VENTING TABLES – TECHNICAL VENTING DATA. State Water Heaters SBL85275NE, SBL85366NEA, SBL85390NE, SBL85310NE, SBL85275NEA, SBL85310NEA, SBL85366NE, SBL85390NEA


Add to my manuals
36 Pages

advertisement

VENTING TABLES – TECHNICAL VENTING DATA. State Water Heaters SBL85275NE, SBL85366NEA, SBL85390NE, SBL85310NE, SBL85275NEA, SBL85310NEA, SBL85366NE, SBL85390NEA | Manualzz

VENTING TABLES

TECHNICAL VENTING DATA

TYPE B GAS VENT

Multiple Gas Fired Tank-Type Heaters

When venting multiple tank type heaters using Type B vent pipe, follow the installation diagram and tables below which give sizing and data based upon NFPA 54 ANSI Z223.1.

MODEL SBL85275NE(A) Input: 275,000 Btu/hr

Vent Connector Size: 6 inches

Input Btu/hr

Number of Heaters

2

3

4

275,000

275,000

275,000

Combined Input in

Thousands of Btu/hr

550,000

825,000

1,100,000

MODEL SBL85310NE(A) Input: 310,000 Btu/hr

Vent Connector Size: 6 inches

Input Btu/hr

310,000

Number of Heaters

2

3

4

310,000

310,000

Combined Input in

Thousands of Btu/hr

620,000

930,000

1,240,000

MODEL SBL85366NE(A) Input: 366,000 Btu/hr

Vent Connector Size: 6 inches

Input Btuh/hr

366,000

366,000

Number of Heaters

2

3

4

366,000

Combined Input in

Thousands of Btu/hr

732,000

1,098,000

1,464,000

MODEL SBL85390NE(A) Input: 390,000 Btu/hr

Vent Connector Size: 6 inches

Input Btuh/hr

390,000

Number of Heaters

2

3

4

390,000

390,000

Combined Input in

Thousands of Btu/hr

780,000

1,170,000

1,560,000

14

Servicing should only be performed by a Qualified Service Technician

Rise

1 Ft.

2 Ft.

3 Ft.

Rise

1 Ft.

2 Ft.

3 Ft.

Rise

1 Ft.

2 Ft.

3 Ft.

Rise

1 Ft.

2 Ft.

3 Ft.

6

8

8

7

8

8

8

7

10

Total Vent Height (Feet)

15 20 30 50

Vent Connector Diameter (Inches)

8

7

7

7

7

7

7

7

7

6

6

6

6

6

6

100

10

14

14

Manifold and Common Vent Diameters (Inches)

10

12

14

9

12

14

9

10

12

8

10

12

8

9

12

7

9

10

7

8

9

6

6

6

6

-

8

8

8

8

8

8

10

Total Vent Height (Feet)

15 20 30 50

Vent Connector Diameter (Inches)

8 8 7 7 6

8

8

7

7

7

7

7

7

6

6

100

12

14

16

Manifold and Common Vent Diameters (Inches)

10

14

14

10

12

14

9

12

14

9

10

12

8

10

12

8

9

10

7

9

9

6

6

6

6

-

-

-

8

-

-

8

Total Vent Height (Feet)

10 15 20 30

Vent Connector Diameter (Inches)

8 8 7 7

8

8

8

8

8

7

7

7

50

7

6

Manifold and Common Vent Diameters (Inches)

12

14

16

12

14

16

12

14

16

10

12

14

9

12

14

9

12

12

8

10

12

100

6

6

6

8

9

10

6

-

-

-

8

-

-

-

Total Vent Height (Feet)

10 15 20 30 50

Vent Connector Diameter (Inches)

8 7 7

-

8

8

8

8

8

7

7

Manifold and Common Vent Diameters (Inches)

12

16

16

12

14

16

12

14

16

10

14

14

10

12

14

9

12

14

9

10

12

7

7

100

6

6

6

8

9

10

TYPE B GAS VENT: Single Gas Fired Tank-Type Heater

When venting single tank type water heater using Type B vent pipe, follow the tables below which give sizing and data based upon NFPA 54 ANSI Z223.1.

MODELS

MODEL SBL85275NE(A)

Input: 275,000 Btu/hr

Vent Connector Diameter: 6 inches

Vent Type: Type B Double-Wall Gas Vent

Vent Connection: Connected directly to Vent

Number of Appliances: Single

Appliance Venting: Fan assist

Note: Refer to NFPA 54/ ANSI Z223.1 for maximum vent diameter.

Lateral (Feet)

0

2

4

5

6

8

10

15

20

30

50

6

NA

7

NA

NA

NA

NA

6

7

7

NA

NA

8

6

7

NA

7

NA

7

NA

NA

NA

NA

NA

TOTAL VENT HEIGHT (FEET)

7

NA

NA

7

NA

NA

10 15 20 30

Minimum Vent Diameter (Inches)

6 5 5 5

7

NA

6

NA

6

NA

6

NA

NA

NA

6

NA

NA

6

6

NA

NA

NA

6

NA

NA

6

6

6

NA

NA

6

NA

6

NA

NA

6

6

6

50

5

5

NA

5

NA

NA

6

6

6

6

NA

100

5

5

NA

5

NA

NA

5

5

5

6

6

MODEL SBL85310NE(A)

Input: 310,000 Btu/hr

Vent Connector Diameter: 6 inches

Vent Type: Type B Double-Wall Gas Vent

Vent Connection: Connected directly to Vent

Number of Appliances: Single

Appliance Venting: Fan assist

Note: Refer to NFPA 54/ ANSI Z223.1 for maximum vent diameter.

Lateral (Feet)

0

2

4

5

6

8

10

15

20

30

50

MODEL SBL85366NE(A)

Input: 366,000 Btu/hr

Vent Connector Diameter: 6 inches

Vent Type: Type B Double-Wall Gas Vent

Vent Connection: Connected directly to Vent

Number of Appliances: Single

Appliance Venting: Fan assist

Note: Refer to NFPA 54/ ANSI Z223.1 for maximum vent diameter.

Lateral (Feet)

0

2

4

5

6

8

10

15

20

30

50

MODEL SBL85390NE(A)

Input: 390,000 Btu/hr

Vent Connector Diameter: 6 inches

Vent Type: Type B Double-Wall Gas Vent

Vent Connection: Connected directly to Vent

Number of Appliances: Single

Appliance Venting: Fan assist

Note: Refer to NFPA 54/ ANSI Z223.1 for maximum vent diameter.

Lateral (Feet)

0

2

4

5

6

8

10

15

20

30

50

8

NA

NA

NA

NA

6

8

8

NA

NA

NA

7

NA

NA

NA

6

7

7

NA

NA

NA

NA

8

NA

NA

NA

7

8

8

NA

NA

NA

NA

NA

8

NA

NA

NA

6

8

NA

8

NA

NA

NA

7

NA

NA

6

7

NA

7

NA

NA

NA

NA

8

NA

NA

6

8

NA

8

NA

NA

NA

Minimum Vent Diameter (Inches)

6 6 5 5

7

NA

6

NA

6

NA

6

NA

7

NA

NA

7

6

NA

NA

6

6

NA

NA

6

6

NA

NA

6

NA

NA

NA

NA

7

NA

NA

NA

6

6

NA

NA

6

6

6

NA

Minimum Vent Diameter (Inches)

6 6 6 6

7

NA

7

NA

6

NA

6

NA

7

NA

NA

7

NA

NA

7

NA

NA

7

7

NA

6

NA

NA

7

7

7

6

NA

NA

6

6

6

NA

NA

NA

NA

NA

NA

7

NA

Minimum Vent Diameter (Inches)

6 6 6 6

7

NA

7

NA

7

NA

6

NA

7

NA

NA

8

7

NA

NA

7

7

NA

NA

7

6

NA

NA

6

NA

NA

NA

NA

7

NA

NA

NA

7

7

NA

NA

7

7

7

NA

NA

NA

6

6

6

6

6

NA

6

6

NA

NA

NA

6

6

5

6

NA

6

6

6

NA

NA

NA

6

6

6

6

NA

6

6

6

NA

NA

NA

6

6

6

5

6

NA

6

6

6

NA

NA

6

6

5

5

NA

5

6

6

6

NA

NA

6

6

6

6

6

6

6

NA

6

Servicing should only be performed by a Qualified Service Technician