advertisement
Application and Installation Guide EMCP 4.1, 4.2 Generator Set Control
Figure 68: Excitation Module Over- Excitation Protection Strategy
The Excitation Limit Potentiometer on the Excitation Module has 270 degrees of rotation and is used to configure the Excitation Current Upper Limit as shown in Figure 69. Keep in mind that this must be set for maximum forcing current, and not nominal excitation current.
Minimum Position
Maximum Position
EM10
4 Amps
10 Amps
EM15
6 Amps
15 Amps
Figure 69: Maximum and Minimum Limits of Excitation Current Limit Potentiometer
IVR EXCITATION MODULE FUSING
The EM10 has internal fusing, therefore it is not necessary to fit external fuses on the excitation power supply inputs.
The EM15 requires external fusing to be fitted on inputs X1 and Z2. The recommended fuse for UL listed gensets is a Bussman KTK-10 (Cat part number 6V7802). For non-UL listed gensets an alternative fuse of Bussman AGC-10RX (Cat part number 3K8782) may also be used.
Connection diagrams showing the location of external fusing on the EM15 are provided in Appendix C.
©2013 Caterpillar
All rights reserved. Page 235
EMCP 4.1, 4.2 Generator Set Control Application and Installation Guide
19.3 IVR SOFTWARE CONFIGURATION
The Integrated Voltage Regulator parameters can be accessed using either the CAT ET
Service tool, or directly through the EMCP display. Some setpoints are locked at ET only or at Security Level 3 and cannot be changed from the EMCP display or will require a level 3 password. Please note that ET Service Tool version 2012C or later is recommended for accessing and adjusting IVR parameters.
To access the Integrated Voltage Regulator setpoints using the ET Service Tool, connect to the EMCP Genset Control and click on the ‘Configuration Tool’ button
(alternatively press F5) to enter the configuration menu. Select ‘Integrated Voltage
Regulator’ from the menu on the left and set Voltage Regulator Control Source
Configuration equal to ‘Genset Control’ to display the following default settings:
To access the Integrated Voltage Regulator setpoints through the EMCP display, navigate to the following sub-menu:
MAIN MENU
CONFIGURE
ALL SETPOINTS
VOLTAGE REGULATOR
If replacing a CDVR with IVR, the parameters can be programmed the same as the
CDVR (using ET scaling) in order to achieve similar performance.
If the IVR is a new installation, or a R450 or VR6 voltage regulator is being replaced, the parameters can be programmed to the default values with a low loop gain starting in the region
1.0%-5.0%. Note that the default parameters should provide stable voltage control for most generator sets, however some optimization and tuning may be required to achieve the desired performance. The following subsections provide further detail on each individual setpoint, including range, resolution and default values.
Page 236 All rights reserved.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 24 Connecting to the EMCP 4 to Configure Setpoints
- 26 Supported Parameters
- 26 Engine Overview
- 30 AC Overview
- 32 Setting The Preferences Using The EMCP 4 Display
- 34 Changing The EMCP 4 Contrast When the Display is Unreadable
- 34 Changing The EMCP 4 Display to Technician English
- 35 Changing The EMCP 4 Display to the Primary Language
- 35 Setting the Preferences Using the Service Tool
- 36 Changing The Time/Date
- 38 Changing Date Format
- 39 Generator Output Voltage
- 39 Engine Speed
- 40 Idle/Rated
- 41 Engine Sensor Versus Data link
- 43 Engine Oil Pressure
- 46 Engine Coolant Temperature
- 48 Starting The Engine
- 49 EMCP 4 Remote Start
- 49 Stopping The Engine
- 51 Emergency Stop
- 53 Procedure For Overspeed Verification
- 53 Procedure For Low Oil Pressure Verification
- 54 Procedure For High Coolant Temperature Verification
- 55 Updating Engine Operating Hours
- 66 Not in Auto Warning
- 66 Service Maintenance Interval (EMCP 4.2 Only)
- 78 Setpoint Categories
- 83 Viewing the Current Digital Input Status
- 84 Configuring Digital Inputs for Status Parameters
- 86 Digital Input Command/STatus Descriptions
- 89 Configuring Digital Inputs for System Events
- 92 Configuring Digital Inputs for SCADA Data link
- 93 Disabling Digital Inputs
- 95 Configuring Digital Inputs for Status Parameter
- 96 Configuring Digital Inputs for System Events
- 100 Configuring Digital Inputs for SCADA Data link
- 100 Disabling Digital Inputs
- 103 Viewing the Current Analog Input Status
- 104 Configuring Analog Inputs for Resistive Mode
- 106 Configuring Analog Inputs for Voltage Mode
- 108 Disabling Analog Inputs
- 110 Configuring Analog Inputs for Resistive Mode
- 113 Configuring Analog Inputs for Voltage Mode
- 116 Disabling Analog Inputs
- 127 Warnings and Shutdowns
- 127 Unsupported Analog Input Sensor Ranges
- 127 Sensor Range is Smaller than Setpoint Options
- 129 Sensor Range is Larger than Setpoint Options, But Usable Range is Not
- 130 Sensor Range is Larger than Setpoint Options, And Usable Range is Larger Than Setpoint Options
- 132 Viewing the Current Output Status
- 133 Configuring Outputs for Status Parameters
- 135 Digital/relay Output Command/STatus Descriptions
- 138 Configuring Outputs for System Events
- 142 Digital/relay Output SYSTEM EVENT DESCRIPTIONS
- 145 Configuring Outputs for SCADA Data link
- 146 Disabling Outputs
- 147 Configuring Outputs for Status Parameters
- 149 Configuring Outputs for System Events
- 150 Configuring Outputs for SCADA Data link
- 151 Disabling Outputs
- 158 Fleet Configuration Option
- 158 ECM Replacement Option
- 178 Primary CAN Wiring
- 178 Network Topology
- 180 Accessory CAN Wiring
- 180 Network Topology
- 184 CAN Annunciator Features
- 184 Annunciator Specifications
- 185 Annunciator Wiring
- 186 LED Colors
- 187 CAN Annunciator Software Configuration
- 187 Global Acknowledge
- 187 ECU Instance Number
- 187 Configuring Annunciator LED Behavior
- 190 Trigger Condition
- 191 Severity Level
- 192 Suspect Parameter Number
- 193 Annunciator Features
- 193 Annunciator Specifications
- 194 RS-485 Annunciator Wiring
- 195 LED Colors
- 196 Lamp Test Function
- 196 Alarm Acknowledge
- 197 RS-485 ANNUNCIATOR ALARM GROUPS
- 197 Alarm Group Selection Mode (AGSM)
- 198 Entering AGSM
- 198 Re-configuring/Selecting Alarm Group Address
- 199 Exiting AGSM
- 199 RS-485 Annunciator Custom Alarm Group Configuration
- 199 CUSTOM ALARM GROUP SELECTION
- 200 Severity Level
- 200 Suspect Parameter Number
- 202 Alarm Groups
- 206 Configuring Custom Alarm Groups using Cat Service Tool
- 213 Thermocouple Features
- 214 Thermocouple Specifications
- 215 Thermocouple Wiring
- 216 Thermocouple Physical Layout
- 216 Thermocouple Module – Configuration
- 218 Configuring Thermocouple Inputs
- 219 RTD Features
- 220 RTD Specifications
- 221 RTD Wiring
- 222 RTD Physical Layout
- 222 RTD Module – Configuration
- 223 Configuring RTD Inputs
- 224 Discrete I/O Features
- 225 Discrete I/O Specifications
- 226 Discrete I/O Wiring
- 227 Discrete I/O Physical Layout
- 227 Discrete I/O Software Configuration
- 229 Configuring Digital Inputs
- 230 Configuring Relay Outputs
- 233 Configuring The SCADA Data Link Using The Display
- 235 Configuring The SCADA Data Link Using The Cat Service Tool
- 239 EMCP IVR Connections
- 239 IVR Excitation Module
- 240 IVR Excitation Module Physical Layout
- 241 IVR Excitation Module Connections
- 242 IVR Excitation Module Over-Excitation Protection
- 243 IVR Excitation Module Fusing
- 245 Voltage Regulator Control Source Configuration
- 246 Starting Profile
- 249 IVR PID Gain Setpoints
- 250 Under-Frequency Roll-Off (Loading) Profile
- 251 Voltage Regulator Load Compensation Type Configuration
- 251 Line Loss (IR) Compensation
- 252 Reactive Droop Compensation
- 254 Voltage Regulator Lockout Configuration
- 254 Loss of Sensing Shutdown Event
- 255 Over Excitation Shutdown Event
- 256 Digital Inputs
- 256 Voltage/Hz Control (EMCP Display)
- 256 SCADA Modbus (EMCP 4.2 Only)
- 257 Analog Inputs