Chapter 15
Product Specifications
15.1 Model Numbers
The UPS systems are housed in free-standing cabinets with safety shields behind the doors.
The UPS systems are available in 50/60 Hz with various output power ratings.
SModels
Powerware 9390-40/20
Powerware 9390-40/30
Powerware 9390-40/40
Powerware 9390-80/40
Powerware 9390-80/50
Powerware 9390-80/60
Powerware 9390-80/80
Power Rating
20 kVA
30 kVA
40 kVA
40 kVA
50 kVA
60 kVA
80 kVA
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
The following sections detail the input, output, environmental, and battery specifications for the UPS.
15.2 Single Module Specifications
15.2.1 UPS System Input
Operating Input Voltage
(Nominal +10/–15%)
Operating Input
Frequency Range
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
480 Vac for operation from 408 Vac to 528 Vac
¦
5 Hz
Operating Input Current See Appendix A, Table E through Table J.
Reduced for Generator
Adjustable
5% THD at full load
Input Current Harmonic
Content
Power Factor
Line Surges
Battery Voltage
Minimum 0.99
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
384 Vdc (208V/220V units only)
432 Vdc
480 Vdc
EATON Powerware
®
9390 UPS (20–80 kVA) Installation and Operation Manual S 164201603 Rev 1 www.powerware.com
15-1
Product Specifications
15.2.2 UPS System Output
UPS Output Capacity
Output Voltage
Regulation
Output Voltage
Adjustment
(Nominal +/–3%)
Output Voltage Harmonic
Content
100% rated current
¦
1% (10% to 100% load)
208 Vac nominal, adjustable from 202 Vac to 214 Vac
220 Vac nominal, adjustable from 214 Vac to 226 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac
1.5% max THD (linear load)
5% max THD (nonlinear load)
Output Current See Appendix A, Table E through Table J.
Output Voltage Balance
3% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
Output Transients
3° for 100% maximum load imbalance (linear load)
5% for 100% load step or removal
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Overload Capability
0.01 Hz free running
Bypass within voltage limits of +5%, –8% of output setting; bypass within 0.5 Hz
1 Hz per second maximum
110% for 10 minutes
125% for 30 seconds
150% for 10 seconds
15.2.3 Environmental
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity
(operating and storage)
Acoustical Noise
EMI Suppression
Electrostatic Discharge
(ESD) Immunity
0 to 40°C (32–104°F) without derating. The recommended operating temperature is 25°C (77°F).
Maximum 1500m (5000 ft) at 40°C without derating
–25 to +60°C, excluding batteries (prolonged storage above
40°C causes rapid battery self-discharge)
5% to 95% maximum noncondensing
65 dB at a 1m distance, c weighted
Meets FCC Regulation 47, Part 15, for class A devices
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without damage and with no disturbance or adverse effect to the critical load.
15-2
EATON Powerware
®
9390 UPS (20–80 kVA) Installation and Operation Manual S 164201603 Rev 1 www.powerware.com
Product Specifications
15.3 Multiple Module Parallel Specifications
15.3.1 UPM Input
Same as single module.
15.3.2 UPM Output
Same as single module.
15.3.3 Environmental
Same as single module.
15.3.4 Battery
Same as single module.
15.3.5 Module Tie Cabinet Input
Operating Input Voltage
(UPM Dependent)
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
480 Vac for operation from 408 Vac to 528 Vac
Operating Input Current See Appendix A, Table S through Table V.
15.3.6 Module Tie Cabinet Output
Operating Output Voltage
(UPM Dependent)
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
480 Vac for operation from 408 Vac to 528 Vac
Operating Output Current See Appendix A, Table S through Table V.
EATON Powerware
®
9390 UPS (20–80 kVA) Installation and Operation Manual S 164201603 Rev 1 www.powerware.com
15-3
Product Specifications
This page intentionally left blank.
15-4
EATON Powerware
®
9390 UPS (20–80 kVA) Installation and Operation Manual S 164201603 Rev 1 www.powerware.com
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 Title
- 3 Table of Contents
- 9 List of Figures
- 11 Chapter 1 Introduction
- 17 Section I Installation
- 19 Chapter 2 UPS Installation Plan and Unpacking
- 23 Chapter 3 Installing the UPS System
- 39 Chapter 4 Batteries
- 41 Chapter 5 Installing a Remote Emergency Power-off Switch
- 45 Chapter 6 Installing Options and Accessories
- 53 Section II Operation
- 55 Chapter 7 Understanding UPS Operation
- 71 Chapter 8 Features, Options, and Accessories
- 75 Chapter 9 Using the Control Panel
- 123 Chapter 10 UPS Operating Instructions
- 137 Chapter 11 Using Features and Options
- 143 Chapter 12 Responding to System Events
- 153 Chapter 13 Communication
- 159 Chapter 14 Maintaining the UPS System
- 163 Chapter 15 Product Specifications
- 167 Appendix Installation Information
- 229 Warranty
- 232 Manual Part Number and Revision