3. SPECIFICATION
Measurement Specification
Continuity (to IEC61557-4)
Open Circuit
Voltage(DC)
Short Circuit
Current
Range Accuracy
Greater than 4V
Greater than
200mA
20/200Ω
Auto-Ranging
Up to 2Ω
Over 2Ω
±(3%rdg+4dgt)
±(3%rdg+3dgt)
Operating range(as in IEC61557) 20Ωrange:0.2Ω∼19.99Ω/200ΩRange:20Ω∼199.9Ω
Insulation Resistance (to IEC61557-2)
Open Circuit
Voltage (DC)
Rated Current Range
500V +20%−0%
1mA or greater
@ 500kΩ
20/200MΩ
Auto-Ranging
Accuracy
±(3% rdg +3dgt)
Operating range(as in IEC61557) 20MΩ Range:0.5MΩ∼19.99MΩ/200MΩ Range:20MΩ∼100MΩ
Loop Impedance (to IEC61557-3)
Rated Voltage
(AC)
Nominal Test
Current at 0Ω
External Loop
Range Accuracy
230V+10%−15%
50Hz
25A/10ms 20Ω ±(3%rdg +8dgt)
15mA/350ms max.
2000Ω
±(3%rdg +8dgt)
Operating range(as in IEC61557) 20Ω Range:2Ω∼19.99Ω/2000Ω Range:100Ω∼1999Ω
RCD testing (to IEC61557-6)
Function
Rated Voltage
(AC)
Trip Current
Settings
Trip Current
Duration
RCD × 1/2
RCD × 1
FAST
230V+10%−15%
50Hz
10/30/100/300/
500mA
150mA
2000ms
50ms
Accuracy
Trip Current:
−8% ∼−2%
Trip Current:
+2% ∼+8%
Trip Time
±(1%rdg+3dgt)
Voltage Measurement
Rated Voltage
100∼250V 50Hz
Measuring Range
100∼250V 50Hz
Accuracy
3%rdg
― 6 ―
To prevent wrong connection of test leads and to maintain safety, the dedicated terminals used for continuity and insulation tests are automatically covered when using the terminals for loop impedance and RCD tests
Instrument dimensions
Instrument weight
175 X 115 X 86mm
780g including batteries.
Reference conditions
Battery type
Low battery warning
Maximum numbers of measurements
Operating temperature and humidity.
Storage temperature and humidity
LED indication of live circuit warning
LED indication of correct
Polarity
Auto data hold
Display
Specifications are based on the following conditions except where otherwise stated:-
1.Ambient temperature: 23± 5:
2.Relative humidity: 45% to 75%
3.Position: horizontal
4.AC power source: 230V, 50Hz
5.DC power source: 12.0 V, ripple content 1% or less
6. Altitude: Up to 2000m
"
Eight R6 or LR6 batteries.
" symbol appears in the display if the battery voltage drops below 8V.
Approx. 700 times for use by continuity range or approx. 1000 times for use by insulation resistance range.
0 to +40:, relative humidity 80% or less, no condensation.
-10 to +50:, relative humidity 75% or less, no condensation.
Illuminates if there is an alternating voltage of 20V
AC or more in the circuit under test before continuity or insulation resistance tests. When DC voltage is detected across the measuring terminal the LED lights up.
The P-E and P-N LEDs illuminate when the wiring of the circuit under test is correct. The reverse lamp is lit when P and N are reversed.
In the loop impedance and RCD test functions, the
LCD reading is automatically frozen for 5 seconds after measurement.
The liquid crystal display has 3 1/2 digits with a decimal point and units of measurement (Ω, MΩ,
V and ms) relative to selected function. The display
― 7 ―
Overload protection
is updated approximately five times per second.
The continuity test circuit is protected by a 0.5 A
600 V fast acting(HRC)ceramic fuse mounted in the battery compartment, where a spare fuse is also stored.
The insulation resistance test circuit is protected by a resistor against 600 V AC for 10 seconds.
Mains Voltage Indication
On connecting test leads to the circuit under test on Loop and RCD ranges, the LCD reads V-PE.
Sign "V-PE Lo" or "V-PE Hi" is also shown when
Symbols used on the instrument
the voltage is 100V or less, or 260V or greater respectively.
Equipment protected throughout by DOUBLE
INSULATION or REINFORCED INSULATION.
Caution, risk of electric shock.
Caution(refer to accompanying instruction
― 8 ―