Sensaphone STATIONSitter Manual

Figure 4: Float positions for a drain application

Float Switch Wiring for Filling the Well

In a Fill application, the Lag and All-Off floats would change position as shown below:

92

Figure 5: Float positions for a fill application

In this case, the pumps are attempting to keep the well full. When the well is full, all three floats are closed. If the level drops below the Lead float, then the first pump will turn on. If the level rises above the All-Off float then the pump will turn off. If the level continues to fall below the Lag float, then the 2nd pump will turn on. Both pumps will remain on until the All-Off float closes.