Chapter 15 Product Specifications. Eaton Powerware 9390


Add to my manuals
232 Pages

advertisement

Chapter 15 Product Specifications. Eaton Powerware 9390 | Manualzz

Chapter 15

Product Specifications

15.1 Model Numbers

The UPS systems are housed in free-standing cabinets with safety shields behind the doors.

The UPS systems are available in 50/60 Hz with various output power ratings.

SModels

Powerware 9390-40/20

Powerware 9390-40/30

Powerware 9390-40/40

Powerware 9390-80/40

Powerware 9390-80/50

Powerware 9390-80/60

Powerware 9390-80/80

Power Rating

20 kVA

30 kVA

40 kVA

40 kVA

50 kVA

60 kVA

80 kVA

Frequency

50/60 Hz

50/60 Hz

50/60 Hz

50/60 Hz

50/60 Hz

50/60 Hz

50/60 Hz

The following sections detail the input, output, environmental, and battery specifications for the UPS.

15.2 Single Module Specifications

15.2.1 UPS System Input

Operating Input Voltage

(Nominal +10/–15%)

Operating Input

Frequency Range

208 Vac for operation from 177 Vac to 229 Vac

220 Vac for operation from 187 Vac to 242 Vac

480 Vac for operation from 408 Vac to 528 Vac

¦

5 Hz

Operating Input Current See Appendix A, Table E through Table J.

Reduced for Generator

Adjustable

5% THD at full load

Input Current Harmonic

Content

Power Factor

Line Surges

Battery Voltage

Minimum 0.99

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4

384 Vdc (208V/220V units only)

432 Vdc

480 Vdc

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual S 164201603 Rev 1 www.powerware.com

15-1

Product Specifications

15.2.2 UPS System Output

UPS Output Capacity

Output Voltage

Regulation

Output Voltage

Adjustment

(Nominal +/–3%)

Output Voltage Harmonic

Content

100% rated current

¦

1% (10% to 100% load)

208 Vac nominal, adjustable from 202 Vac to 214 Vac

220 Vac nominal, adjustable from 214 Vac to 226 Vac

480 Vac nominal, adjustable from 466 Vac to 494 Vac

1.5% max THD (linear load)

5% max THD (nonlinear load)

Output Current See Appendix A, Table E through Table J.

Output Voltage Balance

3% for 100% maximum load imbalance (linear load)

Output Voltage Phase

Displacement

Output Transients

3° for 100% maximum load imbalance (linear load)

5% for 100% load step or removal

Frequency Regulation

Synchronous to Bypass

Frequency Slew Rate

Overload Capability

0.01 Hz free running

Bypass within voltage limits of +5%, –8% of output setting; bypass within 0.5 Hz

1 Hz per second maximum

110% for 10 minutes

125% for 30 seconds

150% for 10 seconds

15.2.3 Environmental

Operating Temperature

Operating Altitude

Storage Temperature

Relative Humidity

(operating and storage)

Acoustical Noise

EMI Suppression

Electrostatic Discharge

(ESD) Immunity

0 to 40°C (32–104°F) without derating. The recommended operating temperature is 25°C (77°F).

Maximum 1500m (5000 ft) at 40°C without derating

–25 to +60°C, excluding batteries (prolonged storage above

40°C causes rapid battery self-discharge)

5% to 95% maximum noncondensing

65 dB at a 1m distance, c weighted

Meets FCC Regulation 47, Part 15, for class A devices

Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without damage and with no disturbance or adverse effect to the critical load.

15-2

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual S 164201603 Rev 1 www.powerware.com

Product Specifications

15.3 Multiple Module Parallel Specifications

15.3.1 UPM Input

Same as single module.

15.3.2 UPM Output

Same as single module.

15.3.3 Environmental

Same as single module.

15.3.4 Battery

Same as single module.

15.3.5 Module Tie Cabinet Input

Operating Input Voltage

(UPM Dependent)

208 Vac for operation from 177 Vac to 229 Vac

220 Vac for operation from 187 Vac to 242 Vac

480 Vac for operation from 408 Vac to 528 Vac

Operating Input Current See Appendix A, Table S through Table V.

15.3.6 Module Tie Cabinet Output

Operating Output Voltage

(UPM Dependent)

208 Vac for operation from 177 Vac to 229 Vac

220 Vac for operation from 187 Vac to 242 Vac

480 Vac for operation from 408 Vac to 528 Vac

Operating Output Current See Appendix A, Table S through Table V.

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual S 164201603 Rev 1 www.powerware.com

15-3

Product Specifications

This page intentionally left blank.

15-4

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual S 164201603 Rev 1 www.powerware.com