INSTALLATION SECTION

Clearances

The boiler can be installed with the following clearances:

25 mm either side of the boiler

50 mm to the front of the boiler

300 mm below the boiler

200 mm above the boiler

The above clearances are minimum clearances, consideration must be given to allow adequate space for servicing.

The recommended servicing clearances are:

50 mm either side of the boiler

600 mm to the front of the boiler

300 mm below the boiler

200 mm above the boiler

Terminal position

The minimum acceptable spacings from the terminal to obstructions and ventilation openings are shown in diagram 5 below:

8

Diagram 5

Minimum dimensions (in mm) for the positioning of flue terminals

a Under a window . . . . . . . . . . . . . . . . . . . . . . . . 300 b Under an air vent . . . . . . . . . . . . . . . . . . . . . . . 300 c Under a gutter . . . . . . . . . . . . . . . . . . . . . . . . . . 75 d Under a balcony . . . . . . . . . . . . . . . . . . . . . . . . 300 f e From an adjacent window . . . . . . . . . . . . . . . . . 300

From an adjacent air vent . . . . . . . . . . . . . . . . . 300 g From vertical drain pipes or soil pipes . . . . . . . . 75 h From an external corner of the building . . . . . . 300 l i From an internal corner of the building . . . . . . . 300

From the ground or from another floor . . . . . . . 300 m Between two terminals vertically . . . . . . . . . . 1500 n Between two terminals horizontally . . . . . . . . . 300