- No category
advertisement
Function
Project transmission and diagnosis via Ethernet interface
Modbus address for controllere PLC status
Modbus address
1024
Data content (16 bits = 1 word)
status value = 1
PLC is in the operating mode RUN status value = 2
PLC is in the operating mode STOP status value = 8
PLC is in the operating mode GATEWAY
Modbus address for Modbus timeout
Modbus address Data content (16 bits = 1 word)
2048 timeout value in [ms]
► The PLC of the controllere must be in the gateway mode.
► If value ≠ 0: the outputs are reset if no Modbus telegram (read or write request) has been received in the specified time [ms].
► If value = 0: this function is deactivated.
► The register is predefined by the corresponding setting on the ifm standard HTML page of the web server. The value set via the ifm standard HTML page is stored non-volatilely in the controllere.
Changes of this register via Modbus however are volatile. After rebooting the controllere the value defined by the HTML page is again activated.
Modbus address for Modbus write timeout
Modbus address
2049
Data content (16 bits = 1 word)
timeout value in [ms]
► The PLC of the controllere must be in the gateway mode.
► Function is identical to "Modbus timeout" ( page
), but for the Modbus write timeout only
Modbus write requests are taken into account to trigger the timeout time counter.
Modbus address for "delete Modbus write timeout register"
Modbus address Data content (16 bits = 1 word)
2050 user-defined
► Writing on this Modbus address results in a reset of the Modbus write timeout register, thus the timeout time counter is reset.
► This function allows to prevent the triggering of the Modbus write timeout without having to write on the outputs used.
► The value written in this register is ignored in the controllere.
4-36
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses of the digital slave inputs and outputs
Modbus addresses Bits of the Modbus address
Master 1 inputs
Master 1 outputs
Master 2 inputs
Master 2 outputs
Slave data bits
15…12 11 10 9 8 7…4 3
D3 D2 D1 D0
2 1 0
D3 D2 D1 D0
4203
4104
4105
4106
4107
4108
4109
4110
4111
4112
4096
4097
4098
4099
4100
4101
4102
4120
4121
4122
4123
4124
4113
4114
4115
4116
4117
4118
4119
4125
4126
4127
4532
4533
4534
4535
4536
4537
4538
4539
4540
4541
4525
4526
4527
4528
4529
4530
4531
4549
4550
4551
4552
4553
4542
4543
4544
4545
4546
4547
4548
4554
4555
4556
8199
8200
8201
8202
8203
8204
8205
8206
8207
8208
8192
8193
8194
8195
8196
8197
8198
8216
8217
8218
8219
8220
8209
8210
8211
8212
8213
8214
8215
8221
8222
8223
8628
8629
8630
8631
8632
8633
8634
8635
8636
8637
8621
8622
8623
8624
8625
8626
8627
8645
8646
8647
8648
8649
8638
8639
8640
8641
8642
8643
8644
8650
8651
8652
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 slave 2 (A) slave 4 (A) slave 6 (A) slave 8 (A) slave 10 (A) slave 12 (A) slave 14 (A) slave 16 (A) slave 18 (A) slave 20 (A) slave 22 (A) slave 24 (A) slave 26 (A) slave 28 (A) slave 30 (A) reserved slave 2 B slave 4 B slave 6 B slave 8 B slave 10 B slave 12 B slave 14 B slave 16 B slave 18 B slave 20 B slave 22 B slave 24 B slave 26 B slave 28 B slave 30 B reserved
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 slave 1 (A) slave 3 (A) slave 5 (A) slave 7 (A) slave 9 (A) slave 11 (A) slave 13 (A) slave 15 (A) slave 17 (A) slave 19 (A) slave 21 (A) slave 23 (A) slave 25 (A) slave 27 (A) slave 29 (A) slave 31 (A) slave 1 B slave 3 B slave 5 B slave 7 B slave 9 B slave 11 B slave 13 B slave 15 B slave 17 B slave 19 B slave 21 B slave 23 B slave 25 B slave 27 B slave 29 B slave 31 B
4-37
Function
Project transmission and diagnosis via Ethernet interface
Master 1 inputs
%IB1.1
%IB1.2
%IB1.3
%IB1.4
%IB1.5
%IB1.6
%IB1.7
%IB1.8
%IB1.9
%IB1.10
%IB1.11
%IB1.12
%IB1.13
%IB1.14
%IB1.15
%IB1.16
%IB1.17
%IB1.18
%IB1.19
%IB1.20
%IB1.21
%IB1.22
%IB1.23
%IB1.24
%IB1.25
%IB1.26
%IB1.27
%IB1.28
%IB1.29
%IB1.30
IEC addresses in the PLC of the controllere for the digital slave inputs and outputs
Data area
I = input
Q = output
%QB1.1
%QB1.2
%QB1.3
%QB1.4
%QB1.5
%QB1.6
%QB1.7
%QB1.8
%QB1.9
%QB1.10
%QB1.11
%QB1.12
%QB1.13
%QB1.14
%QB1.15
%QB1.16
%QB1.17
%QB1.18
%QB1.19
%QB1.20
%QB1.21
%QB1.22
%QB1.23
%QB1.24
%QB1.25
%QB1.26
%QB1.27
%QB1.28
%QB1.29
%QB1.30
% I B 1. 7
% Q X 21. 2 .3
Identification Type of access
Slave address Data bit
B = byte
X = bit
1 = S/A slave on master 1
2 = S/A slave on master 2
11 = B slave on master 1
21 = B slave on master 2
…
31 = slave 31
S/A slave = single slave or A slave
IEC addresses
(PLC in controllere)
Master 1 outputs
Master 2 inputs
Master 2 outputs
1 = slave 1
2 = slave 2 if type of access = X:
0 = D0
1 = D1
2 = D2
3 = D3
Inputs / outputs to slave address
%IB2.1
%IB2.2
%IB2.3
%IB2.4
%IB2.5
%IB2.6
%IB2.7
%IB2.8
%IB2.9
%IB2.10
%IB2.11
%IB2.12
%IB2.13
%IB2.14
%IB2.15
%IB2.16
%IB2.17
%IB2.18
%IB2.19
%IB2.20
%IB2.21
%IB2.22
%IB2.23
%IB2.24
%IB2.25
%IB2.26
%IB2.27
%IB2.28
%IB2.29
%IB2.30
4-38
%IB11.11
%IB11.12
%IB11.13
%IB11.14
%IB11.15
%IB11.16
%IB11.17
%IB11.18
%IB11.19
%IB11.20
Master 1 inputs
%IB1.31
%IB11.1
%IB11.2
%IB11.3
%IB11.4
%IB11.5
%IB11.6
%IB11.7
%IB11.8
%IB11.9
%IB11.10
%IB11.21
%IB11.22
%IB11.23
%IB11.24
%IB11.25
%IB11.26
%IB11.27
%IB11.28
%IB11.29
%IB11.30
%IB11.31
Function
Project transmission and diagnosis via Ethernet interface
%QB11.21
%QB11.22
%QB11.23
%QB11.24
%QB11.25
%QB11.26
%QB11.27
%QB11.28
%QB11.29
%QB11.30
%QB11.31
%QB11.11
%QB11.12
%QB11.13
%QB11.14
%QB11.15
%QB11.16
%QB11.17
%QB11.18
%QB11.19
%QB11.20
IEC addresses
(PLC in controllere)
Master 1 outputs
Master 2 inputs
%QB1.31
%QB11.1
%QB11.2
%QB11.3
%IB2.31
%IB21.1
%IB21.2
%IB21.3
%QB11.4
%QB11.5
%QB11.6
%QB11.7
%QB11.8
%QB11.9
%QB11.10
%IB21.4
%IB21.5
%IB21.6
%IB21.7
%IB21.8
%IB21.9
%IB21.10
%IB21.11
%IB21.12
%IB21.13
%IB21.14
%IB21.15
%IB21.16
%IB21.17
%IB21.18
%IB21.19
%IB21.20
%IB21.21
%IB21.22
%IB21.23
%IB21.24
%IB21.25
%IB21.26
%IB21.27
%IB21.28
%IB21.29
%IB21.30
%IB21.31
Master 2 outputs
Inputs / outputs to slave address
4-39
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the master flags
Modbus address
IEC address
(PLC in controllere)
Bit
Master 1 Master 2
Bit = TRUE means:
4128
%IW31.240
8224
%IW32.240
4129
%IW31.241
8225
%IW32.241
0
"No Slave Reset"
When executing the function "Config all" (via the menu or command channel of the controllere) the slaves are NOT reset, as described in the AS-i specification.
1...15 reserved
0
1
"Config OK"
There is no configuration error. The configuration of all AS-i slaves in the network complies with the configuration data.
"LDS.0"
One slave with the AS-i address 0 was detected on the master.
2 reserved
3 reserved
4
5
"Configuration_Active"
The controllere is in the configuration mode
"Normal_Operation_Active"
The AS-i master is in normal operation: it communicates with at least one slave.
6
„AS-i_Power_Fail“
The AS-i voltage is too low.
7 reserved
„Periphery_OK“
8
None of the active AS-i slaves signals a periphery fault.
9
„Auto_Address_Enable“
The mode "automatic addressing of the slaves" on this master is activated.
10...15 reserved
Examples:
To retrieve the bit LDS.0 "slave 0 detected" for master 1, the address %IX31.241.1 is used; for master 2 the address
%IX32.241.1 is used.
IEC addresses in the PLC of the controllere for the master flags
Data area
% I W 31. 240
% I X 32. 241 .8
Identification Word selection
I = input
Type of access
W = word
X = bit
31 = master 1
32 = master 2
240 = master flags word 1
241 = master flags word 2
Data bit no.
if type of access = X:
0…15
4-40
4582
4583
4584
4585
4586
4577
4578
4579
4580
4581
4572
4573
4574
4575
4576
4587
4588
4589
4590
4567
4568
4569
4570
4571
4562
4563
4564
4565
4566
8249
8250
8251
8252
8253
8244
8245
8246
8247
8248
8239
8240
8241
8242
8243
8254
8255
8256
8257
8234
8235
8236
8237
8238
8229
8230
8231
8232
8233
4153
4154
4155
4156
4157
4148
4149
4150
4151
4152
4143
4144
4145
4146
4147
4158
4159
4160
4161
4138
4139
4140
4141
4142
4133
4134
4135
4136
4137
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the analogue slave inputs and outputs
Master 1 inputs
Modbus addresses
Master 1 outputs
Master 2 inputs
Master 2 outputs
Data content (16 bits = word)
Channel Description
4130
4131
4559
4560
8226
8227
8655
8656
0
1
1st channel S/A slave
2nd channel S/A slave
4132 4561 8228
8660
8661
8665
8666
8670
8671
8675
8676
8680
8681
8685
8686
0
1
0
1
0
1
0
1
0
1
0
1
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
Slave address
1
2
3
4
5
6
7
4-41
4612
4613
4614
4615
4616
4607
4608
4609
4610
4611
4617
4618
4619
4620
4621
4602
4603
4604
4605
4606
4597
4598
4599
4600
4601
4592
4593
4594
4595
4596
8279
8280
8281
8282
8283
8274
8275
8276
8277
8278
8284
8285
8286
8287
8288
8269
8270
8271
8272
8273
8264
8265
8266
8267
8268
8259
8260
8261
8262
8263
4183
4184
4185
4186
4187
4178
4179
4180
4181
4182
4188
4189
4190
4191
4192
4173
4174
4175
4176
4177
4168
4169
4170
4171
4172
4163
4164
4165
4166
4167
Function
Project transmission and diagnosis via Ethernet interface
Master 1 inputs
4162
Modbus addresses
Master 1 outputs
Master 2 inputs
4591 8258
Data content (16 bits = word)
Master 2 outputs
Channel Description
8690
8691
8695
8696
8700
8701
8705
8706
8710
8711
8715
8716
0
1
0
1
0
1
0
1
0
1
0
1
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
4193
4194
4-42
4622
4623
8289
8290
Slave address
8
9
10
11
12
13
4642
4643
4644
4645
4646
4637
4638
4639
4640
4641
4647
4648
4649
4650
4651
4632
4633
4634
4635
4636
4627
4628
4629
4630
4631
8309
8310
8311
8312
8313
8304
8305
8306
8307
8308
8314
8315
8316
8317
8318
8299
8300
8301
8302
8303
8294
8295
8296
8297
8298
4213
4214
4215
4216
4217
4208
4209
4210
4211
4212
4218
4219
4220
4221
4222
4203
4204
4205
4206
4207
4198
4199
4200
4201
4202
Function
Project transmission and diagnosis via Ethernet interface
Master 1 inputs
4195
4196
4197
Modbus addresses
Master 1 outputs
Master 2 inputs
4624
4625
8291
8292
4626 8293
Data content (16 bits = word)
Master 2 outputs
8720
8721
Channel Description
0
1
1st channel S/A slave
2nd channel S/A slave
8725
8726
8730
8731
8735
8736
8740
8741
8745
8746
0
1
0
1
0
1
0
1
0
1
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
4223
4224
4225
4226
4227
4652
4653
4654
4655
4656
8319
8320
8321
8322
8323
8750
8751
0
1
1st channel S/A slave
2nd channel S/A slave
Slave address
14
15
16
17
18
19
20
4-43
4258
4259
4260
4261
4-44
4248
4249
4250
4251
4252
4253
4254
4255
4256
4257
4243
4244
4245
4246
4247
4238
4239
4240
4241
4242
4682
4683
4684
4685
4686
4687
4688
4689
4690
4677
4678
4679
4680
4681
4672
4673
4674
4675
4676
4667
4668
4669
4670
4671
4662
4663
4664
4665
4666
Function
Project transmission and diagnosis via Ethernet interface
Master 1 inputs
4228
4229
4230
4231
4232
Modbus addresses
Master 1 outputs
Master 2 inputs
4657
4658
4659
4660
4661
8324
8325
8326
8327
8328
Data content (16 bits = word)
Master 2 outputs
Channel Description
8755
8756
0
1
1st channel S/A slave
2nd channel S/A slave
4233
4234
4235
4236
4237
8760
8761
0
1
1st channel S/A slave
2nd channel S/A slave
8349
8350
8351
8352
8353
8354
8355
8356
8357
8344
8345
8346
8347
8348
8339
8340
8341
8342
8343
8334
8335
8336
8337
8338
8329
8330
8331
8332
8333
8765
8766
8770
8771
8775
8776
8780
8781
8785
8786
0
1
0
1
0
1
0
1
0
1
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
1st channel S/A slave
2nd channel S/A slave
Slave address
21
22
23
24
25
26
27
Function
Project transmission and diagnosis via Ethernet interface
Master 1 inputs
4262
Modbus addresses
Master 1 outputs
Master 2 inputs
4691 8358
Data content (16 bits = word)
Master 2 outputs
Channel Description
Slave address
4263
4264
4265
4266
4267
4692
4693
4694
4695
4696
8359
8360
8361
8362
8363
8790
8791
0
1
1st channel S/A slave
2nd channel S/A slave
28
4268
4269
4270
4271
4272
4697
4698
4699
4700
4701
8364
8365
8366
8367
8368
8795
8796
0
1
1st channel S/A slave
2nd channel S/A slave
29
4273
4274
4275
4276
4277
4702
4703
4704
4705
4706
8369
8370
8371
8372
8373
8800
8801
0
1
1st channel S/A slave
2nd channel S/A slave
30
4278
4279
4280
4281
4282
4707
4708
4709
4710
4711
8374
8375
8376
8377
8378
8805
8806
0
1
1st channel S/A slave
2nd channel S/A slave
31
4283 4712 8379
4284 4713 8380
Status information of analogue slaves
Word no.
0
1
15 14 13 12
Bit
11 10 9 8 7 6 5 analogue channel 0 from/for slave or: analogue data channel 0 from/for slave 1A analogue data channel 1 from/for slave 1 or: analogue data channel 1 from/for slave 1A
4 3 2 1 0
2
3 analogue data channel 2 from/for slave 1 or: analogue data channel 0 from/for slave 1B analogue data channel 3 from/for slave 1 or: analogue data channel 1 from/for slave 1B
4 TIB TOB TIA TOA TVB OVB TVA OVA O3 V3 O2 V2 O1 V1 O0 V0
4-45
Function
Project transmission and diagnosis via Ethernet interface
Word no.
5
15 14 13 12
Bit
11 10 9 8 7 6 5 analogue data channel 0 from/for slave 2 or: analogue data channel 0 from/for slave 2A
4 3 2 1 0
6
7
8 analogue data channel 1 from/for slave 2 or: analogue data channel 1 from/for slave 2A analogue data channel 2 from/for slave 2 or: analogue data channel 0 from/for slave 2B analogue data channel 3 from/for slave 2 or: analogue data channel 1 from/for slave 2B
9 TIB TOB TIA TOA TVB OVB TVA OVA O3 V3 O2 V2 O1 V1 O0 V0
… …
150
151
152
153 analogue data channel 0 from/for slave 31 or: analogue data channel 0 from/for slave 31A analogue data channel 1 from/for slave 31 or: analogue data channel 1 from/for slave 31A analogue data channel 2 from/for slave 31 or: analogue data channel 0 from/for slave 31B analogue data channel 3 from/for slave 31 or: analogue data channel 1 from/for slave 31B
154 TIB TOB TIA TOA TVB OVB TVA OVA O3 V3 O2 V2 O1 V1 O0 V0
Legend:
Vn
On
OVA
TVA
OVB
TVB
TIA
TIB
TOA
TOB validity bit "valid" for channel number n = 0...3
NOTE: set Vn = "1" for analogue output slaves! bit "overflow" for channel number n = 0…3 channel-independent bit "output data valid" from A slave
CTT1:
0 = more than 3.5 s have elapsed since the last update of the output values
1 = slave requests new output data within the next 3 s
CTT2…CTT5:
0 = slave receives no new output data
1 = slave receives new output data channel-independent bit "transmission valid" from A slave/single slave:
0 = error during transmission or: timeout
1 = transmission of analogue input/output data OK channel-independent bit "output data valid" from B slave:
CTT1:
0 = more than 3.5 s have elapsed since the last update of the output values
1 = slave requests new output data within the next 3 s
CTT2…CTT5:
0 = slave receives no new output data
1 = slave receives new output data
NOTE: only valid for analogue output slaves. Set OVB = 0 for input slaves! channel-independent bit "transmission valid" from B slave:
0 = error during transmission or: timeout
1 = transmission of analogue input/output data OK slave transmits analogue input data...
0 = in the analogue mode (15 bits, with sign)
1 = in the transparent mode (16 bits, without sign) slave receives analogue output data...
0 = in the analogue mode (15 bits, with sign)
1 = in the transparent mode (16 bits, without sign)
4-46
Function
Project transmission and diagnosis via Ethernet interface
IEC addresses in the PLC of the controllere for the analogue slave inputs and outputs
% I W 21. 6 .0
Data area Type of access
% Q W 22. 9 .3
Identification Slave address Data channel
I = input
Q = output
W = word
21 = master 1
22 = master 2
S/A slave = single slave or A slave
1 = slave 1
2 = slave 2
…
31 = slave 31
0 =
1 =
2 =
3 =
1st channel S/A slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 = status
A/B slaves have max. 2 analogue channels
Master 1 inputs
IEC addresses
(PLC in controllere)
Master 1 outputs
Master 2 inputs
Master 2 outputs
Data content (16 bits = word)
Channel Description
Slave address
%IW21.1.0 %QW21.1.0 %IW22.1.0 %QW22.1.0
%IW21.1.1 %QW21.1.1 %IW22.1.1 %QW22.1.1
%IW21.1.2 %QW21.1.2 %IW22.1.2 %QW22.1.2
%IW21.1.3 %QW21.1.3 %IW22.1.3 %QW22.1.3
%IW21.1.4 %QW21.1.4 %IW22.1.4 %QW22.1.4
%IW21.2.0 %QW21.2.0 %IW22.2.0 %QW22.2.0
%IW21.2.1 %QW21.2.1 %IW22.2.1 %QW22.2.1
%IW21.2.2 %QW21.2.2 %IW22.2.2 %QW22.2.2
%IW21.2.3 %QW21.2.3 %IW22.2.3 %QW22.2.3
%IW21.2.4 %QW21.2.4 %IW22.2.4 %QW22.2.4
%IW21.3.0 %QW21.3.0 %IW22.3.0 %QW22.3.0
%IW21.3.1 %QW21.3.1 %IW22.3.1 %QW22.3.1
%IW21.3.2 %QW21.3.2 %IW22.3.2 %QW22.3.2
%IW21.3.3 %QW21.3.3 %IW22.3.3 %QW22.3.3
%IW21.3.4 %QW21.3.4 %IW22.3.4 %QW22.3.4
%IW21.4.0 %QW21.4.0 %IW22.4.0 %QW22.4.0
%IW21.4.1 %QW21.4.1 %IW22.4.1 %QW22.4.1
%IW21.4.2 %QW21.4.2 %IW22.4.2 %QW22.4.2
%IW21.4.3 %QW21.4.3 %IW22.4.3 %QW22.4.3
%IW21.4.4 %QW21.4.4 %IW22.4.4 %QW22.4.4
%IW21.5.0 %QW21.5.0 %IW22.5.0 %QW22.5.0
0
1
2
3
1st channel S/A slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
4 status
0 1st channel S/A slave
1
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0 1st channel S/A slave
1
2
3
4
5
4-47
Function
Project transmission and diagnosis via Ethernet interface
Master 1 inputs
IEC addresses
(PLC in controllere)
Master 1 outputs
Master 2 inputs
Master 2 outputs
%IW21.5.1 %QW21.5.1 %IW22.5.1 %QW22.5.1
%IW21.5.2 %QW21.5.2 %IW22.5.2 %QW22.5.2
%IW21.5.3
%IW21.5.4 %QW21.5.4 %IW22.5.4 %QW22.5.4
%IW21.6.0 %QW21.6.0 %IW22.6.0 %QW22.6.0
%IW21.6.1
%IW21.6.2
%IW21.6.3
%IW21.8.2
%QW21.6.1
%QW21.6.2
%QW21.8.2
%IW22.6.1
%IW22.6.2
%IW22.8.2
%QW22.6.1
%QW22.6.2
%IW21.6.4 %QW21.6.4 %IW22.6.4 %QW22.6.4
%IW21.7.0 %QW21.7.0 %IW22.7.0 %QW22.7.0
%IW21.7.1
%IW21.7.2
%IW21.7.3
%IW21.7.4 %QW21.7.4 %IW22.7.4 %QW22.7.4
%IW21.8.0 %QW21.8.0 %IW22.8.0 %QW22.8.0
%IW21.8.1 %QW21.8.1 %IW22.8.1 %QW22.8.1
%IW21.8.3
%IW21.9.3
%IW21.9.4
%QW21.7.1
%QW21.7.2
%QW21.7.3
%QW21.8.3
%IW22.7.1
%IW22.7.2
%IW22.7.3
%IW22.8.3
%QW22.7.1
%QW22.7.2
%QW22.7.3
%QW22.8.2
%QW22.8.3
%IW21.8.4 %QW21.8.4 %IW22.8.4 %QW22.8.4
%IW21.9.0 %QW21.9.0 %IW22.9.0 %QW22.9.0
%IW21.9.1 %QW21.9.1 %IW22.9.1 %QW22.9.1
%IW21.9.2 %QW21.9.2 %IW22.9.2 %QW22.9.2
%IW21.10.0 %QW21.10.0 %IW22.10.0 %QW22.10.0
%IW21.10.1 %QW21.10.1 %IW22.10.1 %QW22.10.1
%IW21.10.2
%IW21.10.3
%IW21.10.4
%QW21.9.4
%QW21.10.4
%IW22.9.4
%IW22.10.4
%QW22.9.4
%QW22.10.4
%IW21.11.0 %QW21.11.0 %IW22.11.0 %QW22.11.0
%IW21.11.1 %QW21.11.1 %IW22.11.1 %QW22.11.1
%IW21.11.2
%QW21.5.3
%QW21.6.3
%QW21.9.3
%QW21.10.2
%QW21.10.3
%QW21.11.2
%IW22.5.3
%IW22.6.3
%IW22.9.3
%IW22.10.2
%IW22.10.3
%IW22.11.2
%QW22.5.3
%QW22.6.3
%QW22.9.3
%QW22.10.2
%QW22.10.3
%QW22.11.2
Channel Description
1
2
Data content (16 bits = word)
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
3
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
2
3
1st channel S/A slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
4 status
0 1st channel S/A slave
1
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0 1st channel S/A slave
1
2
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4-48
Slave address
6
7
8
9
10
11
Function
Project transmission and diagnosis via Ethernet interface
Master 1 inputs
IEC addresses
(PLC in controllere)
Master 1 outputs
Master 2 inputs
Master 2 outputs
%IW21.11.3 %QW21.11.3 %IW22.11.3 %QW22.11.3
Data content (16 bits = word)
Channel Description
%IW21.11.4 %QW21.11.4 %IW22.11.4 %QW22.11.4
%IW21.12.0 %QW21.12.0 %IW22.12.0 %QW22.12.0
%IW21.12.1
%IW21.12.2
%IW21.12.3
%IW21.12.4 %QW21.12.4 %IW22.12.4 %QW22.12.4
%IW21.13.0 %QW21.13.0 %IW22.13.0 %QW22.13.0
%IW21.13.1 %QW21.13.1 %IW22.13.1 %QW22.13.1
%IW21.13.2
%IW21.13.3
%IW21.15.2
%QW21.13.2
%QW21.13.3
%QW21.15.2
%IW22.13.2
%IW22.13.3
%IW22.15.2
%QW22.13.2
%QW22.13.3
%IW21.13.4 %QW21.13.4 %IW22.13.4 %QW22.13.4
%IW21.14.0 %QW21.14.0 %IW22.14.0 %QW22.14.0
%IW21.14.1 %QW21.14.1 %IW22.14.1 %QW22.14.1
%IW21.14.2
%IW21.14.3
%IW21.14.4 %QW21.14.4 %IW22.14.4 %QW22.14.4
%IW21.15.0 %QW21.15.0 %IW22.15.0 %QW22.15.0
%IW21.15.1 %QW21.15.1 %IW22.15.1 %QW22.15.1
%IW21.15.3
%IW21.17.2
%QW21.14.2
%QW21.14.3
%QW21.15.3
%QW21.16.2
%QW21.17.2
%IW22.14.2
%IW22.14.3
%IW22.15.3
%IW22.16.2
%IW22.17.2
%QW22.14.2
%QW22.14.3
%QW22.15.2
%QW22.15.3
%IW21.15.4 %QW21.15.4 %IW22.15.4 %QW22.15.4
%IW21.16.0 %QW21.16.0 %IW22.16.0 %QW22.16.0
%IW21.16.1 %QW21.16.1 %IW22.16.1 %QW22.16.1
%IW21.16.2
%IW21.16.3
%QW21.12.1
%QW21.12.2
%QW21.12.3
%QW21.16.3
%IW22.12.1
%IW22.12.2
%IW22.12.3
%IW22.16.3
%QW22.12.1
%QW22.12.2
%QW22.12.3
%QW22.16.2
%QW22.16.3
%IW21.16.4 %QW21.16.4 %IW22.16.4 %QW22.16.4
%IW21.17.0 %QW21.17.0 %IW22.17.0 %QW22.17.0
%IW21.17.1 %QW21.17.1 %IW22.17.1 %QW22.17.1
%QW22.17.2
%IW21.17.3 %QW21.17.3 %IW22.17.3 %QW22.17.3
%IW21.17.4 %QW21.17.4 %IW22.17.4 %QW22.17.4
%IW21.18.0 %QW21.18.0 %IW22.18.0 %QW22.18.0
3
4th channel single slave or:
2nd channel B slave
4 status
0
1
2
3
1st channel S/A slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
4 status
0 1st channel S/A slave
1
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0 1st channel S/A slave
1
2
3
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0 1st channel S/A slave
1
2
3
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0 1st channel S/A slave
Slave address
12
13
14
15
16
17
18
4-49
Function
Project transmission and diagnosis via Ethernet interface
Master 1 inputs
IEC addresses
(PLC in controllere)
Master 1 outputs
Master 2 inputs
Master 2 outputs
%IW21.18.1 %QW21.18.1 %IW22.18.1 %QW22.18.1
Data content (16 bits = word)
Channel Description
%IW21.18.2
%IW21.18.3
%IW21.18.4
%IW21.19.0
%IW21.19.1
%IW21.19.2
%IW21.19.3
%IW21.19.4
%IW21.20.0
%IW21.20.1
%IW21.20.2
%IW21.20.3
%IW21.20.4
%IW21.21.0
%IW21.21.1
%IW21.21.2
%IW21.21.3
%IW21.21.4
%IW21.22.0
%IW21.22.1
%IW21.22.2
%IW21.22.3
%IW21.22.4
%IW21.23.0 %QW21.23.0 %IW22.23.0 %QW22.23.0
%IW21.23.1 %QW21.23.1 %IW22.23.1 %QW22.23.1
%IW21.23.2
%IW21.23.3
%IW21.23.4
%QW21.22.4
%QW21.23.4
%IW22.22.4
%IW22.23.4
%QW22.22.4
%QW22.23.4
%IW21.24.0 %QW21.24.0 %IW22.24.0 %QW22.24.0
%IW21.24.1 %QW21.24.1 %IW22.24.1 %QW22.24.1
%IW21.24.2
%QW21.18.2
%QW21.18.3
%QW21.18.4
%QW21.19.0
%QW21.19.1
%QW21.19.2
%QW21.19.3
%QW21.19.4
%QW21.20.0
%QW21.20.1
%QW21.20.2
%QW21.20.3
%QW21.20.4
%QW21.21.0
%QW21.21.1
%QW21.21.2
%QW21.21.3
%QW21.21.4
%QW21.22.0
%QW21.22.1
%QW21.22.2
%QW21.22.3
%QW21.23.2
%QW21.23.3
%QW21.24.2
%IW22.18.2
%IW22.18.3
%IW22.18.4
%IW22.19.0
%IW22.19.1
%IW22.19.2
%IW22.19.3
%IW22.19.4
%IW22.20.0
%IW22.20.1
%IW22.20.2
%IW22.20.3
%IW22.20.4
%IW22.21.0
%IW22.21.1
%IW22.21.2
%IW22.21.3
%IW22.21.4
%IW22.22.0
%IW22.22.1
%IW22.22.2
%IW22.22.3
%IW22.23.2
%IW22.23.3
%IW22.24.2
%QW22.18.2
%QW22.18.3
%QW22.18.4
%QW22.19.0
%QW22.19.1
%QW22.19.2
%QW22.19.3
%QW22.19.4
%QW22.20.0
%QW22.20.1
%QW22.20.2
%QW22.20.3
%QW22.20.4
%QW22.21.0
%QW22.21.1
%QW22.21.2
%QW22.21.3
%QW22.21.4
%QW22.22.0
%QW22.22.1
%QW22.22.2
%QW22.22.3
%QW22.23.2
%QW22.23.3
%QW22.24.2
1
2
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
3
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
2
3
1st channel S/A slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
4 status
0 1st channel S/A slave
1
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0 1st channel S/A slave
1
2
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4-50
Slave address
19
20
21
22
23
24
Function
Project transmission and diagnosis via Ethernet interface
Master 1 inputs
IEC addresses
(PLC in controllere)
Master 1 outputs
Master 2 inputs
Master 2 outputs
%IW21.24.3 %QW21.24.3 %IW22.24.3 %QW22.24.3
Data content (16 bits = word)
Channel Description
%IW21.24.4 %QW21.24.4 %IW22.24.4 %QW22.24.4
%IW21.25.0 %QW21.25.0 %IW22.25.0 %QW22.25.0
%IW21.25.1
%IW21.25.2
%IW21.25.3
%IW21.25.4 %QW21.25.4 %IW22.25.4 %QW22.25.4
%IW21.26.0 %QW21.26.0 %IW22.26.0 %QW22.26.0
%IW21.26.1 %QW21.26.1 %IW22.26.1 %QW22.26.1
%IW21.26.2
%IW21.26.3
%IW21.28.2
%QW21.26.2
%QW21.26.3
%QW21.28.2
%IW22.26.2
%IW22.26.3
%IW22.28.2
%QW22.26.2
%QW22.26.3
%IW21.26.4 %QW21.26.4 %IW22.26.4 %QW22.26.4
%IW21.27.0 %QW21.27.0 %IW22.27.0 %QW22.27.0
%IW21.27.1 %QW21.27.1 %IW22.27.1 %QW22.27.1
%IW21.27.2
%IW21.27.3
%IW21.27.4 %QW21.27.4 %IW22.27.4 %QW22.27.4
%IW21.28.0 %QW21.28.0 %IW22.28.0 %QW22.28.0
%IW21.28.1 %QW21.28.1 %IW22.28.1 %QW22.28.1
%IW21.28.3
%IW21.30.2
%QW21.27.2
%QW21.27.3
%QW21.28.3
%QW21.29.2
%QW21.30.2
%IW22.27.2
%IW22.27.3
%IW22.28.3
%IW22.29.2
%IW22.30.2
%QW22.27.2
%QW22.27.3
%QW22.28.2
%QW22.28.3
%IW21.28.4 %QW21.28.4 %IW22.28.4 %QW22.28.4
%IW21.29.0 %QW21.29.0 %IW22.29.0 %QW22.29.0
%IW21.29.1 %QW21.29.1 %IW22.29.1 %QW22.29.1
%IW21.29.2
%IW21.29.3
IW21.29.4
%QW21.25.1
%QW21.25.2
%QW21.25.3
%QW21.29.3
IW21.29.4
%IW22.25.1
%IW22.25.2
%IW22.25.3
%IW22.29.3
IW22.29.4
%QW22.25.1
%QW22.25.2
%QW22.25.3
%QW22.29.2
%QW22.29.3
IW22.29.4
%IW21.30.0 %QW21.30.0 %IW22.30.0 %QW22.30.0
%IW21.30.1 %QW21.30.1 %IW22.30.1 %QW22.30.1
%QW22.30.2
%IW21.30.3 %QW21.30.3 %IW22.30.3 %QW22.30.3
%IW21.30.4 %QW21.30.4 %IW22.30.4 %QW22.30.4
%IW21.31.0 %QW21.31.0 %IW22.31.0 %QW22.31.0
3
4th channel single slave or:
2nd channel B slave
4 status
0
1
2
3
1st channel S/A slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0
1
1st channel S/A slave
2nd channel S/A slave
2
3
4 status
0 1st channel S/A slave
1
2
3
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0 1st channel S/A slave
1
2
3
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0 1st channel S/A slave
1
2
3
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
4th channel single slave or:
2nd channel B slave
4 status
0 1st channel S/A slave
Slave address
25
26
27
28
29
30
31
4-51
Function
Project transmission and diagnosis via Ethernet interface
Master 1 inputs
IEC addresses
(PLC in controllere)
Master 1 outputs
Master 2 inputs
Master 2 outputs
%IW21.31.1 %QW21.31.1 %IW22.31.1 %QW22.31.1
Data content (16 bits = word)
Channel Description
%IW21.31.2
%IW21.31.3
%IW21.31.4
%QW21.31.2
%QW21.31.3
%QW21.31.4
%IW22.31.2
%IW22.31.3
%IW22.31.4
%QW22.31.2
%QW22.31.3
%QW22.31.4
1
2
2nd channel S/A slave
3rd channel single slave or:
1st channel B slave
3
4th channel single slave or:
2nd channel B slave
4 status
Slave address
4-52
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for configuration data (CDI) of the slaves
CDI = Configuration Data Image
Modbus addresses Bits / data content
Master 1 Master 2
15…12
XID2 current projected current projected
4285 4381 8381 8477
11…8
XID1
7…4
ID
0
3…0
IO configuration data of slave
4286 4382 8382 8478
4287 4383 8383 8479
4288 4384 8384 8480
4289 4385 8385 8481
4290 4386 8386 8482
4291 4387 8387 8483
4292 4388 8388 8484
4293 4389 8389 8485
4294 4390 8390 8486
4295 4391 8391 8487
4296 4392 8392 8488
4297 4393 8393 8489
4298 4394 8394 8490
4299 4395 8395 8491
4300 4396 8396 8492
4301 4397 8397 8493
4302 4398 8398 8494
4303 4399 8399 8495
4304 4400 8400 8496
4305 4401 8401 8497
4306 4402 8402 8498
4307 4403 8403 8499
4308 4404 8404 8500
4309 4405 8405 8501
4310 4406 8406 8502
4311 4407 8407 8503
4312 4408 8408 8504
4313 4409 8409 8505
4314 4410 8410 8506
4315 4411 8411 8507
4316 4412 8412 8508
4317 4413 8413 8509
4318 4414 8414 8510
4319 4415 8415 8511
4320 4416 8416 8512
4321 4417 8417 8513
4322 4418 8418 8514
IEC addresses
(PLC in controllere)
Master 1 Master 2 current projected current projected
%IW31.0 %IW31.96 %IW32.0 %IW32.96
%IW31.1 %IW31.97 %IW32.1 %IW32.97
%IW31.2 %IW31.98 %IW32.2 %IW32.98
%IW31.3 %IW31.99 %IW32.3 %IW32.99
%IW31.4 %IW31.100 %IW32.4 %IW32.100
%IW31.5 %IW31.101 %IW32.5 %IW32.101
%IW31.6 %IW31.102 %IW32.6 %IW32.102
%IW31.7 %IW31.103 %IW32.7 %IW32.103
%IW31.8 %IW31.104 %IW32.8 %IW32.104
%IW31.9 %IW31.105 %IW32.9 %IW32.105
%IW31.10 %IW31.106 %IW32.10 %IW32.106
%IW31.11 %IW31.107 %IW32.11 %IW32.107
%IW31.12 %IW31.108 %IW32.12 %IW32.108
%IW31.13 %IW31.109 %IW32.13 %IW32.109
%IW31.14 %IW31.110 %IW32.14 %IW32.110
%IW31.15 %IW31.111 %IW32.15 %IW32.111
%IW31.16 %IW31.112 %IW32.16 %IW32.112
%IW31.17 %IW31.113 %IW32.17 %IW32.113
%IW31.18 %IW31.114 %IW32.18 %IW32.114
%IW31.19 %IW31.115 %IW32.19 %IW32.115
%IW31.20 %IW31.116 %IW32.20 %IW32.116
%IW31.21 %IW31.117 %IW32.21 %IW32.117
%IW31.22 %IW31.118 %IW32.22 %IW32.118
%IW31.23 %IW31.119 %IW32.23 %IW32.119
%IW31.24 %IW31.120 %IW32.24 %IW32.120
%IW31.25 %IW31.121 %IW32.25 %IW32.121
%IW31.26 %IW31.122 %IW32.26 %IW32.122
%IW31.27 %IW31.123 %IW32.27 %IW32.123
%IW31.28 %IW31.124 %IW32.28 %IW32.124
%IW31.29 %IW31.125 %IW32.29 %IW32.125
%IW31.30 %IW31.126 %IW32.30 %IW32.126
%IW31.31 %IW31.127 %IW32.31 %IW32.127
%IW31.32 %IW31.128 %IW32.32 %IW32.128
%IW31.33 %IW31.129 %IW32.33 %IW32.129
%IW31.34 %IW31.130 %IW32.34 %IW32.130
%IW31.35 %IW31.131 %IW32.35 %IW32.131
%IW31.36 %IW31.132 %IW32.36 %IW32.132
%IW31.37 %IW31.133 %IW32.37 %IW32.133
4-53
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses Bits / data content
IEC addresses
(PLC in controllere)
Master 1 Master 2
15…12
XID2 current projected current projected
4323 4419 8419 8515
4324 4420 8420 8516
4325 4421 8421 8517
4326 4422 8422 8518
4327 4423 8423 8519
4328 4424 8424 8520
11…8
XID1
7…4
ID
3…0
IO configuration data of slave
Master 1 Master 2 current projected current projected
%IW31.38 %IW31.134 %IW32.38 %IW32.134
%IW31.39 %IW31.135 %IW32.39 %IW32.135
%IW31.40 %IW31.136 %IW32.40 %IW32.136
%IW31.41 %IW31.137 %IW32.41 %IW32.137
%IW31.42 %IW31.138 %IW32.42 %IW32.138
%IW31.43 %IW31.139 %IW32.43 %IW32.139
%IW31.44 %IW31.140 %IW32.44 %IW32.140
4329 4425 8425 8521
4330 4426 8426 8522
4331 4427 8427 8523
4332 4428 8428 8524
4333 4429 8429 8525
4334 4430 8430 8526
4335 4431 8431 8527
%IW31.45 %IW31.141 %IW32.45 %IW32.141
%IW31.46 %IW31.142 %IW32.46 %IW32.142
%IW31.47 %IW31.143 %IW32.47 %IW32.143
%IW31.48 %IW31.144 %IW32.48 %IW32.144
%IW31.49 %IW31.145 %IW32.49 %IW32.145
%IW31.50 %IW31.146 %IW32.50 %IW32.146
%IW31.51 %IW31.147 %IW32.51 %IW32.147
4336 4432 8432 8528
4337 4433 8433 8529
4338 4434 8434 8530
4339 4435 8435 8531
4340 4436 8436 8532
4341 4437 8437 8533
%IW31.52 %IW31.148 %IW32.52 %IW32.148
%IW31.53 %IW31.149 %IW32.53 %IW32.149
%IW31.54 %IW31.150 %IW32.54 %IW32.150
%IW31.55 %IW31.151 %IW32.55 %IW32.151
%IW31.56 %IW31.152 %IW32.56 %IW32.152
4342 4438 8438 8534
4343 4439 8439 8535
%IW31.57 %IW31.153 %IW32.57 %IW32.153
%IW31.58 %IW31.154 %IW32.58 %IW32.154
4344 4440 8440 8536
4345 4441 8441 8537
4346 4442 8442 8538
4347 4443 8443 8539
4348 4444 8444 8540
%IW31.59 %IW31.155 %IW32.59 %IW32.155
%IW31.60 %IW31.156 %IW32.60 %IW32.156
%IW31.61 %IW31.157 %IW32.61 %IW32.157
%IW31.62 %IW31.158 %IW32.62 %IW32.158
%IW31.63 %IW31.159 %IW32.63 %IW32.159
*) For the AS-i address 0B there is no configuration data. The value of this field is always zero.
IEC addresses in the PLC of the controllere for configuration data (CDI) of the slaves
CDI = Configuration Data Image
Data area Type of access
% I W 31. 8
Identification IEC address index
I = input W = word
31 = master 1
32 = master 2
0…63
96…159 current configuration projected configuration
––
not used
4-54
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for parameter data of the slaves
Modbus addresses Bits
Master 1 current reflected
Master 2 current reflected
15…12 11…8 7…4 3…0 parameter data of slave
IEC addresses
(PLC in controllere)
Master 1 current reflected
Master 2 current reflected
4351 4447 8447 8543
%IW31.66 %IW31.162 %IW32.66 %IW32.162
4352 4448 8448 8544 %IW31.67 %IW31.163 %IW32.67 %IW32.163
4353 4449 8449 8545
%IW31.68 %IW31.164 %IW32.68 %IW32.164
4354 4450 8450 8546 %IW31.69 %IW31.165 %IW32.69 %IW32.165
4355 4451 8451 8547
%IW31.70 %IW31.166 %IW32.70 %IW32.166
4356 4452 8452 8548 1B %IW31.71 %IW31.167 %IW32.71 %IW32.167
IEC addresses in the PLC of the controllere for parameter data of the slaves
% I W 31. 64
Data area Type of access
Identification IEC address index
I = input W = word
31 = master 1
32 = master 2
64….79
160…175 current parameters reflected parameters
––
not used
4-55
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the slave list LAS (list of active slaves)
Modbus addresses
IEC addresses
(PLC in controllere)
Master 1 Master 2 15 14 13 12 11 10
Bits
AS-i slave addresses
9 8 7 6 5 4 3 2 1 0
4365
%IW31.80
4366
%IW31.81
4367
%IW31.82
8461
%IW32.80
8462
%IW32.81
8463
%IW32.82
15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0*)
31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)
15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B —
4368
%IW31.83
8464
%IW32.83
31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B
*) LAS has no slave 0, so these values are set to 0 by default!
IEC addresses in the PLC of the controllere for the slave list LAS (list of active slaves)
Data area Type of access
% I W 31. 80
Identification Slave selection ––
I = input W = word
31 = master 1
32 = master 2
80 = LAS of the slaves 1(A)…15(A)
81 = LAS of the slaves 16(A)…31(A)
82 = LAS of the slaves 1B…15B
83 = LAS of the slaves 16B…31B not used
4-56
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the slave list LDS (list of detected slaves)
Modbus addresses
IEC addresses
(PLC in controllere)
Master 1 Master 2 15 14 13 12 11 10
Bits
AS-i slave addresses
9 8 7 6
4369
%IW31.84
4370
%IW31.85
4371
%IW31.86
4372
%IW31.87
5 4 3 2 1 0
8465
%IW32.84
8466
%IW32.85
8467
%IW32.86
8468
%IW32.87
15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0
31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)
15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B —
31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B
IEC addresses in the PLC of the controllere for the slave list LDS
(list of detected slaves)
% I W 31. 84
Data area Type of access
Identification Slave selection
I = input W = word
31 = master 1
32 = master 2
84 = LDS of the slaves 1(A)…15(A)
85 = LDS of the slaves 16(A)…31(A)
86 = LDS of the slaves 1B…15B
87 = LDS of the slaves 16B…31B
––
not used
4-57
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the slave list LPF (list of slaves with periphery faults)
Modbus addresses
IEC addresses
(PLC in controllere)
Master 1 Master 2 15 14 13 12 11 10
Bits
AS-i slave addresses
9 8 7 6 5 4 3 2 1 0
4373
%IW31.88
4374
%IW31.89
4375
%IW31.90
8469
%IW32.88
8470
%IW32.89
8471
%IW32.90
15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0*)
31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)
15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B —
4376
%IW31.91
8472
%IW32.91
31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B
*) LPF has no slave 0, so these values are set to 0 by default!
IEC addresses in the PLC of the controllere for the slave list LPF
(list of slaves with periphery faults)
% I W 31. 88
Data area Type of access
Identification Slave selection
I = input W = word
31 = master 1
32 = master 2
88 = LPF of the slaves 1(A)…15(A)
89 = LPF of the slaves 16(A)…31(A)
90 = LPF of the slaves 1B…15B
91 = LPF of the slaves 16B…31B
––
not used
4-58
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the slave list LPS (list of projected slaves)
Modbus addresses
IEC addresses
(PLC in controllere)
Master 1 Master 2 15 14 13 12 11 10
Bits
AS-i slave addresses
9 8 7 6 5 4 3 2 1 0
4377
%IW3192
4378
%IW31.93
4379
%IW31.94
8473
%IW32.92
8474
%IW32.93
8475
%IW32.94
15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0*)
31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)
15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B —
4380
%IW31.95
8476
%IW32.95
31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B
*) LPS has no slave 0, so these values are set to 0 by default!
IEC addresses in the PLC of the controllere for the slave list LPS
(list of projected slaves)
% I W 31. 92
Data area Type of access
Identification Slave selection
I = input W = word
31 = master 1
32 = master 2
92 = LPS of the slaves 1(A)…15(A)
93 = LPS of the slaves 16(A)…31(A)
94 = LPS of the slaves 1B…15B
95 = LPS of the slaves 16B…31B
––
not used
4-59
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the slave telegram error counters
Modbus addresses
Master 1
4494
4495
4496
4497
4498
4499
4500
4501
4484
4485
4486
4487
4488
4489
4490
4491
4492
4493
4473
4474
4475
4476
4477
4478
4479
4480
4481
4482
4483
4467
4468
4469
4470
4471
4472
4461
4462
4463
4464
4465
4466
Master 2
8590
8591
8592
8593
8594
8595
8596
8597
8580
8581
8582
8583
8584
8585
8586
8587
8588
8589
8569
8570
8571
8572
8573
8574
8575
8576
8577
8578
8579
8563
8564
8565
8566
8567
8568
8557
8558
8559
8560
8561
8562
Telegram error counter of slave
(16 bits = 1 word)
3 B
4 B
5 B
6 B
7 B
8 B
9 B
10 B
24 (A)
25 (A)
26 (A)
27 (A)
28 (A)
29 (A)
30 (A)
31 (A)
1 B
2 B
13 (A)
14 (A)
15 (A)
16 (A)
17 (A)
18 (A)
19 (A)
20 (A)
21 (A)
22 (A)
23 (A)
7 (A)
8 (A)
9 (A)
10 (A)
11 (A)
12 (A)
1 (A)
2 (A)
3 (A)
4 (A)
5 (A)
6 (A)
4-60
IEC addresses
(PLC in controllere)
Master 1 Master 2
%IW31.176 %IW32.176
%IW31.177 %IW32.177
%IW31.178 %IW32.178
%IW31.179 %IW32.179
%IW31.180 %IW32.180
%IW31.181 %IW32.181
%IW31.182 %IW32.182
%IW31.183 %IW32.183
%IW31.184 %IW32.184
%IW31.185 %IW32.185
%IW31.186 %IW32.186
%IW31.187 %IW32.187
%IW31.188 %IW32.188
%IW31.189 %IW32.189
%IW31.190 %IW32.190
%IW31.191 %IW32.191
%IW31.192 %IW32.192
%IW31.193 %IW32.193
%IW31.194 %IW32.194
%IW31.195 %IW32.195
%IW31.196 %IW32.196
%IW31.197 %IW32.197
%IW31.198 %IW32.198
%IW31.199 %IW32.199
%IW31.200 %IW32.200
%IW31.201 %IW32.201
%IW31.202 %IW32.202
%IW31.203 %IW32.203
%IW31.204 %IW32.204
%IW31.205 %IW32.205
%IW31.206 %IW32.206
%IW31.207 %IW32.207
%IW31.208 %IW32.208
%IW31.209 %IW32.209
%IW31.210 %IW32.210
%IW31.211 %IW32.211
%IW31.212 %IW32.212
%IW31.213 %IW32.213
%IW31.214 %IW32.214
%IW31.215 %IW32.215
%IW31.216 %IW32.216
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses
Master 1
4512
4513
4514
4515
4516
4517
4518
4519
4520
4521
4522
4502
4503
4504
4505
4506
4507
4508
4509
4510
4511
Master 2
8608
8609
8610
8611
8612
8613
8614
8615
8616
8617
8618
8598
8599
8600
8601
8602
8603
8604
8605
8606
8607
Telegram error counter of slave
(16 bits = 1 word)
26 B
27 B
28 B
29 B
30 B
31 B
21 B
22 B
23 B
24 B
25 B
16 B
17 B
18 B
19 B
20 B
11 B
12 B
13 B
14 B
15 B
IEC addresses
(PLC in controllere)
Master 1 Master 2
%IW31.217 %IW32.217
%IW31.218 %IW32.218
%IW31.219 %IW32.219
%IW31.220 %IW32.220
%IW31.221 %IW32.221
%IW31.222 %IW32.222
%IW31.223 %IW32.223
%IW31.224 %IW32.224
%IW31.225 %IW32.225
%IW31.226 %IW32.226
%IW31.227 %IW32.227
%IW31.228 %IW32.228
%IW31.229 %IW32.229
%IW31.230 %IW32.230
%IW31.231 %IW32.231
%IW31.2xx %IW32.2xx
%IW31.233 %IW32.233
%IW31.234 %IW32.234
%W31.235 %W32.235
%IW31.236 %IW32.236
%IW31.237 %IW32.237
IEC addresses in the PLC of the controllere for the slave telegram error counter
% I W 31. 176
Data area Type of access
Identification IEC address index
I = input W = word
31 = master 1
32 = master 2
––
176…237 = error counter of the slaves 1(A)…31B not used
4-61
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the configuration error counter
Modbus addresses
Master 1
4523
Master 2
8619
Configuration error counter of AS-i master
(16 bits = 1 word)
configuration error counter of AS-i master
IEC addresses
(PLC in controllere)
Master 1 Master 2
%IW31.238 %IW32.238
IEC addresses in the PLC of the controllere for the configuration error counter
% I W 31. 238
Data area Type of access
Identification IEC address index
I = input W = word
31 = master 1
32 = master 2
238 = configuration error counter
––
not used
Modbus addresses for the AS-i cycle counter
Modbus addresses
Master 1
4524
Master 2
8620
AS-i cycle counter of AS-i master
(16 bits = 1 word)
AS-i cycle counter of AS-i master
IEC addresses in the PLC of the controllere for the AS-i cycle counter
Data area Type of access
% I W 31. 239
Identification IEC address index
I = input W = word
31 = master 1
32 = master 2
239 = AS-i cycle counter
IEC addresses
(PLC in controllere)
Master 1 Master 2
%IW31.239 %IW32.239
––
not used
4-62
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the request data of the host command channel
Modbus addresses Bit
Master 1 Master 2 15 14 13 12 11 10 9 8 7 6 5
echo byte of the request
4 3
request / status
2
4794 8890
4795 8891
4796 8892
4797 8893
4798 8894
4799 8895
4800 8896
4801 8897
4802 8898
4803 8899
4804 8900
4805 8901
4806 8902
4807 8903
4808 8904
4809 8905
4810 8906
4811 8907
4812 8908 reserved
1 0
4-63
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the response data of the host command channel
Modbus addresses Bit
Master 1 Master 2 15 14 13 12 11 10 9 8 7 6 5
4813 8909
4814 8910
4815 8911
4816 8912
4817 8913
4818 8914
4819 8915
4820 8916
4821 8917
4822 8918
4823 8919
4824 8920
4825 8921
4826 8922
4827 8923
4828 8924
4829 8925
4830 8926
4831 8927 echo byte of the response reserved
4 3
status
2 1 0
4-64
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the fieldbus data from/to the PLC of the controllere
Modbus addresses
Data to the
PLC
Data from the PLC
Data content
(16 bits = 1 word)
IEC addresses
(PLC in controllere)
Data to the
PLC
Data from the PLC
12318
12319
12320
12321
12322
12323
12324
12325
12326
12327
12328
12308
12309
12310
12311
12312
12313
12314
12315
12316
12317
12298
12299
12300
12301
12302
12303
12304
12305
12306
12307
12288
12289
12290
12291
12292
12293
12294
12295
12296
12297
%QW0.30
%QW0.31
%QW0.32
%QW0.33
%QW0.34
%QW0.35
%QW0.36
%QW0.37
%QW0.38
%QW0.39
%QW0.40
%QW0.20
%QW0.21
%QW0.22
%QW0.23
%QW0.24
%QW0.25
%QW0.26
%QW0.27
%QW0.28
%QW0.29
%QW0.10
%QW0.11
%QW0.12
%QW0.13
%QW0.14
%QW0.15
%QW0.16
%QW0.17
%QW0.18
%QW0.19
%QW0.0
%QW0.1
%QW0.2
%QW0.3
%QW0.4
%QW0.5
%QW0.6
%QW0.7
%QW0.8
%QW0.9
4-65
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses
Data content
(16 bits = 1 word)
Data to the
PLC
12338
12339
12340
12341
12342
12343
12344
12345
12346
12347
12348
12349
12350
12351
12329
12330
12331
12332
12333
12334
12335
12336
12337
Data from the PLC
IEC addresses in the PLC of the controllere for the fieldbus data from/to the PLC of the controllere
Data area Type of access
% I W 0. 10
% Q W 0. 20
Identification IEC address index
I = input
Q = output
W = word 0 (fixed value) 0…63 = word x of the data field
––
not used
IEC addresses
(PLC in controllere)
Data to the
PLC
Data from the PLC
%QW0.50
%QW0.51
%QW0.52
%QW0.53
%QW0.54
%QW0.55
%QW0.56
%QW0.57
%QW0.58
%QW0.59
%QW0.60
%QW0.61
%QW0.62
%QW0.63
%QW0.41
%QW0.42
%QW0.43
%QW0.44
%QW0.45
%QW0.46
%QW0.47
%QW0.48
%QW0.49
4-66
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses for the extended data from/to the PLC of the controllere
Modbus addresses
Data to the
PLC
Data from the PLC
Data content
(16 bits = 1 word)
IEC addresses
(PLC in controllere)
Data to the
PLC
Data from the PLC
12446
12447
12448
12449
12450
12451
12452
12453
12454
12455
12456
12436
12437
12438
12439
12440
12441
12442
12443
12444
12445
12426
12427
12428
12429
12430
12431
12432
12433
12434
12435
12416
12417
12418
12419
12420
12421
12422
12423
12424
12425
%QW4.30
%QW4.31
%QW4.32
%QW4.33
%QW4.34
%QW4.35
%QW4.36
%QW4.37
%QW4.38
%QW4.39
%QW4.40
%QW4.20
%QW4.21
%QW4.22
%QW4.23
%QW4.24
%QW4.25
%QW4.26
%QW4.27
%QW4.28
%QW4.29
%QW4.10
%QW4.11
%QW4.12
%QW4.13
%QW4.14
%QW4.15
%QW4.16
%QW4.17
%QW4.18
%QW4.19
%QW4.0
%QW4.1
%QW4.2
%QW4.3
%QW4.4
%QW4.5
%QW4.6
%QW4.7
%QW4.8
%QW4.9
4-67
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses
Data to the
PLC
12466
12467
12468
12469
12470
12471
12472
12473
12474
12475
12476
12477
12457
12458
12459
12460
12461
12462
12463
12464
12465
12478
12479
12480
12481
12482
12483
12484
12485
12486
12487
12488
12489
12490
12491
12492
12493
12494
12495
12496
12497
12498
Data from the PLC
4-68
Data content
(16 bits = 1 word)
IEC addresses
(PLC in controllere)
Data to the
PLC
Data from the PLC
%QW4.50
%QW4.51
%QW4.52
%QW4.53
%QW4.54
%QW4.55
%QW4.56
%QW4.57
%QW4.58
%QW4.59
%QW4.60
%QW4.61
%QW4.41
%QW4.42
%QW4.43
%QW4.44
%QW4.45
%QW4.46
%QW4.47
%QW4.48
%QW4.49
%QW4.62
%QW4.63
%QW4.64
%QW4.65
%QW4.66
%QW4.67
%QW4.68
%QW4.69
%QW4.70
%QW4.71
%QW4.72
%QW4.73
%QW4.74
%QW4.75
%QW4.76
%QW4.77
%QW4.78
%QW4.79
%QW4.80
%QW4.81
%QW4.82
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses
Data to the
PLC
12508
12509
12510
12511
12512
12513
12514
12515
12516
12517
12518
12519
12499
12500
12501
12502
12503
12504
12505
12506
12507
12520
12521
12522
12523
12524
12525
12526
12527
12528
12529
12530
12531
12532
12533
12534
12535
12536
12537
12538
12539
12540
Data from the PLC
Data content
(16 bits = 1 word)
IEC addresses
(PLC in controllere)
Data to the
PLC
Data from the PLC
%QW4.83
%QW4.84
%QW4.85
%QW4.86
%QW4.87
%QW4.88
%QW4.89
%QW4.90
%QW4.91
%QW4.92
%QW4.93
%QW4.94
%QW4.95
%QW4.96
%QW4.97
%QW4.98
%QW4.99
%QW4.100
%QW4.101
%QW4.102
%QW4.103
%QW4.104
%QW4.105
%QW4.106
%QW4.107
%QW4.108
%QW4.109
%QW4.110
%QW4.111
%QW4.112
%QW4.113
%QW4.114
%QW4.115
%QW4.116
%QW4.117
%QW4.118
%QW4.119
%QW4.120
%QW4.121
%QW4.122
%QW4.123
%QW4.124
4-69
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses
Data to the
PLC
12550
12551
12552
12553
12554
12555
12556
12557
12558
12559
12560
12561
12541
12542
12543
12544
12545
12546
12547
12548
12549
12562
12563
12564
12565
12566
12567
12568
12569
12570
12571
12572
12573
12574
12575
12576
12577
12578
12579
12580
12581
12582
Data from the PLC
4-70
Data content
(16 bits = 1 word)
IEC addresses
(PLC in controllere)
Data to the
PLC
Data from the PLC
%QW4.125
%QW4.126
%QW4.127
%QW4.128
%QW4.129
%QW4.130
%QW4.131
%QW4.132
%QW4.133
%QW4.134
%QW4.135
%QW4.136
%QW4.137
%QW4.138
%QW4.139
%QW4.140
%QW4.141
%QW4.142
%QW4.143
%QW4.144
%QW4.145
%QW4.146
%QW4.147
%QW4.148
%QW4.149
%QW4.150
%QW4.151
%QW4.152
%QW4.153
%QW4.154
%QW4.155
%QW4.156
%QW4.157
%QW4.158
%QW4.159
%QW4.160
%QW4.161
%QW4.162
%QW4.163
%QW4.164
%QW4.165
%QW4.166
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses
Data to the
PLC
12592
12593
12594
12595
12596
12597
12598
12599
12600
12601
12602
12603
12583
12584
12585
12586
12587
12588
12589
12590
12591
12604
12605
12606
12607
12608
12609
12610
12611
12612
12613
12614
12615
12616
12617
12618
12619
12620
12621
12622
12623
12624
Data from the PLC
Data content
(16 bits = 1 word)
IEC addresses
(PLC in controllere)
Data to the
PLC
Data from the PLC
%QW4.167
%QW4.168
%QW4.169
%QW4.170
%QW4.171
%QW4.172
%QW4.173
%QW4.174
%QW4.175
%QW4.176
%QW4.177
%QW4.178
%QW4.179
%QW4.180
%QW4.181
%QW4.182
%QW4.183
%QW4.184
%QW4.185
%QW4.186
%QW4.187
%QW4.188
%QW4.189
%QW4.190
%QW4.191
%QW4.192
%QW4.193
%QW4.194
%QW4.195
%QW4.196
%QW4.197
%QW4.198
%QW4.199
%QW4.200
%QW4.201
%QW4.202
%QW4.203
%QW4.204
%QW4.205
%QW4.206
%QW4.207
%QW4.208
4-71
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses
Data to the
PLC
12634
12635
12636
12637
12638
12639
12640
12641
12642
12643
12644
12645
12625
12626
12627
12628
12629
12630
12631
12632
12633
12646
12647
12648
12649
12650
12651
12652
12653
12654
12655
12656
12657
12658
12659
12660
12661
12662
12663
12664
12665
12666
Data from the PLC
4-72
Data content
(16 bits = 1 word)
IEC addresses
(PLC in controllere)
Data to the
PLC
Data from the PLC
%QW4.209
%QW4.210
%QW4.211
%QW4.212
%QW4.213
%QW4.214
%QW4.215
%QW4.216
%QW4.217
%QW4.218
%QW4.219
%QW4.220
%QW4.221
%QW4.222
%QW4.223
%QW4.224
%QW4.225
%QW4.226
%QW4.227
%QW4.228
%QW4.229
%QW4.230
%QW4.231
%QW4.232
%QW4.233
%QW4.234
%QW4.235
%QW4.236
%QW4.237
%QW4.238
%QW4.239
%QW4.240
%QW4.241
%QW4.242
%QW4.243
%QW4.244
%QW4.245
%QW4.246
%QW4.247
%QW4.248
%QW4.249
%QW4.250
Function
Project transmission and diagnosis via Ethernet interface
Modbus addresses
Data to the
PLC
12667
12668
12669
12670
12671
Data from the PLC
Data content
(16 bits = 1 word)
IEC addresses
(PLC in controllere)
Data to the
PLC
Data from the PLC
%QW4.251
%QW4.252
%QW4.253
%QW4.254
%QW4.255
IEC addresses in the PLC of the controllere for the extended data from/to the PLC of the controllere
% Q W 4. 27
Identification IEC address index Data area
I = input
Q = output
Type of access
W = word 4 (fixed value) 0…255 = word x of the data field
––
not used
4-73
4-74
Function
Project transmission and diagnosis via Ethernet interface
4.5.4 Data exchange HTML page – controllere
Connection between
controllere
via
controllere controllere network connection controllere client MODBUS/TCP server / client controllere HTML page PC HTML data exchange
page
here
Overview HTML data exchange
With an integrated web server HTML pages of the controllere can be represented on a PC via an
Ethernet network by means of a standard browser. By integrating a Java applet in the HTML page data can dynamically be exchanged with the controllere. To do so, the applet uses the Modbus/TCP protocol.
HTML page switch
Ethernet
AC1353/54
Modbus/TCP server web server
AS-i master
file server
AS-Interface digital
I/O slaves
analogue
I/O slaves
Function
Project transmission and diagnosis via Ethernet interface
Setting up an own web page
An own web page is to be realised on the controllere. For this the following steps are required:
Step 1
Step 2
► Connect the devices via Ethernet (
)
► Set IP addresses and subnet mask (
page
)
Step 3
Step 4
Step 5
Step 6
► Open the HTML page in the browser (
page
)
► Address the file server via FTP (
)
► Edit the web page (
)
► Load and test the modified web page (
)
Here is the detailed description of the steps:
Step 1: Connect the devices via Ethernet
► Set up the Ethernet network by connecting the PC and the controllere to the hub (or switch).
► To do so, use common CAT5 Ethernet patch cables with an RJ45 connector on both sides.
Step 2: Set IP addresses and subnet mask
► Set appropriate IP addresses and subnet masks on the controllere and your PC
(methode
NOTE
In a local network the participants can only communicate if their IP addresses are from the same
"family".
Example: Subnet mask = 255.255.255.0
Then the IP addresses of the first 3 address groups (where "255" is) must be identical for all participants. The IP address may (and must) only be different in the last block (where "0" is)
(permitted values): 0…254).
Ask the network administrator for the specifications!
In our example we assume the following values:
Subnet mask = 255.255.255.0
IP address of the controllere = 192.168.10.11
IP address of the PC = 192.168.10.20
Set up the Ethernet network by connecting the PC and the controllere to the switch.
4-75
Function
Project transmission and diagnosis via Ethernet interface
Step 3: Open the HTML page in the browser
On delivery, a start page is stored in the web server of the controllere. This page is displayed when you access the IP address of the controllere with the HTTP protocol in a browser.
An example of calling the start page of the controllere with the IP address 192.168.10.11 is shown in the following figure.
► Enter "http://" and then the IP address of the controllere in the address bar.
> The following figure appears:
In this window:
A click on ...
Software update
enables ...
Update of the Ethernet driver software
...in this window:
Modbus Settings of the Modbus/TCP server
User Site
4-76
Calling the HTML page
In the following we will describe the adaptation of the contents:
Function
Project transmission and diagnosis via Ethernet interface
NOTE
To allow the web page to be updated it must be possible to run Java applets in the browser (e.g. by
Java 2 Runtime Environment 5.0).
Step 4: Address the file server via FTP
As shown in the following example the file server in the controllere can be called via the browser /
Explorer.
► Enter "ftp://" followed by the requested IP address of the controllere as search address:
4-77
Function
Project transmission and diagnosis via Ethernet interface
If RAM disk in the controllere <10.120:
> The following figure appears:
► User name = ftpuser
Do not enter a password
► Click [Login]
To all controllere devices the following applies:
> The browser opens a kind of Windows Explorer
► Open the directory pub under the requested IP address of the controllere
Then open the subdirectory WWW
> The following figure appears:
The file user.html contains the source code of the page accessed as example in step 3.
In the following you can adapt this page to your application.
4-78
Function
Project transmission and diagnosis via Ethernet interface
Step 5: Edit the web page
► Right-click the file name user.html
► Select [Edit the source code]
In the following we describe the device-specific particularities of the HTML program code. Please find a description of the HTML orders in the appropriate technical literature.
> The following figure appears (detail):
<html>
<head>
</head>
<body onLoad="LoadFct()">
<applet archive="CeMasterApplet.jar" code="CeMasterApplet" name="CeM" width="0" height="0"><param name="DEBUG" value="0"><param name="UNITID" value="1"></applet>
<script LANGUAGE=javascript> function LoadFct()
{ setTimeout("Timer()", 500);
} etc.
In the HTML file an HTML tag <applet> must be indicated.
Detail from the above example:
<applet archive=“CeMasterApplet.jar“ code=“CeMasterApplet“ name=“CeM“ width=“0“ height=“0“> <param name=“DEBUG“ value=“0“>
<param name=“UNITID“ value=“1“>
</applet>
Here, the applet which is saved and available in the Java archive CeMasterApplet.jar is integrated in a web page. name=“CeM“ param name=“UNITID“
The object created by the applet is assigned the name "CeM"
The parameter UNITID is passed to the applet value="1"
UNITID is assigned the value 1
With this applet the user can read or write all registers of the Modbus register model (
) to display data on a web page or to enter values via the web page in the Modbus registers of the controllere.
Functions available in the applet
public int getUnitID()
With this function the UnitID of the Java applets can be read. The applet tries to address the controllere with this UnitID. If the UnitID of the applet and the controllere do not match, a
Modbus connection is not set up.
public void setUnitID(int id) setUnitID
is used to change the UnitID of the applet.
public int readInputRegister(int ref) readInputRegister reads the register "ref" of the Modbus register model of the controllere. In
4-79
Function
Project transmission and diagnosis via Ethernet interface case of a fault the value "-1" is returned. The content of the Modbus register is returned in the value range 0…65535.
public void writeSingleRegister(int ref, int value) writeSingleRegister
is used to write a register of a Modbus register model. With the parameter "value" the value to be written is transmitted. If the value is greater than 65535, the bits which are more significant are ignored. With the parameter "ref" the Modbus register to be written is identified.
public int readDigitalInputSlave(int slave) readDigitalInputSlave
reads the data of a digital input slave. This is a comfort function which makes it unnecessary for the user to extract the slave data from the register value. The 4-bit value of the corresponding input slave is directly delivered. The parameter “slave" must contain a slave address in the range of 0...62. The slave addresses 32...62 are used for B slaves.
public int writeDigitalOutputSlave(int slave, int value) writeDigitalOutputSlave
enables to write the outputs of a digital output slave. With the parameter "slave" a slave address in the range of 0...62 is transmitted. The addresses 32...62 are used to address B slaves. In the parameter "value" the value to be written is transmitted.
public void setDebugMode(int level)
With the setDebugMode the output of debug messages of the Java applet to the Java console can be controlled. For the parameter "level" the values 0...9 are possible. Outputs are activated by setting a bit in the parameter "level".
public int getDebugMode()
The function getDebugMode delivers the currently set debug level value.
Call the function cyclically
Function calls in the script are normally only processed when a page is loaded. To obtain a cyclic update of the data the function "Timer" recalls itself always at the end with a defined delay (here: 250 ms): function LoadFct()
{ setTimeout("Timer()", 500); // Initial call of Timer()
} function Timer() // List of all textboxes whose values shall be updated regularly
{
... // Update of the data setTimeout("Timer()", 250);
}
//Restarts Timer() in 250 ms
4-80
Function
Project transmission and diagnosis via Ethernet interface
Step 6: Loading and testing the modified web page
There are two possibilities to open an application-specific web page:
The page shall be accessible via the link [User-Site] from the supplied start page:
A file user.html must be saved in the directory /pub/www.
The web page shall replace the supplied start page:
It must be saved as file index.html in the directoy /pub/www.
The page cannot be saved from the editor directly in the controllere. Therefore:
► First save the new page on the hard disk of the PC.
► Carry out the following steps to copy the user web page to the controllere:
Login to the controllere by means of ftp Step 4, page
).
Change to the directory pub.
If it does not yet exist: create directory www
Change to the directory www
Copy the file user.html or index.html from the PC to this directory.
If
changed:
Power the controllere off and on again
NOTE
After switching on the controllere it is checked whether a file user.html or index.html exists. If yes, a link to this file is created.
If none of these both files exists, a link to a default page is created.
4-81
Function
Project transmission and diagnosis via Ethernet interface
4-82
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 12 On this manual
- 12 What do the symbols and formats stand for?
- 12 Warning levels, signal words
- 12 Symbols and formats
- 12 What devices are described in this manual?
- 12 How is this manual structured?
- 12 Overview: where is what?
- 13 Safety instructions
- 13 General
- 13 What previous knowledge is required?
- 13 Functions and features
- 14 System requirements
- 14 Information concerning the device
- 14 Information concerning the software
- 14 Required accessories
- 15 Function
- 15 Overview
- 15 Data management
- 15 Which operating modes are there for the PLC in the controllere?
- 15 AS-Interface as well as project transmission and diagnosis via RS
- 15 Project transmission and diagnosis via Ethernet interface
- 15 Point-to-point connection
- 15 Overview point-to-point connection
- 15 Step 1: Connect the PC to the controllere
- 15 Step 2: Set IP addresses and subnet mask
- 15 Step 3: Select the target system and write the project
- 15 Step 4: Set the communication parameters
- 15 Step 5: Transmit and start the project
- 15 Step 6: Set-up, monitoring and diagnosis of the AS-i system
- 15 Step 7: Create the boot project and save the source code
- 15 Step 8: Transmit the source code from the controllere to the PC (service case)
- 15 Ethernet network connection
- 15 Overview Ethernet network connection
- 15 Excursion: Global network variables / EXP files
- 15 Overview: Steps for implementing an Ethernet network connection
- 15 Step 1: Connect the devices via Ethernet
- 15 Step 2: Set IP addresses and subnet mask
- 15 Step 3: Select the first target system and create a project
- 52 Step 4: Set the communication parameters
- 52 Step 5: Activate the network variable support
- 52 Step 6: Integrate libraries
- 52 Step 7: Complete and transmit the project (Global network variables)
- 52 Excursion: variable list identifier (COB ID)
- 52 Continuation of step
- 52 Step 8: Write projects for further controllere devices
- 52 Step 9: Transmit projects
- 52 Step 10: Test the global network variable transmission
- 52 MODBUS/TCP server / client
- 52 Overview MODBUS/TCP server / client
- 52 Valid Modbus addresses and their meaning
- 52 Modbus address for controllere PLC status
- 52 Modbus address for Modbus timeout
- 52 Modbus address for Modbus write timeout
- 52 Modbus address for "delete Modbus write timeout register
- 52 Modbus addresses of the digital slave inputs and outputs
- 52 inputs and outputs
- 52 Modbus addresses for the master flags
- 52 IEC addresses in the PLC of the controllere for the master flags
- 52 Modbus addresses for the analogue slave inputs and outputs
- 52 Status information of analogue slaves
- 52 and outputs
- 52 Modbus addresses for configuration data (CDI) of the slaves
- 52 of the slaves
- 52 Modbus addresses for parameter data of the slaves
- 52 of the slaves
- 52 Modbus addresses for the slave list LAS (list of active slaves)
- 52 (list of active slaves)
- 52 Modbus addresses for the slave list LDS (list of detected slaves)
- 52 (list of detected slaves)
- 52 Modbus addresses for the slave list LPF (list of slaves with periphery faults)
- 52 (list of slaves with periphery faults)
- 52 Modbus addresses for the slave list LPS (list of projected slaves)
- 52 (list of projected slaves)
- 52 Modbus addresses for the slave telegram error counters
- 52 error counter
- 99 Modbus addresses for the configuration error counter
- 99 error counter
- 99 Modbus addresses for the AS-i cycle counter
- 99 IEC addresses in the PLC of the controllere for the AS-i cycle counter
- 99 Modbus addresses for the request data of the host command channel
- 99 Modbus addresses for the response data of the host command channel
- 99 Modbus addresses for the fieldbus data from/to the PLC of the controllere
- 99 from/to the PLC of the controllere
- 99 Modbus addresses for the extended data from/to the PLC of the controllere
- 99 from/to the PLC of the controllere
- 99 Data exchange HTML page – controllere
- 99 Overview HTML data exchange
- 99 Setting up an own web page
- 99 Step 1: Connect the devices via Ethernet
- 99 Step 2: Set IP addresses and subnet mask
- 99 Step 3: Open the HTML page in the browser
- 99 Step 4: Address the file server via FTP
- 99 Step 5: Edit the web page
- 99 Functions available in the applet
- 99 Call the function cyclically
- 99 Step 6: Loading and testing the modified web page
- 100 Menu "Ethernet Setup
- 101 Operation
- 101 The Modbus command channel
- 101 Request from host
- 101 Response from controllere
- 101 Overview of the commands in the Modbus command channel
- 101 Command 0 (0#00): no execution of a command
- 101 Request from host
- 101 Response from controllere
- 101 Command 1 (0#01): Write parameters to a connected AS-i slave
- 101 Request from host
- 101 Response from controllere in the normal case
- 101 Response from controllere in the case of an error
- 101 Possible error codes
- 101 in the configuration
- 101 Request from host
- 101 Response from controllere in the normal case
- 101 Response from controllere in the case of an error
- 101 Possible error codes
- 111 Command 4 0#04): List of the projected AS-i slaves (LPS)
- 111 Request from host
- 111 Response from controllere in the normal case
- 111 Response from controllere in the case of an error
- 111 Possible error codes
- 111 Command 5 (0#05): Set the operating mode of the AS-i master
- 111 Request from host
- 111 Response from controllere in the normal case
- 111 Response from controllere in the case of an error
- 111 Possible error codes
- 111 Command 6 (0#06): Readdress a connected AS-i slave
- 111 Request from host
- 111 Response from controllere in the normal case
- 111 Response from controllere in the case of an error
- 111 Possible error codes
- 111 Command 7 (0#07): Set the auto address mode of the AS-i master
- 111 Request from host
- 111 Response from controllere
- 111 AS-i slave
- 111 Request from host
- 111 Response from controllere in the normal case
- 111 Response from controllere in the case of an error
- 111 Possible error codes
- 111 directly to / from 3 AS-i slaves in each case
- 111 Request from host
- 111 Response from controllere
- 111 Command 21 (0#15): Read the ID string of an AS-i slave with profile S
- 111 Request from host
- 111 Response from controllere in the normal case
- 111 Response from controllere in the case of an error
- 111 Possible error codes
- 111 protected mode
- 111 Request from host
- 111 Response from controllere
- 111 Protocol" in the "Safety at work" monitor
- 111 Request from host
- 111 Response from controllere in the normal case
- 111 Response from controllere in the case of an error
- 111 Possible error codes
- 111 profile S
- 111 Request from host
- 111 Response from controllere
- 152 profile S
- 152 Request from host
- 152 Response from controllere
- 152 profile S
- 152 Request from host
- 152 Response from controllere
- 152 CTT2 profile (S-7.5.5, S-7.A.5 or S-B.A.5)
- 152 Request from host
- 152 Response from controllere in the normal case
- 152 Response from controllerein the case of an error (error detected by AS-i master)
- 152 Possible error codes
- 152 Response from controllere in the case of an error (error detected by AS-i slave)
- 152 Possible CTT2 error codes
- 152 CTT2 profile (S-7.5.5, S-7.A.5 or S-B.A.5)
- 152 Request from host
- 152 Response from controllere in the normal case
- 152 Possible error codes
- 152 Response from controllere in the case of an error (error detected by AS-i slave)
- 152 Possible CTT2 error codes
- 152 AS-i slave with CTT2 profile (S-7.5.5, S-.7.A.5 or S-B.A.5)
- 152 Request from host
- 152 Response from controllere in the normal case
- 152 Possible error codes
- 152 Response from controllere in the case of an error (error detected by AS-i slave)
- 152 Possible CTT2 error codes
- 152 to an AS-i slave with CTT2 profile (S-7.5.5, S-7.A.5 or S-B.A.5)
- 152 Request from host
- 152 Response from controllere in the normal case
- 152 Possible error codes
- 152 Response from controllere in the case of an error (error detected by AS-i slave)
- 152 Possible CTT2 error codes
- 152 Request from host
- 152 Response from controllere
- 152 Command 54 (0#36): Read current parameters of a connected AS-i slave
- 152 Request from host
- 152 Response from controllere
- 161 Command 55 (0#37): Read current AS-i slaves
- 161 Request from host
- 161 Response from controllere
- 161 1(A)...15(A)
- 161 Request from host
- 161 Response from controllere
- 161 of the controllere
- 161 Request from host
- 161 Response from controllere
- 161 Command 97 (0#61): Carry out various settings in the controllere
- 161 Request from host
- 161 Response from controllere
- 161 Command 102 (0#66): Retrieve the status of the controllere display
- 161 Request from host
- 161 Response from controllere
- 161 Command 105 (0#69): Read the device properties of the controllere
- 161 Request from host
- 161 Response from controllere
- 162 Terms, abbreviations
- 163 Index