5.3.5 Bus overview
C7000AT "ME", on which this content is displayed .
Symbol for a C7000AT
Stop cause
Operational state of the control of a selected IOC
Symbol for a C7000IOC
Actual temperature
Operational state of the control
At this unit an alarm has occurred.
Actual humidity
This unit cannot be reached.
Global address of the selected
IOC
Selected IOC + Bus address
Example for a de-energized or disconnected (from the bus) IOC with data bus address 6
The AT with the bus address 19 edits the following configuration after the IOC 6 has been switched off :
ID glob.adr. dev.type reliab. config.
0 - unknown 0% 0
1 - unknown 0% 0
2 - unknown 0% 0 addresses are expected as active bus participants.
3 - unknown 0% 0
4 - IO-Controller 100% 1
5 - IO-Controller 100% 1
6 - unknown 0% 1 error
7 - IO-Controller 100% 1
8 - unknown 0% 0
9 - unknown 0% 0
10 - unknown 0% 0
11 - unknown 0% 0
12 - unknown 0% 0
13 - unknown 0% 0
14 - unknown 0% 0
15 - unknown 0% 0
16 255 AdvancedTerminal 100% 1
17 255 AdvancedTerminal 100% 1
18 255 AdvancedTerminal 100% 1
19 255 AdvancedTerminal me 1
Column "config" displays, which bus
When the availability of a con-
ERROR IN THE BUS CONFIGURATION DETECTED.
figured unit is 0%, an error is indicated.
The AT 19 detects, that the IOC 6 has been available in the bus, but can not be reached anymore. When the disconnected unit is switched on again, the bus error is automatically deleted at all bus participants. A bus error can also be deleted by inputting the command " iobusok" at an IOC or an AT.
E/0409/ 57/29