Vibration Isolators
Vibration isolators are recommended for all roof-mounted installations or wherever vibration transmission is a consideration.
The unit should be initially on shims or blocks at the listed free height. When all piping, wiring, flushing, charging, etc. is completed, the springs are adjusted upward to loosen the blocks or shims that are then removed.
A rubber anti-skid pad is part of the isolator. Installation of spring isolators requires flexible piping connections and at least three feet of flexible conduit to avoid straining the piping and transmitting vibration and noise. These units cannot be bolted to isolators.
Table 1, Recommended Vibration Isolators
RF
Neoprene-in-Shear
LF
RP-3 Red
RP-3 Green
RP-3 Red
RP-3 Green
RB
RP-3 Black
RP-3 Red
LB
RP-3 Black
RP-3 Red
Kit P/N
Model
010, 013,016,020,025,028
033, 039
350014859
350014857
Spring
LF
Kit P/N
Model
010, 013
016, 020
025, 028
033
039
RF
CP 1-24 Brown
CP 1-25 Red
CP 1-24 Brown
CP 1-25 Red
RB
CP 1-24 Brown
CP 1-24 Brown
LB
CP 1-24 Brown
CP 1-24 Brown
350014831
350014830
CP1-26 Purple CP1-26 Purple CP 1-24 Brown CP 1-24 Brown 350014829
CP1-27 Orange CP1-26 Purple CP 1-24 Brown CP 1-24 Brown 350014836
CP1-27 Orange CP1-27 Orange CP 1-24 Brown CP 1-24 Brown 350014828
Note: See dimension drawing for location of isolators
Corner Operating Weights
ACZ
Unit
Model
010
013
016
020
025
028
033
039
RF LF RB LB Total
259 257 243 241 1000
259 257 243 241 1000
353 360 251 256 1220
377 383 288 292 1340
498 505 232 235 1470
508 515 232 235 1490
605 567 304 284 1760
712 649 313 286 1960
RP-3, Neoprene-in Shear Isolator CP-1, Spring Isolator
Control
Panel
ACZ 010A through 039A IOMM ACZ1-3
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 General Description
- 3 Inspection
- 3 Installation
- 3 Handling
- 4 Location
- 4 Service Access
- 6 Vibration Isolators
- 7 Chilled Water System
- 9 Refrigerant Piping
- 13 Unit Component Location
- 13 Control Center
- 16 Pre Start-up
- 16 Start-up
- 16 Sequence of Operation
- 20 R-407C
- 21 Field Wiring
- 30 General
- 30 Lubrication
- 30 Electrical Terminals
- 30 Condensers
- 30 Refrigerant Sight glass
- 31 Table of Contents
- 32 Overview
- 32 General Description
- 34 Automatic Adjusted Limits
- 35 Dynamic Default Values
- 36 Control Functions and Definitions
- 37 Unit Enable
- 38 Unit Mode
- 38 Power Up Start Delay
- 38 Unit State
- 39 Evaporator Fan State Control
- 39 Condenser Fans
- 40 Low OAT Start
- 40 Capacity Overrides
- 41 Low Ambient Lockout
- 41 Compressor Control
- 42 Normal Shutdown
- 42 Rapid Shutdown
- 42 Liquid Line Solenoid
- 43 Using the Controller
- 54 Thermostatic Expansion Valve
- 54 Filter-Driers
- 54 Liquid Line Solenoid
- 55 Optional Controls
- 57 Troubleshooting Chart