Excel 15 W7760C Plant Controller System Engineering Guide

Add to My manuals
52 Pages

advertisement

Excel 15 W7760C Plant Controller System Engineering Guide | Manualzz

EXCEL 15 W7760C PLANT CONTROLLER

INTRODUCTION

Description of Devices

The Excel 15 W7760C Plant Controller is a device that can be used to monitor and control HVAC equipment and other miscellaneous loads using L protocol on an Echelon L

ON

ON

W

T

ALK

ORKS

communications

network. See Fig. 1.

The W7760C Plant Controller communicates via the 78 kilo bits per second (kbps) L

ON

W

ORKS

network, using a Free

Topology Transceiver (FTT). The W7760C is compatible with the Excel 15 W7760A Building Manager, the S7760A

Command Display, individual Excel 10 Controllers and

T7300F/Q7300H Series 2000 Commercial Thermostats and

Communicating Subbases. The W7760C monitors and controls both local and remote controller points.

The W7760C also supports configurable control loops for a wide variety of applications.(Each of the following control strategies can be configured with a combination of features, up to the maximum number stated for each type of loop.)

— Scheduling (from a W7760A Building Manager).

— Demand Limit Control (from a W7760A Building Manager).

— Time-of-Day Bypass.

— Setpoint Reset.

— Adaptive Intelligent Recovery™.

— Sequencer.

— Lead/Lag.

— Analog Limit.

— Setpoint Override.

— Setpoint Alarming.

— Start/stop loops (eight maximum). Start/stop loops are used to turn equipment on and off based on a Time Of Day

(TOD) schedule or a Demand Limit Control (DLC) situation.

— General Purpose Configurable Proportional Integral

Derivative (PID) Control Loops (ten maximum). Modulating or staged output (up to four stages per sequencer). Built-in auxiliary output to coordinate pumps or fans.

— If/Then/Else Logic Loops (32 maximum).

— Math Functions: MIN, MAX, AVG, SUM, SUB, SQRT, MUL,

DIV, ENTHALPY (36 maximum).

The W7760C is used in conjunction with the following devices:

— Excel 15 W7760A Building Manager.

— Excel 15 S7760A Command Display.

— Excel 10 W7751B,D,F,H VAV II Controllers

— Excel 10 W7750A,B,C Constant Volume AHU Controller.

— Excel 10 W7753A Unit Ventilator Controller.

— Excel 10 W7761A Remote Input/Output (RIO) Device.

— T7300F/Q7300H Series 2000 Commercial Thermostat/

Communicating Subbase.

— Q7760A Serial L

ON

T

ALK

Adapter (SLTA).

— Q7740A,B FTT Repeater (2-way and 4-way).

— 209541B FTT Termination Module.

NOTEBOOK PC

BUILDING MANAGER

1 4 8 12 16

EXCEL 15

W7760A

PLANT

CONTROLLER

EXCEL 15

W7760C

EXCEL 10

UV

T7770 OR T7560A,B

WALL MODULE

MODEM

EIA-232

SERIAL

PORT

SLTA

17 23 30 31 37 44

S7760

L

ON

W

ORKS

BUS

T7300F/

Q7300H

EXCEL 10

RI0

Back Select

EXCEL 10

VAVII

Q7740A

2-WAY

REPEATER

EXCEL 10

VAVII

PLANT

CONTROLLER

EXCEL 15

W7760C

BUILDING MANAGER

1 4 8 12 16

EXCEL 15

W7760A

EXCEL 10 VAVII

EXCEL 10

UV

T7770 OR T7560A,B

WALL MODULE

1 2 3

MODEM

EIA-232

SERIAL

PORT

SLTA

17 23 30 31 37 44

S7760

L

ON

W

ORKS

BUS

T7300F/Q7300H

Back Select

Fig. 1. Typical system overview.

M14508

74-3079 2

The T7770 or T7560 direct-wired Wall Modules are used in conjunction with Excel 10 W7751, W7750 and W7753

Controllers.

EXCEL 15 W7760C PLANT CONTROLLER

Control Application

Fig. 2 shows a typical W7760C control application.

EXHAUST

AIR

EXHAUST AIR DAMPER

NC

NO

EXHAUST

FAN

OUTSIDE

AIR

NC

MIXED

AIR

TEMPERATURE

T

+

RETURN

FAN

-

HEATING

VALVE

COOLING

VALVE

FAN

ON

H

RETURN

AIR

HUMIDITY

T

RETURN

AIR

TEMPERATURE

RETURN

AIR

VARIABLE

SPEED

DRIVE

P T

FAN

SPEED

HUMIDITY

VALVE

DUCT

STATIC

DISCHARGE

AIR

TEMPERATURE

FAN

STATUS

1

1

DO

3 1

1&2

32

COM 2

DO

33

3

DO

34

3&4

35

COM 4

DO

36

5

DO

37

5&6

38

COM 6

DO

39

7

DO

40

7&8

41

COM 8

DO

42

20

43

VDC

GND

44

2

45

24VAC

46

COM

47

24VAC

48

LINE

E

49

GND 1

AO

50

GND

51

2

AO

52

3

AO

53

GND

54

4

AO

55

5

AO

56

GND

57

6

AO

58

TRIAC EQUIVALENT CIRCUITS

HONEYWELL

W7760C

PLANT

CONTROLLER

1

DO

3 1

COM

1&2

32

DI

1

1

2

GND

3

DI

2

4

DI

3

5

GND

6

DI

4

7

DI

5

8

GND

9

DI

6

10

DI

7

11

GND

12

DI

8

13 14

EBUS

1 2

2

DO

33

1 CONNECT EACH D0 COMMON TO EITHER TERMINALS

(45, 46) FOR LOW-SIDE SWITCHING OR

TERMINALS (47, 48) FOR HIGH-SIDE SWITCHING.

2 EACH REPRESENTS TWO CONDUCTORS.

15 16

EBUS

1 2

17

AI

1

18

GND

19

AI

2

20

AI

3

21

GND

22

AI

4

23

AI

5

24

GND

25

AI

6

26

AI

7

27

GND

28

AI

8

29

GND

30

GND

DUCT

STATIC

PRESSURE

NETWORK

OUTSIDE AIR

TEMPERATURE

T

ROOM

TEMPERATURE

M17292A

Fig. 2. Typical air handling unit control application.

Control Provided

The W7760C functions to monitor and control HVAC equipment and other miscellaneous loads using a L

ON

W

ORKS network.

Product Name

The Excel 15 W7760C Plant Controller is available in one model:

— The W7760C2009 Plant Controller.

3 74-3079

EXCEL 15 W7760C PLANT CONTROLLER

Organization of Manual

This manual is divided into four basic sections:

1. Introduction: Provides an overview of the W7760C, discusses any related devices, lists additional literature and furnishes a glossary of abbreviations and definitions.

2. Construction: Describes controller hardware.

3. Application Steps: A step-by-step procedure that provides the necessary information to plan and lay out the

W7760C application and accurately order materials

4. Appendices: Provide information that allows a configuration to start using Honeywells Excel L

ON

S

PEC

PC software.

The organization of the manual assumes a project is being engineered from start to finish. If an operator is adding to, or is changing an existing system, the Table of Contents can provide the relevant information.

Applicable Literature

The following list of documents contains information related to the Excel 15 W7760C Plant Controller and the EXCEL 5000

OPEN SYSTEM.

Form No.

Title

74-2976

74-2977

Excel L

ON

S

PEC

™ Specification Data

Excel L

ON

S

PEC

Software Release Bulletin

Excel L

ON

S

PEC

Help is internal to ZL7760A software

74-3069

74-3090

74-2865

74-3123

74-3080

95-7611

74-3079

74-2967

95-7565

Excel L

ON

S

TATION

™ Specification Data

Excel L

ON

S

TATION

Software Release Bulletin

Excel L

ON

S

TATION

Help is internal to ZL7761A software

L

ON

W

ORKS

Bus Wiring Guidelines

Light Commercial Building Solution System

Communication Guide

Excel 15 W7760C Plant Controller Specification

Data

Excel 15 W7760C Plant Controller Installation

Instructions and Checkout and Test

Excel 15 W7760C Plant Controller System

Engineering

Excel 15 W7760A Building Manager

Specification Data

Excel 15 W7760A Building Manager Installation

74-2969

74-2970

74-2972

95-7561

74-2974

74-2942

74-2953

95-7504

95-7553

Instructions and Checkout and Test

Excel 15 W7760A Building Manager System

Engineering

Excel 15 System Integration Manual

Excel 15 S7760A Command Display

Specification Data

Excel 15 S7760A Command Display Installation

Instruction

Excel 15 S7760A Command Display User Guide

Excel 10 W7751B,D,F VAV II Controllers

Specification Data

Excel 10 W7751H Smart VAV Actuator

Specification Data

Excel 10 W7751B,D,F VAV II Controllers

Installation Instructions and Checkout

Excel 10 W7751H Smart VAV Actuator

Installation Instructions and Checkout

74-2949

74-2956

95-7521

74-2958

74-2962

95-7520

74-2964

74-2698

95-7539

74-2699

63-1281

63-4366

74-2697

95-7538

74-3097

95-7620

74-2954

95-7511

74-3067

95-7613

74-2858

95-7555

95-7554

62-0155

62-0125

63-4365

Excel 10 W7751B,D,F,H VAV II Controllers

System Engineering

Excel 10 W7750A,B,C CVAHU Controller

Specification Data

Excel 10 W7750A,B,C CVAHU Controller

Installation Instructions and Checkout and Test

Excel 10 W7750A,B,C CVAHU Controller System

Engineering

Excel 10 W7753A Unit Ventilator Controller

Specification Data

Excel 10 W7753A Unit Ventilator Controller

Installation Instructions and Checkout and Test

Excel 10 W7753A Unit Ventilator Controller

System Engineering

Excel 10 W7761A RIO Device Specification Data

Excel 10 W7761A RIO Device Installation

Instructions and Checkout and Test

Excel 10 W7761A RIO Device System

Engineering

T7300F/Q7300H Series 2000 Commercial

Thermostats and Communicating Subbase

Specification Data

Q7300H Series 2000 Commercial Thermostat

Communicating Subbases Installation

Instructions

T7300F Series 2000 Commercial Microelectronic

Conventional or Heat Pump Thermostat

Installation Instructions

T7300F/Q7300H Series 2000 Commercial

Thermostats and Communicating Subbases

System Engineering

Q7300H Communicating Subbase System

Integration User Address Manual

Excel 10 T7770A,B,C,D,E,F,G Wall Module

Specification Data

Excel 10 T7770A,B,C,D,E,F,G Wall Module

Installation Instructions

T7560A,B Digital Wall Module Specification Data

T7560A,B Digital Wall Module Installation

Instructions

SLTA-10 Serial L

ON

T

ALK

Adapter Specification

Data

SLTA-10 Serial L

ON

T

ALK

Adapter Installation

Instructions

Q7752B PCMCIA L

ON

W

ORKS

PCC-10 Card

Specification Data

Q7752B PCMCIA L

ON

W

ORKS

PCC-10 Card

Installation Instructions

Excel 10 Q7740A,B FTT Repeaters Specification

Data

Excel 10 Q7740A,B FTT Repeaters Installation

Instructions

Excel 10 209541B Termination Module

Installation Instructions

Other Product Model Numbers

Q7760A Serial Adapter.

Q7740A,B FTT Repeaters.

209541B FTT Termination Module.

Refer to Table 22 in Application Step 5. Order Equipment for a complete listing of all available part numbers.

74-3079 4

EXCEL 15 W7760C PLANT CONTROLLER

Agency Listings

Table 1 provides information on agency listings for Excel 15 products. Be sure to always follow Local Electrical Codes.

Device

W7760C Plant Controller

Agency

UL

Table 1. Agency Listings.

Comments

Tested and listed under UL916 (file number E14480). NEC Class 2 rated.

cUL Listed E14480. NEC Class 2 rated.

CE Level A general Immunity per European Consortium Standards EN50081-1 (CISPR 22,

Class B) and EN 50082-1:1992 (based on Residential, Commercial, and Light Industrial).

EN 61000-4-2: IEC 1000-4-2 (IEC 801-2) Electromagnetic Discharge.

EN 50140, EN 50204: IEC 1000-4-3 (IEC 801-3) Radiated Electromagnetic Field.

EN 61000-4-4:

EN 55022:

CISPR-22:

IEC 1000-4-4 (IEC 801-4)

Electrical Fast Transient (Burst). Radiated Emissions and

Conducted Emissions:

1987 Class B.

1985.

FCC Complies with requirements in FCC Part 15 rules for subpart J Class A Computing Device.

Operation in a residential area can cause interference to radio or TV reception and require the operator to take steps necessary to correct the interference.

Abbreviations and Definitions

AHU

Air Handling Unit; the central fan system that includes the blower, heating equipment, cooling equipment, ventilation air equipment, and other related equipment.

Application

A specific Building Control function.

Binding

The process of logically connecting network variables in one node to network variable(s) in other node(s). Binding is performed by a network management node that writes the binding information into the EEPROM of each Neuron each Neuron.

involved. The binding information is saved in the network image of

Building Manager

A L

ON

M

ARK

certified device that can be used to monitor and control HVAC equipment and other miscellaneous loads in a distributed network.

Bypass

Temporary override of the scheduled occupancy state to the occupied mode. At the end of the bypass time, the control returns to the scheduled occupancy state.

CO

Carbon Monoxide. Occasionally used as a measure of indoor air quality.

CO

2

Carbon Dioxide. Often used as a measure of indoor air quality.

Command Display

A device that is used to monitor and change parameter in a L

ON

W

ORKS

HVAC application.

Continuous Trend

A type of log that starts accumulating data after configuration and continues to record data until reconfigured. After a specific number of configured samples are recorded, the data is replaced on a first-infirst out basis. This results in the most recent data being in the trend at the time of viewing or downloading.

Control Loop

A control function; A type of function in a node that includes processes, loops and programs. A node can contain one or more control loops. (In Excel

10 devices, the control loop occupies the entire node.)

COS

Change of state; COS conditions are used with schedule states such as occupied and unoccupied.

Changing from the occupied mode to the unoccupied mode is COS.

CPU

Central Processing Unit; an EXCEL 5000

SYSTEM controller module.

OPEN

cUL

Underwriters Laboratories Canada.

CVAHU

Constant Volume AHU; Refers to a type of air handler with a single-speed fan that provides a constant amount of supply air to the space it serves.

CZS

Commercial Zoning System.

DDF

Delta Degrees Fahrenheit.

D/X

Direct Expansion; Refers to a type of mechanical cooling where the refrigerant is expanded to its cold state in a heat exchanging coil that mounts in the air stream supplied to the conditioned space.

DLC

Demand Limit Control; A function that controls the maximum power demand made on the whole system by shedding some of the demand when power usage exceeds the predefined limit. Shedding requires turning off some digital output, or changing a setpoint to a more economical level.

Echelon

The company that developed the L

ON

W

ORKS

Bus and the Neuron

L

ON

W

ORKS

Bus.

chips used to communicate on the

Economizer

Refers to the mixed-air dampers that regulate the quantity of outdoor air that enters the building. In cool outdoor conditions, fresh air can be used to supplement the mechanical cooling equipment.

Because this action saves energy, the dampers are often referred to as economizer dampers.

EEPROM

Electronically Erasable Programmable Read Only

Memory; The variable storage area for saving user setpoint values and factory calibration information.

5 74-3079

EXCEL 15 W7760C PLANT CONTROLLER

EMI

Electromagnetic Interference; Electrical noise that can cause problems with communications signals.

EMS

Energy Management System; Refers to the controllers and algorithms responsible for calculating optimum operational parameters for maximum energy savings in the building.

Enthalpy

The energy content of air measured in BTUs per pound (KiloJoules per Kilogram).

EPID Control

An Enhanced Proportional Integral Derivative control algorithm that improves the PID control algorithm by compensating for system dynamics and allows faster control response rate reset. It also incorporates a sequencer, AI limit, deadband, start ramp and setpoint override.

EPROM

Erasable Programmable Read Only Memory; The firmware that contains the control algorithms for the

Excel 15 and Excel 10 Controllers.

Excel 10s

A family of application specific HVAC Controllers such as the Excel 10 CVAHU, Excel 10 RIO and the

Excel 10 UV.

Firmware

Software stored in a nonvolatile memory medium such as an EPROM.

Floating Control

Refers to Series 60 Modulating Control of a valve or damper. Floating Control utilizes one digital output to drive the actuator open, and another digital output to drive it closed.

FTT

Free Topology Transceiver.

HVAC

Heating Ventilation and Air Conditioning.

IAQ

Indoor Air Quality. Refers to the quality of the air in the conditioned space, as it relates to occupant health and comfort.

I/O

Input/Output; the physical sensors and actuators connected to a controller.

I x R

I times R or current times resistance; refers to Ohms

Law: V = I x R.

K

Degrees Kelvin.

Level IV

Refers to a classification of digital communication wire. Formerly known as UL Level IV, but not equivalent to Category IV cable. If there is any question about wire compatibility, use Honeywell-approved cables (see Step

5 Order Equipment section).

L

ON

W

ORKS

Bus

Echelons L

ON

W

ORKS

network for communication among Excel 15 Controllers, Excel 10

Controllers and T7300F/Q7300H Commercial

Thermostat/Communicating Subbases.

L

ON

W

ORKS

Bus Segment

An L

ON

W

ORKS

Bus network that contains no more than 120 total (Excel 15 W7760A,Cs,

Excel10s and T7300F/Q7300H Commercial

Thermostat/Communicating Subbases). A segment can have a repeater that allows the bus wire length to be doubled.

Mandatory Mechanisms/Objects/Network Variables

Mandatory mechanisms, object and network variables that are implemented in all of the Excel 10 devices.

NamedObject

Objects that have names are called

NamedObjects. These objects are visible on the network as functional independent entities and are accessed by name. Typical examples of NamedObjects are controllers, control loops and logic function blocks.

NEC

National Electrical Code; The body of standards for safe field-wiring practices.

NEMA

National Electrical Manufacturers Association; The standards developed by an organization of companies for safe field wiring practices.

Network Management Node

A L

ON

W

ORKS

node that is responsible for configuring the network, installing the nodes, binding the network variables between nodes and general network diagnostics.

Network Time Master

A network time master will be the only device sending out the time/date. All other network devices will use the time/date from the network time master (even if they have their own real-time clock).

Network time master is chosen/configured from

LonSpec

and remains unchanged until reconfigured, even in the event of a failure on the network time master. (The Excel 15 W7760C can not be the network time master.)

Network Time Scheduler

The network time scheduler sends out current and next state (occupied, unoccupied or standby) and time until the next change of state

(TUNCOS) to all of its control loops based on the configured schedules.

Network Variables

A class of variables defined in Neuron C that allow communication over the L

ON

W

ORKS

network to other nodes on the network. For example; An output network variable in one node can be bound to the corresponding input network variable(s) in other node(s). Changing the value of the output network variable in one node causes the new value to be automatically communicated to the bound input network variable(s) in other node(s). When an input network variable is updated, an nv_update_occurs event is posted at the receiving node(s) so that the application program can take action based on the change. A network management node that explicitly reads and/or writes the network variable can also poll network variables. Network variables can contain one data field

(one or two bytes) or multiple data fields (a structure).

Node

A Communications Connection on a network; An

Excel 15 or Excel 10 Controller is one node on the

L

ON

W

ORKS

Bus network.

NV

Network Variable; An Excel 15 or Excel 10 parameter that can be viewed or modified over the L

ON

W

ORKS

Bus network.

PC

An Personal Computer with Pentium processor capable of running Microsoft

Windows 95.

74-3079 6

EXCEL 15 W7760C PLANT CONTROLLER

Plant Controller

A device that can be used to monitor and control HVAC equipment and other miscellaneous loads in a distributed network.

Proportional Control

A control algorithm or method in which the final control element moves to a position proportional to the deviation of the value of the controlled variable from the setpoint.

Proportional Integral (PI) Control

A control algorithm that combines the proportional control and the integral reset control algorithms. Integral reset virtually eliminates offset by gradually shifting the controlled output in the direction that brings the controlled variable back to the setpoint.

Proportional Integral Derivative (PID) Control

A control algorithm that enhances the PI control algorithm by adding a component that is proportional to the rate of change (derivative) of the deviation of the controlled variable. PID compensates for system dynamics and allows faster control response rate reset.

PWM

Pulse Width Modulated output; Allows analog modulating control of equipment using a digital output on the controller.

RCD

Remote Communication Device; For the Building

Management System, this is a piece of hardware that is functionally compatible to an SLTA and provides access directly to the L

ON

W

ORKS

Bus.

Recovery Mode or Recovery Period

The time in unoccupied periods when the temperature control is adjusting the control setpoint so that the space temperature reaches the occupied setpoint when the schedule change occurs.

Reset

The reset of a control loop varies depending upon the type of control loop being reset. A reset for a thermostat loop or a control loop changes the setpoint and the algorithm in the energy saving direction. A reset for a start/stop loop causes the digital output to go to the inactive state before returning to its normal scheduled state.

RIO

Excel 10 Remote I/O Device; Additional inputs and outputs that can be configured for use by an Excel 15

W7760A or W7760C.

RTC

Real-time clock.

RTD

Resistance Temperature Detector; Refers to a type of temperature sensor whose resistance output changes according to the temperature change of the sensing element.

Schedule

The structure that defines the occupancy states, setpoints and the time of the changes between these states.

SLTA

Serial L

ON

T

ALK

Adapter; A serial interface between the EIA-232 (serial port on a PC) and a L

ON

W

ORKS

Bus used to adapt transformer-coupled Echelon messages.

SNVT

Standard Network Variable Type.

TOD

Time-Of-Day; The scheduling of Occupied and

Unoccupied times of operation.

TUNCOS

Time Until Next Change Of State is a command that can be sent to other controllers.

UV

An Excel 10 Unitary heating/cooling Ventilation System

Controller.

VA

Volt Amperes; A measure of electrical power output or consumption as applies to an ac device.

Vac

Voltage alternating current; ac voltage rather than dc voltage.

VAV

Variable Air Volume; Refers to a type of air distribution system.

VOC

Volatile Organic Compound; Refers to a class of common pollutants sometimes found in buildings.

Sources include out-gassing of construction materials, production-line by-products, and general cleaning solvents. A VOC is occasionally used as a measure of indoor air quality.

W7750

The model number of the Excel 10 CVAHU

Controllers (also see CVAHU).

W7751

The model number of the Excel 10 VAV Box

Controllers (also see VAV).

W7753

The model number of the Excel 10 UV Controller

(also see UV).

W7760

The model number of the Excel 15 Building Manager

Controller and the Plant Controller (also see Building

Manager and Plant Controller).

W7761

The model number of the Excel 10 RIO Device.

Wall Module

The Excel 10 Space Temperature Sensor and other optional controller inputs are contained in the

T7770 or the T7560A,B Wall Modules. See Application

Step 5. Order Equipment for details on the various models of Wall Modules.

7 74-3079

advertisement

Key Features

  • LONWORKS network communication
  • HVAC equipment control
  • Remote control
  • Analog and digital I/O
  • Configurable control loops

Related manuals

Frequently Answers and Questions

What is the W7760C Plant Controller used for?
The W7760C Plant Controller is used to monitor and control HVAC equipment and other miscellaneous loads using LONTALK® communications protocol on an Echelon® LONWORKS® network.
What devices are compatible with the W7760C Plant Controller?
The W7760C Plant Controller is compatible with Excel 15 W7760A Building Manager, Excel 15 S7760A Command Display, individual Excel 10 Controllers and T7300F/Q7300H Series 2000 Commercial Thermostats and Communicating Subbases.
What is the maximum number of start/stop loops that can be configured?
The W7760C Plant Controller supports a maximum of eight start/stop loops.
What is the maximum number of General Purpose Configurable Proportional Integral Derivative (PID) Control Loops that can be configured?
The W7760C Plant Controller supports a maximum of ten General Purpose Configurable Proportional Integral Derivative (PID) Control Loops.