OPERATION
- 9 SYSTEM CONFIGURATION
- 9 CHANGING VARIABLES USING THE KEYPAD
- 9 CHANNEL CONFIGURATION MENUS
- 11 CAL MODE
- 12 DECIMAL POINT RESOLUTION / ASCII FIELDS
- 12 MEASUREMENT RANGE
- 13 ALARM 1 / ALARM 2 / HORN RELAY SET-UP
- 13 ALARM 3 / FAIL ALARM
- 14 RANGE OF A-D COUNTS
- 14 MODBUS, SENSOR OR ANALOG INPUTS?
- 15 COPY DATA TO?
- 15 SYSTEM CONFIGURATION MENUS
- 15 AUTHORIZATION MODE
- 16 ACTIVATING CHANNELS / SCAN TIMER
- 16 ALARM 2 RELAY ACKNOWLEDGE
- 16 ALARM SCAN PRIORITY
- 16 FAIL SAFE / NORMAL ALARMS
- 17 MASTER / SLAVE SERIAL PORT MENUS
- 17 SECTION
- 17 MAIN I/O INTERFACE PCB
- 18 OPTIONAL ANALOG INPUT PCB
- 21 OPTIONAL DISCRETE RELAY PCB
- 22 OPTIONAL CATALYTIC BEAD SENSOR INPUT BOARD
- 22 CATALYTIC BEAD SENSOR INITIAL SETUP
- 25 OPTIONAL 4-20mA ANALOG OUTPUT BOARD
- 26 OPTIONAL 24VDC 60 WATT POWER SUPPLY
- 27 SECTION
- 27 SYSTEM DIAGNOSTICS
- 29 SECTION
- 29 MODBUS RS-485 PORTS
- 30 MODBUS SLAVE REGISTER LOCATIONS
- 34 SECTION
- 34 093-0330 PANEL / RACK MOUNT ENCLOSURE
- 35 093-0282 NEMA 4X WALL MOUNT ENCLOSURE
- 37 093-0284 NEMA 7 EXPLOSION-PROOF WALL MOUNT ENCLOSURE