- No category
Air-Cooled Screw Compressor Chiller Installation, Operation and Maintenance Manual 60 Hertz
Add to my manuals
84 Pages
advertisement
Troubleshooting Chart
Table 55, Troubleshooting
PROBLEM POSSIBLE CAUSES
1. Main power switch open.
2. Unit S1 system switch open.
3. Circuit switch PS1, PS2, PS3, PS4 in pumpdown position.
4. Evap flow switch not closed.
5. Circuit breakers open.
6. Fuse blown or circuit breakers tripped.
Compressor will not run.
7. Unit phase voltage monitor not satisfied.
8. Compressor overload tripped.
9. Defective compressor contactor or contactor coil.
10. System shut down by safety devices.
11. No cooling required.
12. Motor electrical trouble.
13. Loose wiring.
POSSIBLE CORRECTIVE STEPS
1. Close switch.
2. Check unit status on MicroTech display. Close switch.
3. Check circuit status on MicroTech display. Close switch.
4. Check unit status on MicroTech display. Close switch.
5. Close circuit breakers.
6. Check electrical circuits and motor windings for shorts or grounds.
Investigate for possible overloading. Check for loose or corroded connections. Reset breakers or replace fuses after fault is corrected.
7. Check unit power wiring to unit for correct phasing. Check voltage.
8. Overloads are manual reset. Reset overload at button on overload.
Clear alarm on MicroTech.
9. Check wiring. Repair or replace contactor.
10. Determine type and cause of shutdown and correct problem before attempting to restart.
11. Check control settings. Wait until unit calls for cooling.
12. See 6,7,8 above.
13. Check circuits for voltage at required points. Tighten all power wiring terminals
Compressor Noisy or Vibrating
1. Compr. Internal problem.
2. Liquid injection not adequate.
1. Contact McQuayService
2. Check to assure liquid line sightglass is full during steady operation.
Compressor
Overload Relay
Tripped or Circuit
Breaker Trip or
Fuses Blown
1. Low voltage during high load condition.
2. Loose power wiring.
3. Power line fault causing unbalanced voltage.
4. Defective or grounded wiring in the motor.
5. High discharge pressure.
1. Check supply voltage for excessive voltage drop.
2. Check and tighten all connections.
3. Check supply voltage.
4. Check motor and replace if defective.
5. See corrective steps for high discharge pressure.
Compressor Will
Not Load or Unload
1. Defective capacity control solenoids.
2. Unloader mechanism defective.
1. Check solenoids for proper operation. See capacity control section.
2. Replace.
Compressor Liquid
Injection Protection
Trip
1. Liquid injection solenoid did not open at start.
2. Inadequate liquid to liquid injection at start due to a clogged filter drier or low charge.
3. Inadequate liquid to liquid injection during run.
1. Check and replace liquid injection solenoid.
2. Check liquid injection line sight glass. If flashing check filter drier and unit charge.
3. Check liquid injection line sightglass. If flashing check filter-drier and unit charge. Discharge pressure too low. Protect condenser coil from wind.
High Discharge
Pressure
1. Discharge shutoff valve partially closed.
2. Noncondensables in the system.
3. Fans not running.
1. Open shutoff valve.
2. Purge the noncondensables from the condenser coil after shutdown.
3. Check fan fuses and electrical circuits.
IOMM ALS
79
High Discharge
Pressure
4. Fan control out of adjustment.
5. System overcharged with refrigerant.
6. Dirty condenser coil.
7. Air recirculation from outlet into unit coils.
8. Air restriction into unit.
4. Check that unit setup in MicroTech matches the unit model number.
Check MicroTech condenser pressure sensor for proper operation.
5. Check for excessive subcooling above 30oF (-1.1oC). Remove the excess charge.
6. Clean the condenser coil.
7. Remove the cause of recirculation.
8. Remove obstructions near unit.
Low Discharge
Pressure
Low Suction
Pressure
High Suction
Pressure
1.
2.
3.
4.
Wind effect a low ambient temperature.
Condenser fan control not correct.
Low section pressure.
Compressor operating unloaded.
1. Protect unit against excessive wind into vertical coils.
2. Check that unit setup in MicroTech matches the unit model number.
Check SpeedTrol fan on units with SpeedTrol option.
3. See corrective steps for low suction pressure.
4. See corrective steps for failure to load.
1. Inadequate refrigerant charge quantity.
2. Inadequate liquid to liquid injection at start. Clogged liquid line filter-drier.
3. Expansion valve malfunctioning.
4. Insufficient water flow to evaporator.
5. Water temperature leaving evaporator is too low.
6. Evaporator tubes fouled.
7. Evaporator head ring gasket slippage.
8. Glycol in chilled water system
1. Check liquid line sightglass. Check unit for leaks. Repair and recharge to clear sightglass.
2. Check pressure drop across filter-drier. Replace cores.
3. Check expansion valve superheat and valve opening position.
Replace valve only if certain valve is not working.
4. Check water pressure drop across the evaporator and adjust gpm.
5. Adjust water temperature to higher value.
6. Inspect by removing water piping. Clean chemically.
7. Low suction pressure and low superheat both present may indicate an internal problem. Consult factory.
8. Check glycol concentration
1. Excessive load - high water temperature.
2. Compressor unloaders not loading compressor.
3. Superheat is too low.
1. Reduce load or add additional equipment.
2. See corrective steps below for failure of compressor to load.
3. Check superheat on MicroTech display. Check suction line sensor installation and sensor.
80
IOMM ALS
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Introduction
- 3 General Description
- 3 Nomenclature
- 3 Inspection
- 3 Installation and Start-up
- 4 Handling
- 6 Location
- 6 Service Access
- 7 Clearance Requirements
- 10 Vibration Isolators
- 12 Water Piping
- 13 Evaporator Freeze Protection
- 14 Flow Switch
- 15 Water Connections
- 15 Refrigerant Charge
- 15 Glycol Solutions
- 18 Physical Data
- 21 Major Components
- 23 Compressor Staging
- 25 Dimensional Data
- 30 Electrical Data
- 30 Field Wiring
- 31 Wire Sizing Ampacities
- 41 Customer Wiring
- 47 Electrical Data Notes
- 48 Electrical Legend
- 49 Typical Field Wiring Diagram
- 50 Operation
- 50 Major Component Location
- 51 Control Center
- 53 Sequence of Operation
- 55 Start-up and Shutdown
- 55 Seasonal Start-up
- 55 Temporary Shutdown
- 56 Start-up After Temporary Shutdown
- 56 Extended Shutdown
- 57 Start-up After Extended Shutdown
- 58 System Maintenance
- 58 General
- 58 Compressor Maintenance
- 58 Lubrication
- 58 Electrical Terminals
- 58 Condensers
- 59 Refrigerant Sightglass
- 59 Lead-Lag
- 60 Preventative Maintenance Schedule
- 61 Service
- 61 Compressor Solenoids
- 61 Filter-Driers
- 62 Liquid Line Solenoid Valve
- 63 Liquid Injection Solenoid Valve
- 63 Electronic Expansion Valve
- 64 Electronic Expansion Valve Operation
- 65 Evaporator
- 65 Refrigerant Charging
- 67 Procedure
- 68 Standard Controls
- 76 Optional Controls
- 78 Controls, Settings and Functions
- 79 Troubleshooting Chart
- 81 Periodic Maintenance Log