YASKAWA iQpump1000
Manuals and User Guides for YASKAWA iQpump1000. We found 5 manuals for free downloads installation Guide, Setup Procedure, Quick start Guide, Manual
Below you will find brief information for iQpump1000 200 V Class (3/4 to 175 HP ND), iQpump1000 400 V Class (3/4 to 1000 HP ND), iQpump1000 600 V Class (2 to 250 HP ND). This user manual guides you through the proper installation, wiring, and operation of your Yaskawa iQpump1000 AC Drive Intelligent Pump Controller. It covers essential steps such as model identification, mechanical and electrical installation, start-up programming including real-time clock setup and application selection, and monitoring features. The document also provides specific instructions for simplex pump applications, motor rotation checks, and detailed parameter adjustments for optimal system performance.
Key Features
Intelligent pump control with dedicated application macros
Real-time clock for accurate operation and logging
Flexible start/stop and speed control methods (keypad, external switch)
Support for 2-Wire (4-20mA) and 3-Wire (0-10V) transducers
Configurable PI control for stable system pressure regulation
Sleep mode and Anti-No-Flow (ANF) detection for energy saving
Thrust Bearing function tailored for submersible pump motor protection
Auto Mode with Power Down Storage for automatic restart after power failure
Comprehensive system fault protection with automatic restart attempts
Parameter overview for quick setup and adjustment of pump-specific settings
Pages: 508 YASKAWA iQpump1000 installation Guide
Brand: YASKAWA Category: Measuring, testing & control Size: 23 MB
Languages: English
Table of contents
Open manualOther manuals and documents
Frequently Answers and Questions
How do I set up the real-time clock on the iQpump1000?
After the first power-up, the real-time clock setup screen will appear automatically. Use the navigation buttons on the digital operator to set the date and time, then press 'Enter' to save. Once set, this screen will not reappear unless parameter o4-17 is reset.
What should I do if the motor rotation direction is incorrect?
First, power down the iQpump and wait at least five minutes for the charge indicator to extinguish. Then, swap any two of the three output leads (U/T1, V/T2, W/T3) connected to the motor. Reapply power and recheck the motor direction.
How can I enable the iQpump1000 to automatically restart after a power failure?
To enable automatic restart in Auto mode when operating from the digital operator, set parameter P4-10 to '1' (Enabled). This stores the run status and initiates a run command upon power-up after a power failure.
What is the purpose of the Thrust Bearing function and how do I enable it?
The Thrust Bearing function is primarily used for submersible pumps to prevent excessive motor wear. To enable it, set the minimum motor frequency in parameter P4-11 (e.g., 30.0 Hz for a 1800 RPM motor running at 3600 RPM base speed).
How do I connect a feedback device (transducer) to the iQpump1000?
Ensure power is off, then remove the terminal cover. For a 2-wire, 4-20mA transducer, connect the output to terminal A3 and link AC-SN. For a 3-wire, 0-10V transducer, set the jumper inside the drive for 0-10V, connect the common signal to SN, and the output to A1.
How is the Anti-No-Flow (ANF) function configured and verified?
First, ensure system stability under normal operation. Adjust P2-25 to the actual delta pressure drop plus 1 PSI in a no-flow situation. Then, run the system, monitor U1-99 'ANF Timer' to ensure it increments and resets. Create a no-flow situation to verify the timer holds at P2-24 time before the pump goes to sleep.
Questions & Answers
F F M
How to configure the system pressure setpoint on the controller?
Set parameter Setpoint 1 (Q1-01) to match the required system pressure.