Below you will find brief product information for Master MPS MPT 10, Master MPS MPT 10 HC, Master MPS MPT 15, Master MPS MPT 15 HC, Master MPS MPT 20, Master MPS MPT 20 HC, Master MPS MPT 30, Master MPS MPT 30 HC, Master MPS MPT 40, Master MPS MPT 40 HC, Master MPS MPT 60, Master MPS MPT 60 HC, Master MPS MPT 60 D, Master MPS MPT 60 DHC, Master MPS MPT 80, Master MPS MPT 80 HC, Master MPS MPT 80 D, Master MPS MPT 80 DHC, Master MPS MPM 10, Master MPS MPM 10 HC, Master MPS MPM 15, Master MPS MPM 15 HC, Master MPS MPM 20, Master MPS MPM 20 HC, Master MPS MPM 30, Master MPS MPM 30 HC, Master MPS MPM 40, Master MPS MPM HC 40, Master MPS MPM 60, Master MPS MPM 60 HC, Master MPS MPM 80, Master MPS MPM 80 HC, Master MPS MPM 100, Master MPS MPM 100 HC. Master MPS is an Uninterruptible Power System (UPS), a device which supplies clean energy to the connected load, without any interruption due to disturbances in the mains power supply, including a total power failure. It is designed to protect the critical load from simple installations to more complex systems where a higher level of reliability and maintainability is required.
Key Features
On Line double conversion
Isolated inverter
Battery Care System
Easy source
Parallel configuration
Dual Bus System
Dynamic Dual Bus System
Stand-by mode
Remote control
Network management
Pages: 36 Riello UPS Master MPS MPM 60 Specification
Brand: Riello UPS Category: Uninterruptible power supplies (UPSs) Size: 848 KB
Languages: English
Table of contents
Open manualFrequently Answers and Questions
What is the technical classification of Master MPS?
Master MPS is classified VFI-SS-111 in conformity with standard IEC EN 62040-3.
What is the main purpose of the Master MPS?
Master MPS supplies clean energy to the connected load, without any interruption due to disturbances in the mains power supply, including a total power failure.
How many units can be connected in parallel?
Up to 8 UPSs can be connected in parallel.
Can the system function as a frequency converter?
Yes the system can function as a frequency converter, 50/60 Hz and vice versa, with or without battery.
What are the available operating modes?
The UPS can be set to operate in four operating modes: ON-LINE, STAND-BY ON, SMART ACTIVE and STAND-BY OFF.
What are the communication options available?
Two slots are available inside the device to house two of the following communication options: NetMan 102 Plus, Netman 202 Plus, MultiCom 302, MultiCom 352.
What is the input voltage range for this UPS?
The input voltage range varies depending on the model. You can find the specific ranges in the Technical Data tables at the end of these specifications.
Questions & Answers
A A A
How does the UPS Master MPS manage and maintain its batteries effectively?
The UPS Master MPS incorporates a Battery Care System that includes recharge with two voltage levels (IU1 U2), recharge voltage with temperature compensation, capability to recharge batteries with long autonomy, and battery testing for decay detection.
What input voltage characteristics does the UPS Master MPS support to ensure compatibility with various power sources?
The UPS Master MPS supports low distortion of input voltage (up to 3%) and compatibility with motor generators through features like power walk-in and battery inhibition.
What safety measures are in place for battery mode operation and overload conditions?
The UPS Master MPS provides double protection of the load in battery mode and features thermal overrating of the inverter to guarantee overload capacity.
How can the capacity of the UPS Master MPS system be expanded?
The system is expandable up to 8 units using Dual BUS and Dynamic Dual Bus systems.
What level of load protection does the UPS Master MPS offer by using an isolation transformer?
The UPS Master MPS Includes an isolation transformer downstream the inverter for load protection.
What are the primary differences between the HC, D, and DHC versions of the UPS Master MPS?
The differences between HC, D, and DHC versions of the UPS Master MPS mainly concern input characteristics, specifically harmonic currents and power factor.