R48-2000e3 Rectifier Data Sheet


Add to my manuals
2 Pages

advertisement

R48-2000e3 Rectifier Data Sheet | Manualzz

DC Power for

Business-Critical Continuity ™

eSure™ Rectifier

R48-2000e3

Key Features

High efficiency, above 96% – reduces power consumption for lower operating costs

Full output power (2kW) up to system and operating costs

High power density – reduced footprint allows installation in short-depth racks and cabinets

Wide input voltage range to operate in the most demanding environments

Hot pluggable – facilitates future expansions and easy maintenance

Compliant with global standards – delivers quality, performance and reliability no matter what the application or location demands

In addition to reducing power consumption and lowering operating cost, eSure™ high-efficiency rectifiers offer superior performance and uncompromised reliability.

Description

The 2000W high-efficiency eSure™ rectifier ( model R48-2000e3) is designed to convert standard AC supply voltages into stable nominal -48 V DC voltage that is adjustable to application needs. The R48-2000e3 i s a constant power rectifier designed with the latest

patented switchmode technology, using DSP (Digital Signaling Processor) functionality for efficient operation.

For a higher load capacity, rectifiers can be connected in parallel, and intelligent control can be added with the help of a separate controller.

Efficiency

98%

96%

94%

92%

90%

88%

86%

84%

10% eSure ™ Rectifier

Efficiency Curve eSure ™

Rectifier

20% 30% 40% 50% 60% 70% 80% 90% 100%

Load

2013.09

1

eSure ™ Rectifier R48-2000e3

Technical Specifications

AC Input

Input Voltage, Nominal

Input Voltage, Permitted Variation

Line Frequency

Max Input Current

Power Factor

THD (Total Harmonic Distortion)

200 to 250 VAC

85 to 300 VAC

45 to 65 Hz

12 A

>0.99 for 50%-100% load

≤5% for 50%-100% load at 208Vac, 220Vac, 230Vac, 240Vac

DC Output

Output Voltage, Adjustment Range -42 to -58 V DC

Output Power

Output Power, Derated for Input

Voltage

2000W Maximum

See diagram

Output Current

42A@-48VDC

Output Current Limit Set Point

Peak Efficiency

Temperature Derating

96.2%

Full output power up to +65°C at input voltage range

>200 - 300VAC ( >176 - 200VAC, +55°C)

Control and Monitoring

Rectifier Alarm and Signaling

Visual Indications

Alarm and status reported via CAN bus to system controller

Green LED: Normal Operation

Yellow LED: Alarm

Red LED: Failure

Environmental

Temperature Range, Operating

Temperature Range, Storage

Relative Humidity

Altitude

EMC

S a f e t y

-40 to 80°C,-40 to +176°F (See diagram for de-rating)

-40 to +70°C, -40 to +158°F

0 to 95%

2000 m, 6560 ft at full power

ETSI EN300 386: 2005, Class B. Other than telecom centers.

FCC CFR 47 Part 15, Class B conducted and radiated

EN55022, Class B conducted and radiated

CISPR22, Class B conducted and radiated

Telcordia GR-1089-CORE issue 6

U L 60950-1;EN 60950-1;IEC 60950

Diagrams

120

100

80

60

40

20

0

0

Output Power vs. Input Voltage at Tamb < 55 °C

176

85

300

50 100 150 200 250 300

Input Voltage (VAC)

350

120

100

80

60

40

20

0

-40

Output Power vs. Temperature at Uin > 200VAC

65 70

-20 0 20 40 60 80 100 120

Mechanics

Dimensions (H x W x D)

Weight

41x84.5x252.5mm/1.61x3.33x9.94 inches

1.13kg/2.49lbs

Other Parts

Controller Units See separate controller datasheet

Ordering Information

Part Number

1 R 4 8 2 0 0 0 e 3

Description

High efficiency eSure

™ r ectifier , -48VDC,2000W

EmersonNetworkPower.com/EnergySystems (North America)

EmersonNetworkPower.eu/EnergySystems (EMEA)

© Emerson Network Power Energy Systems North America 2013.

Business-Critical Continuity ™ , Emerson Network Power ™ , the Emerson Network Power logo, Emerson ® and Consider it Solved are service marks and trademarks of Emerson

Electric Co. EnergyMaster ™ , eSure ™ , NetPerform ™ , NetReach ™ , NetSpan ™ , NetSure ® and NetXtend ™ are trademarks of Emerson Network Power Energy Systems North America.

Output voltage vs. Output current, max. output power 2000 W

34.5

41.7

60

50

40

30

20

10

0

0 5 10 15 20 25 30 35 40 45 50

Output Current (A)

2 2013.09