1 Safety Precautions. BeiJer T7BR
Add to My manuals29 Pages
The Beijer T7BR operator panel delivers user-friendly visuals with a dynamic indication, time channels, alarm handling, and recipe management. It connects to PLCs, servos, and drives and features a built-in Ethernet connection. The object-oriented configuration simplifies use and setup, and the included iX Developer software enables project transfer and storage on the device itself.
advertisement
Safety Precautions
1 Safety Precautions
•
•
Both the installer and the owner and/or operator of the operator panel must read and understand this installation manual.
1.1 General
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Read the safety precautions carefully.
Check the delivery for transportation damage. If damage is found, notify the supplier as soon as possible.
The supplier is not responsible for modified, altered or reconstructed equipment.
Use only parts and accessories manufactured according to specifications of the supplier.
Read the installation and operating instructions carefully before installing, using or repairing the operator panel.
Never allow fluids, metal filings or wiring debris to enter any openings in the operator panel. This may cause fire or electrical shock.
Only qualified personnel may operate the operator panel.
Storing the operator panel where the temperature is lower/higher than recommended in this manual can cause the LCD display liquid to congeal/become isotopic.
The LCD display liquid contains a powerful irritant. In case of skin contact, wash immediately with plenty of water. In case of eye contact, hold the eye open, flush with plenty of water and get medical attention.
The figures in this manual serves an illustrative purpose. Because of the many variables associated with any particular installation, the supplier cannot assume responsibility for actual use based on the figures.
The supplier neither guarantees that the operator panel is suitable for your particular application, nor assumes responsibility for your product design, installation or operation.
It is recommended to turn on and shut down the operator panel at least once before installing any components/cards or before connecting the operator panel to external devices, like for example serial devices.
This operator panel is certified to operate in a Class I, Division 2, Group A, B,
C and D hazardous environment. The operator panel must be installed and operated as described in this document to meet this certification.
Observe precautions for handling electrostatic discharge sensitive devices.
1.2 UL, cUL, ATEX, and IECEx
Installation
This equipment is suitable for use in Class 2 non-hazardous locations only.
[Combinations of equipment in your system are subject to investigation by the local authority having jurisdiction at the time of installation].
All devices have to be supplied by a Class 2 power supply.
Beijer Electronics, MAEN185
4
Safety Precautions
Warning:
Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous
AVANT DE DECONNECTER L’EQUIPEMENT, COUPER LE COURANT
OUS’ASSURER QUE L‘EMPLACEMENT EST DESIGNE NON DANGEREUX.
Warning:
Battery may explode if mistreated. Do not recharge, disassemble or dispose of in fire.
This product contains a BR2330A battery that is not user replaceable.
LA BATTERIE PEUT EXPLOSER EN CAS DE MAUVAISE MANIPULATION.
NE LA RECHARGEZ PAS, NE LA DÉMONTEZ PAS ET NE LA JETEZ
PAS DANS LE FEU.
CE PRODUIT CONTIENT UNE PILE BR2330A QUI NE PEUT PAS ÊTRE
REMPLACÉE PAR L'UTILISATEUR.
•
•
Use minimum 75°C copper conductors only.
To make wiring connections to the power supply connector, follow the table with cable and torque specifications below:
Terminal Block Connector
Phoenix Contact Part No. 1757022
Wire Size
14–20 AWG
(2.08–0.52 mm
2
)
TQ Lb.In.
5–7
Warning:
Do not open when an explosive atmosphere is present.
N'OUVREZ PAS SI UNE ATMOSPHÈRE EXPLOSIVE EST PRÉSENTE.
Warning:
Explosion hazard! Do not disconnect while circuit is live unless the area is known to be non hazardous.
RISQUE D'EXPLOSION ! NE DÉBRANCHEZ PAS LORSQUE LE CIRCUIT EST
SOUS TENSION SAUF SI LA ZONE EST CONNUE POUR ÊTRE
NON DANGEREUSE.
Caution:
This equipment is tested as a component and is to be installed inside an enclosure rated IP54 minimum if used in an ATEX/IECEx Zone 2 area. However, since the unit is
IP66 rated it can be deployed in an IP66 ATEX/IECEx Zone 2 area if enclosed in an IP66 rated enclosure.
CET ÉQUIPEMENT EST TESTÉ EN TANT QUE COMPOSANT ET DOIT ÊTRE
INSTALLÉ DANS UN BOÎTIER AVEC INDICE DE PROTECTION IP66 MINIMUM.
Caution:
Temperature code T4 IEC/EN 60079-0 (2012) and IEC/EN 60079-15 (2010).
CODES DE TEMPÉRATURE T4 IEC/EN 60079-0 (2012) ET IEC/EN 60079-15 (2010).
Beijer Electronics, MAEN185
5
advertisement
Related manuals
advertisement
Table of contents
- 4 1 Safety Precautions
- 4 General
- 4 UL, cUL, ATEX, and IECEx Installation
- 6 High Potential Testing
- 6 During Installation
- 6 During Use
- 6 Service and Maintenance
- 7 Dismantling and Scrapping
- 8 2 Installation
- 8 Space Requirements
- 9 Installation Process
- 11 Connections to the Controller
- 12 Hazardous Location Installation
- 12 Other Connections and Peripherals
- 13 3 Technical Data
- 15 4 Chemical Resistance
- 15 Metal Casing
- 16 Touch Screen and Overlay Material
- 16 Autoflex EB
- 17 Touch Screen Surface
- 17 Touch Screen Protector
- 18 Terminal to Panel Gasket
- 19 5 Operator Panel Drawings
- 19 Connectors
- 19 Communication Ports
- 20 T7BR Outline
- 21 6 Additional Installation Tips
- 21 Grounding the operator panel
- 22 Ethernet Connection in the Operator Panel
- 24 To Achieve Better EMC Protection
- 25 Ambient Temperature
- 26 Safety
- 27 Galvanic Isolation
- 28 Cable and Bus Termination RS
- 28 COM Port Common-Mode Voltage