9.1 Technical Parameters

9.1.1 Electrical Part

TC500K3US-O User Manual

Input data (DC side)

Parameter description

Maximum DC voltage(Vdc)

PV grounding mode

MPPT voltage range of DC input(V)

Maximum PV array input power(kW)

Maximum input current(A)

 Output data (grid side)

Reference value

600

PV-grounding (ANSI requirements)

DC320 ~ DC580V(full load)

550

1600

Parameter description

Rated output power(kW) 500

Reference value

Rated grid voltage(Vac)

Allowable grid voltage range (three-phase)

Rated grid frequency(Hz)

Allowable grid frequency(Hz)

200

-12% ~ +10 %, i.e. 176Vac ~ 220Vac

60

59.8 (this operating point is adjustable) -60.5

Total current waveform distortion factor(%) <3 (rated power)

Control of power factor 0.9 (leading) ~ 0.9 (lagging)

9.1.2 Mechanical Part

Parameter description

Actual size (W × H × D) mm

Weight(kg)

Reference value

2370×2140×910

2300

57